Esense-Room

Carbon Dioxide Sensor, 0-2000 PPM, Room Mount, 0-10VDC Output, 3 LEDs, Audible Alarm

  • Commercial Office Buildings
  • Gymnasiums
  • Shopping Malls
  • Auditoriums
  • Theaters
  • Hospitals & Schools
  • Demand Control Ventilation & Economizers
Esense-Room
From
Carbon Dioxide Sensor, 0-2000 PPM, Room Mount, 0-10VDC Output, 3 LEDs, Audible Alarm Esense-Room Esense-Room
loading all models
Product Overview
  • Accuracy ± 30 ppm, ±3 %
  • Accuracy Detail Extended Range Accuracy >2,000 PPM: +/- 30 ppm and +/- 5% of reading
  • Alarm Indication @ 1400 ppm, Typ 94 Db w/ Mute button
  • Applications Air and HVAC, Building and Maintenance
  • Approvals EMC Directive 2014/30/EC
  • Calibration Note Calibration3: Senseair ABC algorithm (Automatic Baseline Correction)
  • CO2 Measurement Range 0 to 2000 PPM
  • Coverage Area 7500 sq ft
  • Dimensions Note Room Dimensions: (H) 5.12” (130 mm) x (W) 3.35” (85.1 mm) x (D) 1.18” (30 mm)
  • Enclosure Material Polycarbonate
  • Enclosure Material Note ABS, Flammability Rating UL94V-0
  • Enclosure Ratings UL94 V-0
  • Material Construction Option none
  • Operating Environment Outdoor or Non-Heated Structures
  • Operating Humidity 0 to 95% RH, non-condensing
  • Operating Temperature, Max 122 °F
  • Operating Temperature, Min 32 °F
  • Power Consumption 1 W
  • Repeatability ±20 ppm ±1% of measured value
  • Response Time < 3 minutes diffusion time
  • Sensor Life >15 years
  • Sensor Type Single beam infrared sensing technology (NDIR)
  • Series ID Esense-Room
  • Storage Temperature, Max 122 °F
  • Storage Temperature, Min -4 °F
  • Supply Voltage 24 Vac/Vdc
  • Warm Up Time 1 minutes (@ full specs 15 minutes)
  • Weight 0.304 lb
  • Zero Drift ± 0.3 %

Supported Applications

The ACI eSENSE Room series monitors carbon dioxide (CO₂) levels in school and office type environments, serving as an indicator of overall indoor air quality. The ESENSE-FAI model is designed for residential and commercial spaces including schools, office buildings, auditoriums, gymnasiums, shopping malls, and theaters. These transmitters are utilized with Building Automation or Demand Control Ventilation systems to manage climate control.

Operating Conditions & Performance

The series employs single beam Non-dispersive Infrared (NDIR) sensing technology. Standard measurement ranges cover 0 to 2000 ppm, with extended CO₂ ranges up to 10,000 ppm available via factory set or SADK Calibration Kit configuration. Accuracy is specified as ±30 ppm and ±3% of reading for the standard range; Extended Range Accuracy >2,000 PPM is +/− 30 ppm and +/- 5% of reading. Repeatability is listed at ±20 ppm ±1% of measured value.

Operating conditions require an ambient temperature between 32°F to 122°F (0°C to 50°C) with relative humidity from 0 – 95% RH Non-condensing. The sensor life exceeds 15 years in normal Indoor Air Quality applications, excluding corrosive environments. Response time is <10 seconds @ 30 cc/min flow rate and < 3 minutes diffusion time.

Accuracy definitions require a minimum of three (3) ABC periods (1 period = 8 days) of continuous operation. The Senseair ABC algorithm provides Automatic Baseline Correction, though building CO₂ levels must drop to 400 ppm some time during the week for this function; if occupied 24 hrs/day, ABC must be turned off.

Performance Specifications

  • Sensing Method: Single beam Non-dispersive Infrared (NDIR)
  • Warm-Up Time: 1 minutes (@ full specs 15 minutes)
  • Annual Zero Drift: ± 0.3% of measurement range
  • Operating Pressure Effect: +1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmosphere = 14.7 psi (1.013 KPa))
  • Coverage Area: 7500 sq. ft. maximum
  • Mounting Height: 4-6' off the floor

Configuration Options

The series offers configurable output signals, display options, and alarm features to meet specific control requirements.

Outputs & Signals

  • ESENSE-R: Out 1: 0-10 VDC; Out 2: 2-10 VDC or 4-20 mA for 0 to 2000 ppm.
  • ESENSE-R-LCD: Includes display with same output options as ESENSE-R.
  • ESENSE-R-5-LCD: Features a 0-5 VDC Output option alongside the LCD display.

Housing & Display Options

  • Enclosure Material: ABS with Flammability Rating UL94V-0.
  • Display (Optional): 4 digits, 7 segments LCD with ppm indicator available on specific models.
  • Audible Alarm & LEDs (ESENSE II FAI DISP only): Features a 94 Db audible alarm at 1400 ppm with a mute button. Visual indicators include Green LED (0-800 ppm), Yellow LED (800 - 1400 ppm), and Red LED (>1400 ppm).
  • Dimensions: Room dimensions are (H) 5.12" (130 mm) x (W) 3.35" (85.1 mm) x (D) 1.18" (30 mm).

Calibration & Accessories

  • SADK Calibration Kit: Allows changes to be made using the SADK Calibration Kit and UIP5 software.
  • Custom Calibration Gas: Available via item number 140970 (A/CUSTOM CAL GAS*).
  • Software: Free Software Download (UIP5) available by contacting ACI.

Key Product Differences

The series distinguishes between standard transmitters and models with integrated displays or audible alarms. The ESENSE-R model provides dual analog outputs without a display, while the ESENSE-R-LCD adds a 4-digit LCD screen showing CO₂ values in ppm. The ESENSE II FAI DISP variant includes an acoustic alarm that activates when CO₂ exceeds 1400 ppm and can be silenced for 30 minutes via a push button.

Storage temperature ranges differ by model: the standard ESENSE-R supports -40 to 158°F (-40 to 70°C), whereas the ESENSE-R-LCD is rated for -4 to 122°F (-20 to 50°C). Weight varies slightly, with the ESENSE-R at 0.294 lbs (0.133 kg) and the LCD-equipped models at 0.304 lbs (0.138 kg).

Electrical connections utilize 0.00232 in² (1.5 mm²) screw terminals, powered by a supply of 24 VAC/VDC ±20%; 50/60Hz (Half-wave rectified). Power consumption is <1W.