España 800 900 532 | Fuera de España +34 911 776 121 | Bienvenido a nuestro nuevo sitio web. ¿Encontró algún problema o error? Por favor, infórmelo aquí.
iLD-UTP-Series
Instrumentos y controladores con pantalla grande para temperatura y procesos
Large Display Meters and Controllers For Temperature and Process- UL and cUL Certified
- BIG Bright 2.25'(57.2 mm) or 4.00'(101.6 mm) LED Display
- Program to Change Colors: RED, AMBER, GREEN
- Temperature and Process Input Models
iLD-UTP-Series
Desde
SGD
3,095.99
Resumen del Producto
- A/D Conversion Dual Slope
- Accuracy ± 0.03 %
- CMRR 120 dB
- Decimal Selection 0,001, 0,01, 0,1, None
- Digital Filter Programmable
- Display Type 3.5 Digit LED
- Enclosure Ratings IP65, NEMA Type 1
- Impedance Input 10 MΩ for 100 mV; 1 MΩ for 1V or 10 Vdc
- Input Configuration Single-ended
- Current, Max 0 to 20 mA (5 Ω load)
- NMRR 60 dB
- Number of Inputs 1
- Offset Adjustment -1999 to 9999
- Operating Temperature, Max 40 °C
- Operating Temperature, Min 0 °C
- Polarity Unipolar
- Ramp and Soak Single Ramp & Soak
- Relative Humidity 90% RH Condensing
- Response Time 0.7 sec for 99.9%
- Sampling Rate 3 Hz (3 updates/second)
- Series ID iLD-UTP-Series
- Set Point Adjustment Menu Configurable
- Span Adjustment 0.001 to 9999 counts
- Supply Power Type AC
- Warm-Up to Rated Accuracy 60 min
Supported Applications
The Omega iLD-UTP and iLD-SP Series are large display meters and controllers designed for monitoring temperature, process variables, strain gage inputs, voltage, and current. The series supports universal temperature input via Thermocouples (K, J, T, E, R, S, B, C, N, J DIN) and RTDs (Pt 100, 500, 1000 Ω; 2, 3, or 4 wire). Process applications include DC voltage and current monitoring as well as strain gage measurements. Units are UL and cUL Certified and RoHS 2 Compliant.
Operating Conditions & Performance
The series operates within an ambient temperature range of 0 to 40°C (32 to 104°F) with a humidity rating of 90% RH non-condensing. Accuracy is specified as ±0.5°C for temperature inputs and ±0.03% reading for process, strain gage, and pressure transducer inputs. The step response time is 0.7 sec for 99.9%. Electrical isolation includes a test rating of 2300 Vac per 1 min between power to input/output (RS232 or RS485) and 500 Vac per 1 min between inputs.
Performance specifications include:
- A/D Conversion: Dual slope
- NMR: 60 dB
- CMRR: 120 dB
- Reading Rate: 3 samples per second
- Digital Filter: Programmable
Configuration Options
The iLD-UTP and iLD-SP series are available in two display sizes: the iLD24 with a 57 mm (2.25") 4-digit LED display, and the iLD44 with a 101 mm (4") 4-digit LED display. The programmable color options for the process variable, set point, and temperature units include RED, AMBER, and GREEN.
Input ranges supported by the series include:
- Voltage Inputs: 0 to 100 mVdc, -100 mVdc to 1 Vdc, 0 to 10 Vdc
- Current Input: 0 to 20 mA (5 Ω load)
The series supports optional control outputs for alarm and full PID control. Available output configurations include Form C SPDT mechanical relays (3A @ 120/240 Vac), Solid State Relays, DC pulse, and programmable analog outputs (0 to 20 mA, 0 to 100 mV, 0 to 1 V, 0 to 10 Vdc). Communication options include RS232, RS485, RS422, MODBUS, and Ethernet with an embedded Web server. Factory Scaling (-FS) is available as a no-charge option.
Mounting configurations allow for flush in panel or surface mounted installation. The enclosure provides NEMA 1 protection with an IP65 front bezel rating.
Key Product Differences
The series distinguishes between two primary input models:
- iLD-UTP (Universal Temperature and Process): Supports Thermocouples, RTDs, DC voltage, and DC current inputs. Accuracy is ±0.5°C for temperature and ±0.03% reading for process.
- iLD-SP (Strain Gage/Process): Optimized for Strain Gage and Process Voltage/Current inputs with an accuracy of 0.03% reading. This model supports optional excitation outputs of 5 Vdc @ 40 mA or 10 Vdc @ 60 mA in place of communication options.
Model numbers follow the format: iLD-UTP or iLD-SP - <Display Size> - <Control Outputs> - <Communication Options> - <Factory Scaling>. For example, a model with 2 relays and RS485 communication is designated iLD-UTP-33-C24.
PDFs y Manuales
Software y Controladores