Singapore 1800 622 1156 | Intl +65 6415 5353 | Welcome to our new site - found a bug? Please report it here
HX200HD-W
Wall Mount Dew Point/Temperature Transmitter 4 to 20 mA output only
Choose a Variant
Mounting Orientation
Measurement Type
Added to Your Shopping Cart
Configuration complete.
Please add to cart to keep it or exit the configuration
Please add to cart to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product Models| Brand |
|
| Accuracy | ± 1 °C (± 1.8 °F) |
| Accuracy Detail | ± 1.0°C from -20 to 40°C (-4 to 104°F); ± 3.0°C below -20°C (-4°F) |
| Additional Features 1 | NIST traceable calibration certificate included, Selectable C or F |
| Data Interface | N/A |
| Dew Point Temperature, Max | 40 °C |
| Dew Point Temperature, Min | -60 °C |
| Display Type | 2 line LCD |
| Electrical Output | 4 to 20 mA |
| Filter | Stainless Steel |
| GrossWeightValue | 1 |
| Length | 88.9 mm |
| Measurement Pressure, Min | 0 psi |
| Measurement Type | Temperature, Dew Point |
| Mounting Holes Center Length | 78.7 mm |
| Mounting Orientation | Wall Mount |
| Operating Temperature, Max | 200 °C |
| Output Detail | Single Output: 4 to 20 mA loop powered (relative humidity or dew point) |
| Pressure Limits | Up to 750 psi |
| Pressure Note | Maximum Sensor Pressure Rating |
| Probe Diameter | 1.27 cm |
| Probe Length | 10.16 cm |
| Process Connection Size | 1/2 in |
| Process Connection Type | NPT Male and Female |
| Relative Humidity | 1 to 95% |
| Resolution | 0.1 |
| Sensor Material | 304 Stainless Steel |
| Series ID | HX200-Srs-TRH-Sig-Cond |
| Supply Power Note | 4 to 20 mA loop powered, 2-wire 24 Vdc (typical) 12 to 28 Vdc |
| Supply Power Type | Loop Powered |
| Supply Voltage | 12 to 28 Vdc |
| Weight | 1.8 kg |
| Width | 63.5 mm |
| Country of Origin | United States |
| See All Specs | |
PDFs & Manuals