Esense-Outdoor-Series
Sensore di anidride carbonica, 0-2000 PPM, aria esterna, uscita 0-10VDC, 3 LED, allarme acustico
- Strutture esterne o non riscaldate
Esense-Outdoor-Series
Da
Panoramica del Prodotto
- Accuratezza ± 30 ppm, ±3 %
- Accuratezza Dettagli Precisione a Gamma Estesa >2.000 PPM: +/- 30 ppm e +/- 5% della lettura
- Approvazioni Direttiva EMC 2014/30/UE
- Nota sulla calibrazione Calibrazione3: algoritmo Senseair ABC (Correzione Automatica della Linea di Base)
- Campo di misura CO2 Da 0 a 2000 PPM
- Dimensioni Nota Dimensioni della stanza: (A) 7,62” (193,55 mm) x (L) 4,63” (117,60 mm) x (P) 2,44” (61,98 mm)
- Tipologia Display N/A
- Collegamento elettrico Terminale a vite
- Potenza elettrica Da 0 a 20 mA, da 4 a 20 mA, da 0 a 10 Vcc, da 2 a 10 Vcc
- Materiale della custodia Policarbonato
- Nota sui materiali della custodia IP65, Classe di infiammabilità UL94V-0
- Classificazioni della custodia IP65, UL94 V-0
- Opzione di costruzione dei materiali nessuna
- Orientamento di montaggio Aria esterna
- Ambiente operativo Strutture esterne o non riscaldate
- Umidità di funzionamento Da 0 a 95% di umidità relativa, senza condensa
- Temperatura di esercizio, max 115 °F
- Temperatura di esercizio minima -22 °F
- Consumo energetico 11 W
- Ripetibilit ±20 ppm ±1% del valore misurato
- Tempo di risposta < 3 minuti tempo di diffusione
- Durata del sensore >15 anni
- ID serie Esense-Outdoor-Series
- Temperatura di stoccaggio, max 122 °F
- Temperatura di stoccaggio, min. -4 °F
- Tensione di alimentazione 24 V CA/CC
- Tempo di riscaldamento 1 minuto (@ specifiche complete 15 minuti)
- Peso 1.4 lb
- Deriva dello zero ± 0.3 %
Supported Applications
The ACI eSENSE Outdoor Series is a carbon dioxide (CO₂) transmitter designed for outdoor environments and non-heated structures. The device utilizes Infrared (NDIR) waveguide technology with Automatic Baseline Correction (ABC) to monitor CO₂ levels in ambient air.
Operating Conditions & Performance
The series operates within an ambient temperature range of -22°F to 115°F (-30°C to 46°C). It is rated for humidity from 0 to 95% RH (non-condensing) and features a storage temperature range of -4 to +122 °F. The standard measurement range covers 0 to 2,000 ppm CO₂ with an accuracy of ±30 ppm and ±3% of reading; extended ranges up to 10,000 ppm are available via factory set or SADK Kit with an accuracy of ±30 ppm and ±5% of reading. Repeatability is specified as ±20 ppm ±1% of measured value.
Response time (T₁/ₑ) is < 10 seconds @ 30 cc/min flow rate, or < 3 minutes diffusion time. The sensor life expectancy exceeds 15 years with no maintenance required under normal conditions. Pressure dependence affects the reading by +1.6% per 0.145 psi (1 kPa) deviation from normal pressure.
Configuration Options
The eSENSE Outdoor transmitter is housed in a Poly Carbonate enclosure with an IP65 rating and UL94V-0 flammability classification. The unit includes side ventilation breathers to support outdoor airflow and an integrated heater controlled by an inline thermostat.
- Heating System: An internal 24 VAC heater activates at temperatures of 39°F (4°C) or below to prevent ice crystal accumulation in the Optical Bench Assembly. Power consumption is <1W for the sensor and up to 10W when heating, with a maximum total power draw of 11W.
- Outputs: The device provides two analog outputs: Out 1 delivers 0-10 VDC for 0 to 2,000 ppm; Out 2 is configurable for 4-20 mA or 2-10 VDC (also covering the 0 to 2,000 ppm range). Status signals include ERROR and NOT READY states.
- Power Supply: Requires 24 VAC/VDC ±20% at 50/60 Hz. The input supports half-wave rectified power.
- Electrical Connections: Utilizes screw terminals rated for 1.5 mm² (0.00232 in²) wire, accommodating power inputs and voltage outputs.
Key Product Differences
The primary model is the ESENSE-OUTDOOR (Item # 135028), which includes the heated outdoor sensor configuration. The series supports extended CO₂ ranges up to 10,000 ppm when configured with a factory set or SADK Calibration Kit (Item # 130502). Custom calibration services are available for IP54 housings only.
Accuracy specifications require the device to complete minimum three ABC periods (where one period equals 8 days) of continuous operation. The Senseair ABC algorithm is standard, though it requires building CO₂ levels to drop to 400 ppm periodically; if a facility operates continuously without this drop, ABC must be disabled.