Passer à la recherche Passer au contenu principal Passer à la navigation

Besoin d'aide? Appelez-nous: 1-800-663-4209

Nous avons remarqué que vous êtes dans , veuillez visiter votre site local en cliquant sur le lien ci-dessous pour des offres et un support régionaux.

PRTXI

Sonde RTD industrielle avec IO-Link, 4 à 20 mA et sortie commutée

Industrial RTD Probe with IO-Link, 4 to 20 mA, and Switched Output
Modèles en stock
  • IO-Link capable switching output and a 4-20mA analog output
  • Scalable temperature range from -50 to 200°C (-58 to 392°F)
  • Designed for industrial applications
  • Rugged 316L Stainless Steel housing with a variety of threaded process connections and probe lengths
PRTXI
À partir de C$ 418.26
Modèles en stock
Industrial RTD Probe with IO-Link, 4 to 20 mA, and Switched Output PRTXI PRTXI
loading all models
Aperçu du produit
  • Accuracy Class A
  • Accuracy Detail Full Measuring Range ± 0.55 °C (0.99°F) Scaled Measuring Range ± [0.215 °C (0.39 °F) + 0.134 % x (Measuring Span)]
  • Certifications CE, UKCA
  • Data Interface IO-Link
  • Electrical Output 4 to 20 mA
  • Enclosure Ratings IP67, IP68, IP69K
  • Enclosure Ratings Note 316L Stainless Steel, IP67/IP68/IP69K rated
  • Operating Temperature, Max 85 °C
  • Operating Temperature, Min -40 °C
  • Operating Voltage, Max 30 VDC, 30 V
  • Operating Voltage, Min 15 VDC, 15 V
  • Operating Voltage Note 15 to 30 VDC (IO-Link/Switch); 10 to 30 VDC (Analog)
  • Output Note IO-Link Communication / PNP Switch (200 mA) / Analog 4-20 mA
  • Process Temperature, Max 200 °C
  • Process Temperature, Min -50 °C
  • RTD Type 100 Ω Pt Sensor
  • Series ID PRTXI
  • Sheath Material 316L Stainless Steel
  • Temperature Sensor Type RTD
  • Thermocouple Type N/A

Supported Applications

The Omega PRTXI series is an industrial RTD temperature probe built for process temperature measurement in manufacturing and process environments. Each transmitter pairs a Pt100 Class A sensing element with a 316L stainless steel probe and housing, making it suitable for direct immersion and insertion measurement in tanks, vessels, piping, and industrial equipment.

Because every unit is IO-Link capable, the series fits applications that call for bi-directional, point-to-point communication of process data and sensor configuration. The scalable 4 to 20 mA analog output and an integrated PNP switch let the same probe serve both continuous analog monitoring and simple on/off switching, so the PRTXI can be integrated into new digital installations or into existing analog control loops.

Operating Conditions & Performance

The PRTXI series measures process temperatures over a range of -50 to 200 °C (-58 to 392 °F) using a Pt100 Class A RTD element. Over the full measuring range the accuracy is ± 0.55 °C (0.99°F). When the output is scaled, the accuracy is ± [0.215 °C (0.39 °F) + 0.134 % x (Measuring Span)].

Response time depends on probe diameter: T90 = 2 sec for the 1/8" and 3/16" diameters, and 4 sec for the 1/4" diameter, measured in water. The electronics operate across an ambient temperature range of -40 to 85 °C (-40 to 185 °F) and at relative humidity below 95%.

  • Operating voltage: 15 to 30 VDC for the IO-Link/Switch output; 10 to 30 VDC for the analog output, protected against reverse polarity.
  • Housing construction: 316L Stainless Steel, rated IP67/IP68/IP69K.
  • Output: IO-Link Communication, PNP Switch (200 mA), and Analog 4 to 20 mA.
  • Certifications: CE, UKCA.

Configuration Options

Every PRTXI model shares the same Pt100 Class A sensing element, 316L stainless steel wetted and housing materials, and the combined IO-Link, PNP switch, and 4 to 20 mA output set. Models differ along four ordering dimensions, so a specific configuration can be matched to the mounting point and thermal response a process requires.

Process Connection

Tapered NPT threads are offered in 1/4" NPT, 3/8" NPT, and 1/2" NPT, while cylindrical parallel threads are offered as G 1/4", G 3/8", and G 1/2".

Probe Diameter and Response

Diameters of 1/8", 3/16", and 1/4" are available. The smaller 1/8" and 3/16" diameters reach T90 = 2 sec, whereas the 1/4" diameter reaches T90 = 4 sec, allowing the choice between faster response and a more robust stem.

Probe Length

Insertion lengths of 2", 3", 4", 6", and 12" cover shallow and deep installations, and custom lengths are available upon request.

Key Product Differences

Each catalog number encodes, in order, the process connection, the probe diameter, the probe length, and the output. For example, PRTXI-1/4N-1/8-6-IO is an RTD Temperature Transmitter with a 1/4" NPT process connection, a 1/8" probe diameter, and a 6" probe length.

Combining the six process connections, three probe diameters, and five standard lengths yields the full orderable lineup. Representative configurations include:

  • PRTXI-1/4N-1/8-6-IO — 1/4" NPT connection, 1/8" diameter, 6" length.
  • PRTXI-1/2N-1/4-12-IO — 1/2" NPT connection, 1/4" diameter, 12" length.
  • PRTXI-G1/2-3/16-2-IO — G 1/2" connection, 3/16" diameter, 2" length.
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;

2 part question about the PRTXI. 1. Is it possible to scale the 4-20mA transmitter and set up the PNP switch OTHER THAN THOUGH io-link? e.g. is there PC software/ USB lead? Under "Manuals & Downloads" there is software, but there's only 4 jpg's & 1 XML

Asked by: Greggles the kiwi
Thank you for the inquiry. Unfortunately this device has only the IO Link and mA out operating modes. Details in the "Manuals & Downloads" are used with IO Link set up. Best regards OMEGA
Answered by: Norwalk_AE RS
Date published: 2024-11-01
  • y_2026, m_8, d_26, h_8CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_1
  • loc_en_CA, sid_PRTXI-1-2N-1-4-12-IO, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 4ms
  • QUESTIONS, PRODUCT
fr-CA
en_CA
Enregistrer la configuration