Need assistance? Call us: 1-800-663-4209
HX92B-Srs-RH-Sig-Cond
Relative Humidity Signal Conditioner/Transmitter with Probe
Models In Stock
- 4 to 20 mA, 0 to 1 Vdc, 0 to 5 Vdc or 0 to 10 Vdc Outputs
- Accurate to ± 2.5% (20 to 80% Relative Humidity)
- Rugged Industrial Splashproof Enclosure NEMA 13 (IP54)
- Duct Mount Kit Included with Duct Mount and Remote Probe Models
HX92B-Srs-RH-Sig-Cond
From
$
458.89
Models In Stock
Product Overview
- Accuracy ± 4 %
- Cable Diameter 6.73 mm
- Enclosure Ratings IP54
- Measurement Type Humidity
- Relative Humidity 0 to 100% RH
- Relative Humidity Response Time 8 sec
- Repeatability ± 0.1% RH
- Sampling Rate 0.25 Hz (4 seconds between updates)
- Series ID HX92B-Srs-RH-Sig-Cond
- Supply Power Type DC
- Temperature Measurement, Max 75 °C
- Temperature Measurement, Min -30 °C
- Wire Gauge 22 to 14 AWG
Supported Applications
The Omega HX92B Series Relative Humidity Signal Conditioner/Transmitter with Probe provides remote and on-site monitoring of relative humidity. The series delivers a linearized and temperature compensated output signal calibrated to a 0 to 100% RH scale, suitable for applications requiring precise environmental sensing.
Operating Conditions & Performance
The HX92B Series operates within a process temperature range of -30 to 75°C (-22 to 167°F). Accuracy varies by humidity level: ±2.5% from 20 to 80% RH, ±3.5% from 5 to 20% and 80 to 95% RH, and ±4% from 0 to 5% and 95 to 100% RH. Repeatability is specified as ±0.1% RH, with a typical response time of 8 seconds.
The enclosure provides NEMA 13 (IP54) protection for the electronics. The digital sensor element is protected by a stainless steel mesh type filter that is easily removable for cleaning. Approvals include CE and UKCA; NIST certification is available as an optional feature.
Configuration Options
The series supports multiple output signal configurations, mounting styles, and probe types to accommodate diverse installation requirements.
- Output Signals: 4 to 20 mA (scaled for 0 to 100% RH), 0 to 1 Vdc, 0 to 5 Vdc, or 0 to 10 Vdc. Current output models enable placement of the transmitter at a remote location virtually any distance away from the measuring device.
- Mounting Configurations: Wall mount (standard), Duct mount (-D suffix), and Remote probe (-RP1 suffix).
- Sensor Probes: Standard short probes, field replaceable remote probes with 3 m (10') cable and M12 connector (TH-RP), or field replaceable short probes measuring 71.88 L mm (2.83") (TH-SP).
- Housing & Connections: Gray polycarbonate enclosure with a liquid-tight nylon gland featuring a neoprene seal for cables ranging from 2.29 to 6.73 mm (0.09 to 0.265") diameter. Internal connections utilize a 5-position terminal block accepting 14 to 22 gauge wire.
- Power Supply: Models with 4 to 20 mA, 0 to 1 Vdc, and 0 to 5 Vdc outputs require 9 to 30 Vdc @ 50 mA. The 0 to 10 Vdc output requires 12 to 30 Vdc @ 50 mA.
Key Product Differences
The HX92B Series is differentiated by mounting type, probe configuration, and replaceability of the sensor element:
- HX92B(*) (Wall Mount): Standard wall mount relative humidity transmitter. Models with suffixes C, V0, V1, or V2 include a field-replaceable sensor probe.
- HX92B(*)-D (Duct Mount): Duct mount configuration designed for installation in air handling ducts. These models do not feature a replaceable sensor probe and are supplied with an included duct mounting kit.
- HX92B(*)-RP1 (Remote Probe): Includes a remote probe with 3 m (10') cable and M12 connector. The sensor probe is field-replaceable, and the unit includes a duct mounting kit.
Model numbering follows the pattern HX92B(*) - - , where output codes are C (4 to 20 mA), V0 (0 to 1 Vdc), V1 (0 to 5 Vdc), and V2 (0 to 10 Vdc). Weights vary by configuration: HX92B(*) is 124 g (4.4 oz); HX92B(*)-D is 132 g (4.7 oz); and HX92B(*)-RP1 is 230 g (8.1 oz).
PDFs & Manuals
Show Ratings & Reviews
Rated 5 out of
5
by
Bon007 from
Great response time
I bought this about a month ago I'm so glad I did.
Date published: 2018-02-05
Rated 5 out of
5
by
Supermaint from
Not so great/Excellent!
I was not happy with the service department. I called and asked what would be a good replacement for the HX92A, which has been discontinued, and was told that I should order the HX93BDC.. But when I looked it up, it was not at all what I needed, so I went through the Omega catalog and found the HX92B, which is exactly what I needed. I am very happy with the HX92B, as there is no longer any need to check the calibration (not even possible, in fact), and also due to the fact that this model has a replaceable sensor, which is certainly the most likely part to ever fail. It worked perfectly. Thank you!
Date published: 2018-05-18
Is this 4-20mA loop powered. Do I need 4 wires? 2 for analog and 2 for dc power or just 2 for analog that powers the unit also?
Hi Brian1,
Thank you for the inquiry. The HX92BC is a 2 wire loop powered device.
Best regards
OMEGA
Date published: 2021-02-21
Can i order a replacement probe for the HX92BC transmitter?
Hi Radius
Thank you for the inquiry. Yes, the replacement probe is available. Part# is TH-SP
Best regards
OMEGA
Date published: 2022-07-27
Is there any Hysteresis or delay in the switching once humidity is sampled?
The Humidity is measured continuously and instantly outputs an Analog DC Voltage or Current which is relative to the reading.
Date published: 2020-06-22
Does the HX92BV1 come with the probe?
Hi, Yes, this is a complete unit. Our Tech Support engineer has emailed you the specification sheet to provide any additional information you may need. Thanks for connecting with Omega.
Date published: 2019-06-25
i would like to know if i need to calibrate the instrument if i use it with plc
Thank you for your inquiry. The unit is shipped fully calibrated, no adjustments required.
Date published: 2020-02-12