Singapore 1800 622 1156 | Intl +65 6415 5353 | Welcome to our new site - found a bug? Please report it here
CN730-Series
1/4 DIN Temperature Controllers with Autotune, Alarms and RS485
Models In Stock
This item is discontinued. Please see the CND3-SERIES as a possible alternatives. Contact Engineering if you have any questions
- Dual Display
- Autotune
- RS-485 Communications
- Free Software
CN730-Series
From
SGD
346.49
Models In Stock
Product Overview
- Accuracy ± 0.25 %
- Accuracy Detail ± 0.25% span, ± 1 least significant digit
- Cutout Dimensions 92 × 92 mm
- Data Interface RS485 Modbus
- Depth Behind Panel 79.2 mm
- Display Type 4 Digit LED
- Display Type Note Two 4-digit, 7-segment, LEDs PV: Red, 19 mm H (0.75") SV: Green, 12.7 mm H (0.5")
- Enclosure Ratings IP66
- Form factor 1/4 DIN
- Height 96 mm
- Input Type Thermocouple, RTD, Thermistor
- Length 15.8 mm
- Measurement Type Temperature
- Measuring Range Type B: 100 to 1800°C Type S: 0 to 1700°C Type R: 0 to 1700°C Type N: -200 to 1300°C Type E: 0 to 600°C Type T: -20 to 400°C and -200 to 400°C Type J: -20 to 400°C and -100 to 850°C Type K: -200 to 1300°C and -200 to 500°C Type L: -200 to 500°C Type U: -200 to 800°C Pt100Ω RTD: 0 to 100°C, -20 to 500°C, -200 to 600°C
- Memory Backup Non-Volatile
- Number of Control Outputs 1
- Number of Inputs 1
- Operating Temperature, Max 50 °C
- Operating Temperature, Min 0 °C
- Series ID CN730-Series
- Supply Power Note 100 to 240 Vac, 50/60 Hz
- Supply Power Type AC
- Supply Voltage 100 to 240 Vac
- Weight 425 g
- Width 96 mm
Supported Applications
The Omega CN730 Series consists of microprocessor-based temperature process controllers designed for panel-mount installations. These units provide digital displays for Process Value (PV) and Set Value (SV), supporting thermocouple or RTD inputs to manage heating, cooling, or thermal regulation processes.
Key functional capabilities include:
- PID control with autotune functionality
- Dual alarm outputs
- RS-485 communication for system integration
- ON/OFF and manual tuning modes
Operating Conditions & Performance
The CN730 Series operates within an ambient temperature range of 0 to 50°C (32 to 122°F). The controllers feature a front panel enclosure rating of IP66. Accuracy is specified as ±0.25% span, ±1 least significant digit.
Measurement ranges vary by input type and sensor selection:
- B: 100 to 1800°C (212 to 3272°F)
- S/R: 0 to 1700°C (32 to 3092°F)
- N/K: -200 to 1300°C (-328 to 2372°F)
- E: 0 to 600°C (32 to 1112°F)
- T/J: -20 to 400°C (-4 to 752°F)
- L/U: -200 to 800°C (-328 to 1472°F) and -200 to 500°C (-328 to 932°F)
- Pt100Ω RTD: Ranges include 0 to 100°C (32 to 212°F), -20 to 500°C (-4 to 932°F), and -200 to 600°C (-328 to 1112°F)
Power supply requirements are AC 100-240V, 50/60 Hz. The unit weight is 425 g (15 oz).
Configuration Options
The series offers configurable output signals and communication options to match specific control architectures.
Output Configurations
- CN733: Relay output with RS485 communications
- CN732: DC pulse output with RS485 communications
- CN735: 4 to 20 mA output with RS485 communications
Physical Dimensions & Installation
The CN730 Series utilizes a standard panel cutout of 96 x 96 mm (3.78 x 3.78 in) with an overall bezel dimension of 15.8 mm depth (0.625"). The series includes the following terminal functions:
- Terminals 1, 2: DATA+ / DATA- (RS-485)
- Terminals 11, 12: L / N (AC Power)
- Alarm and Output terminals vary by model configuration
Accessories & Options
- CNQUENCHARC: Noise suppression RC snubber (2 leads), rated for 110 to 230 Vac
- CN7-485-USB-1: RS485 to USB mini-node converter
- Free CN7-A software available for configuration and monitoring
Key Product Differences
The primary distinction within the CN730 Series is the output signal type, which determines the model number suffix:
- CN733 models provide a mechanical relay output.
- CN732 models provide a DC pulse output.
- CN735 models provide an analog 4 to 20 mA current loop output.
All listed variants include RS-485 communication capability. The series is distinct from the CN710 and CN740 families, which feature different panel cutout dimensions (60 mm x 120 mm for CN710; 65 mm x 60 mm for CN740) but share similar input/output logic.
Installation notes specify that thermocouple or Class 2 wiring must not be run in the same conduit as power leads. For supply connections, No. 16 AWG or larger wires rated for at least 75°C are required. Screw torque for mounting should be set to 0.8 kgf-cm.