Esense-Room
Capteur de dioxyde de carbone, 0-2000 PPM, montage mural, sortie 0-10 VCC, 3 DEL, alarme sonore
Sensore di Anidride Carbonica, 0-2000 PPM, Montaggio a Parete, Uscita 0-10VDC, 3 LED, Allarme Acustico- Bureaux commerciaux
- Gymnases
- Centres commerciaux
- Auditoriums
- Théâtres
- Hôpitaux et écoles
- Ventilation à demande contrôlée et économiseurs
Esense-Room
À partir de
Aperçu du produit
- Précision ± 30 ppm ; ±3 %
- Précision Précision de la plage étendue >2 000 PPM : +/- 30 ppm et +/- 5 % de la lecture
- Indication d'alarme @ 1400 ppm, type 94 dB avec bouton de mise en sourdine
- Homologations Directive CEM 2014/30/UE
- Remarque sur l'étalonnage Calibration3 : Algorithme Senseair ABC (Correction Automatique de la Ligne de Base)
- Plage de mesure du CO2 0 à 2000 ppm
- Zone de couverture 7500 pi carrés
- Remarque sur les Dimensions Dimensions de la pièce : (H) 5,12” (130 mm) x (L) 3,35” (85,1 mm) x (P) 1,18” (30 mm)
- Matériau du boîtier Polycarbonate
- Remarque concernant le matériau du boîtier ABS, Indice de résistance au feu UL94V-0
- Caractéristiques nominales du boîtier UL94 V-0
- Option de construction du matériau aucun
- Environnement opérationnel Structures extérieures ou non chauffées
- Humidité de fonctionnement 0 à 95 % HR ; sans condensation
- Température de fonctionnement, max 122 °F
- Température de fonctionnement, min 32 °F
- Consommation électrique 1 W
- Répétabilité ±20 ppm ±1 % de la valeur mesurée
- Temps de réponse < 3 minutes temps de diffusion
- Durée de vie du capteur >15 ans
- Type du capteur Technologie de détection infrarouge à faisceau unique (NDIR)
- ID de série Esense-Room
- Température de stockage, max 122 °F
- Température de stockage, min -4 °F
- Tension d'alimentation 24 Vca/Vcc
- Temps de chauffe 1 minute (@ spécifications complètes 15 minutes)
- Poids 0.304 lb
- Dérive du zéro ± 0.3 %
Supported Applications
The ACI eSENSE Room series monitors carbon dioxide (CO₂) levels in school and office type environments, serving as an indicator of overall indoor air quality. The ESENSE-FAI model is designed for residential and commercial spaces including schools, office buildings, auditoriums, gymnasiums, shopping malls, and theaters. These transmitters are utilized with Building Automation or Demand Control Ventilation systems to manage climate control.
Operating Conditions & Performance
The series employs single beam Non-dispersive Infrared (NDIR) sensing technology. Standard measurement ranges cover 0 to 2000 ppm, with extended CO₂ ranges up to 10,000 ppm available via factory set or SADK Calibration Kit configuration. Accuracy is specified as ±30 ppm and ±3% of reading for the standard range; Extended Range Accuracy >2,000 PPM is +/− 30 ppm and +/- 5% of reading. Repeatability is listed at ±20 ppm ±1% of measured value.
Operating conditions require an ambient temperature between 32°F to 122°F (0°C to 50°C) with relative humidity from 0 – 95% RH Non-condensing. The sensor life exceeds 15 years in normal Indoor Air Quality applications, excluding corrosive environments. Response time is <10 seconds @ 30 cc/min flow rate and < 3 minutes diffusion time.
Accuracy definitions require a minimum of three (3) ABC periods (1 period = 8 days) of continuous operation. The Senseair ABC algorithm provides Automatic Baseline Correction, though building CO₂ levels must drop to 400 ppm some time during the week for this function; if occupied 24 hrs/day, ABC must be turned off.
Performance Specifications
- Sensing Method: Single beam Non-dispersive Infrared (NDIR)
- Warm-Up Time: 1 minutes (@ full specs 15 minutes)
- Annual Zero Drift: ± 0.3% of measurement range
- Operating Pressure Effect: +1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmosphere = 14.7 psi (1.013 KPa))
- Coverage Area: 7500 sq. ft. maximum
- Mounting Height: 4-6' off the floor
Configuration Options
The series offers configurable output signals, display options, and alarm features to meet specific control requirements.
Outputs & Signals
- ESENSE-R: Out 1: 0-10 VDC; Out 2: 2-10 VDC or 4-20 mA for 0 to 2000 ppm.
- ESENSE-R-LCD: Includes display with same output options as ESENSE-R.
- ESENSE-R-5-LCD: Features a 0-5 VDC Output option alongside the LCD display.
Housing & Display Options
- Enclosure Material: ABS with Flammability Rating UL94V-0.
- Display (Optional): 4 digits, 7 segments LCD with ppm indicator available on specific models.
- Audible Alarm & LEDs (ESENSE II FAI DISP only): Features a 94 Db audible alarm at 1400 ppm with a mute button. Visual indicators include Green LED (0-800 ppm), Yellow LED (800 - 1400 ppm), and Red LED (>1400 ppm).
- Dimensions: Room dimensions are (H) 5.12" (130 mm) x (W) 3.35" (85.1 mm) x (D) 1.18" (30 mm).
Calibration & Accessories
- SADK Calibration Kit: Allows changes to be made using the SADK Calibration Kit and UIP5 software.
- Custom Calibration Gas: Available via item number 140970 (A/CUSTOM CAL GAS*).
- Software: Free Software Download (UIP5) available by contacting ACI.
Key Product Differences
The series distinguishes between standard transmitters and models with integrated displays or audible alarms. The ESENSE-R model provides dual analog outputs without a display, while the ESENSE-R-LCD adds a 4-digit LCD screen showing CO₂ values in ppm. The ESENSE II FAI DISP variant includes an acoustic alarm that activates when CO₂ exceeds 1400 ppm and can be silenced for 30 minutes via a push button.
Storage temperature ranges differ by model: the standard ESENSE-R supports -40 to 158°F (-40 to 70°C), whereas the ESENSE-R-LCD is rated for -4 to 122°F (-20 to 50°C). Weight varies slightly, with the ESENSE-R at 0.294 lbs (0.133 kg) and the LCD-equipped models at 0.304 lbs (0.138 kg).
Electrical connections utilize 0.00232 in² (1.5 mm²) screw terminals, powered by a supply of 24 VAC/VDC ±20%; 50/60Hz (Half-wave rectified). Power consumption is <1W.