  • Temperature/Process Input
  • Ramped On/Off Control
  • Five Ramp and Soak Profiles, Each up to 10 Segments
  • Rate of Change and Min or Max Display
CN1501-Series
From SGD 800.67
1/8 DIN Temperature and Process Profile Ramp and Soak Controller CN1501-Series CN1501-Series
loading all models
Product Overview
  • A/D Conversion 20,000 count, dual-slope integrating
  • Cutout Dimensions 45 x 92 mm
  • Decimal Selection 0,001, 0,01, 0,1, None
  • Dimensions Note Case (Bezel Dimensions and Depth): 65 x 117 x 178 mm (2.70 x 5.07 x 6.90"), all metal enclosure
  • Display Size 10 mm (.39 in)
  • Display Type 4 Digit LED
  • Display Type Note Red 7-segment LED display, 10 mm H (0.39") Display rate Variable-displayed as rate of change/time base
  • Form factor 1/8 DIN
  • Height 117 mm
  • Length 178 mm
  • Number of Control Outputs 6
  • Number of Inputs 1
  • On/Off Deadband 0 to FS
  • Proportional Band 0 to 100% of span
  • Reset 0 to 50 repeats/min
  • Sampling Rate 0 to 500 Hz (updates/second)
  • Scale Digital
  • Series ID CN1501-Series
  • Supply Power Note 120 Vac (60 Hz) standard; 220 Vac (50 Hz) and 15 Vdc @ 900 mA (optional)
  • Temperature Resolution None
  • Weight 1.24 kg
  • Width 65 mm

Supported Applications

The Omega CN1501 Series is a 1/8 DIN temperature and process profile ramp and soak controller designed for applications requiring programmable heating or cooling cycles. The unit combines ON/OFF control with PID precision to manage processes that require selectable heat/cool modes. It supports up to five different ramp and soak programs, each configurable with up to ten segments.

Key functional capabilities include:

  • Ramp and Soak profiling for temperature or process variables
  • Selectable heating or cooling applications via programmable heat/cool cycles
  • Manual hold and manual set-point entry modes
  • Tracking of maximum and minimum readings, run time, and setpoint deviation
  • Rate of change monitoring with optional rate alarms

Operating Conditions & Performance

The CN1501 Series accepts a wide range of input types including Thermocouples (J, K, T, E, R, S, B), RTDs (Pt 385/392), Thermistors (2252 Ω @ 25°C), and process signals for Current (4 to 20 mA), Voltage (0 to 10 Vdc), and Millivolt (0 to 100 mV). Measurement ranges vary by input type, spanning from -328°F (-200°C) up to 3300°F (1800°C).

Performance specifications are defined as follows:

  • Accuracy: ±1°C/2°F ±1 cnt for J, K, T, E thermocouples; ±3°C/6°F ±1 cnt for R, S, B thermocouples; ±1°C ±1 digit for RTD and Thermistor inputs.
  • Voltage Accuracy: 0.05% ±1 digit for the CN1501-V model (0 to 10 Vdc).
  • Resolution: 1°C/1°F for thermocouple or RTD inputs; 0.1°C/0.2°F for Thermistor inputs.
  • Cold Junction Compensation Error: +/- 0.5C max (10C to 40C).
  • A/D Conversion: 4 1/2 Digit (20000 count) with a dual slope integrating converter and typical conversion rate of 7/sec.

The controller features an all metal enclosure measuring 65 x 117 x 178 mm (2.70 x 5.07 x 6.90") and weighs 1.24 kg (2.75 lb). The display is a red 7-segment LED with 0.39 inch (10mm) digit height.

Configuration Options

The series offers extensive configuration options for power, output signals, and alarm functions to accommodate specific installation needs.

Power Supply Options

  • Standard: 120 Vac (60 Hz).
  • Suffix -1: 240 Vac power.
  • Suffix -2: 9 to 15 Vdc power.

Output and Alarm Configurations

The controller provides flexible output options including relays, open collector transistors, and DC pulse drivers. Standard outputs include a 5 Vdc drive @ 50 mA max (internal source) or Open Collector: 4 open collector outputs with a max sink capacity of 50 mA per output.

Ordering suffixes define specific alarm and timer configurations:

  • Suffix -3: Four 1 A alarm relays, 2 DC Pulse drivers for timers.
  • Suffix -4: 4 DC pulse drivers for alarms, 2 DC pulse for timers.

Relay outputs are specified as Single pole single throw (SPST), rated at 1 A @ 28 Vdc or 0.5 A @ 120 Vac resistive load.

Sensor and Input Selection

  • CN1501-TC: Thermocouple inputs (J, K, T, E).
  • CN1501-R/S/B: High temperature thermocouples (R, S, B).
  • CN1501-RTD: 2-wire RTDs with alpha coefficients of 0.00385 or 0.00392.
  • CN1501-TH: Thermistor input (2252 Ω @ 25°C).
  • CN1501-C/V/P: Process inputs for Current, Voltage, and Millivolt signals respectively.

Key Product Differences

The CN1501 Series is distinguished by its input type model codes (e.g., -TC, -RTD, -TH) which determine the measurement range and accuracy class. The series supports field programmable inputs for J, K, T, or E thermocouples in specific configurations.

Variations are further defined by power supply suffixes (-1 for 240 Vac, -2 for DC) and output configuration suffixes (-3 for relay-heavy alarm setups, -4 for pulse driver setups). Accessories include a noise suppression kit (CNQUENCHARC) compatible with 110 to 230 Vac systems and a 1/8 DIN panel punch (DPP-5).

Calibration is NIST traceable, with recalibration recommended at 12 months intervals. The unit displays 'OPEN TC' for open thermocouple indication and shows negative polarity indications where applicable.