RH-Combo-Room-Nickel
Relative Humidity Room with Nickel RTD Sensor
- Humidification
- Dehumidification
- Monitoring Indoor Space Humidity
- Clean Rooms
- Hospitals
- Process Control
- Laboratories
- Museums
- Schools
- Office Buildings
- Data Centers
- ESD (Anti-Static) Control
RH-Combo-Room-Nickel
From
$
365.00
Product Overview
- Display Type N/A
- Electrical Connection Screw Terminal
- Electrical Output 4 to 20 mA, 0 to 5 Vdc, 0 to 10 Vdc
- Enclosure Material ABS Plastic
- Filter Hydrophobic Filter
- Height 4.5 in
- Length 2.75 in
- Current, Max 8 mA
- Measurement Type Humidity
- Operating Temperature, Max 60 °C
- Operating Temperature, Min 1.5 °C
- Output Detail 0-5 VDC: 12 - 40 VDC / 18 - 28 VAC
- Relative Humidity 0 to 95%
- Relative Humidity Sensor Type Capacitive with Hydrophobic Filter
- Repeatability 0.5% RH,± 0.05°C
- Response Time 20 Seconds Typical
- Sensitivity 0.1% RH
- Series ID RH-Combo-Room-Nickel
- Stability RH Stability: Less than 2% drift / 5 years, Nickel RTD Sensor Accuracy: 32°F (0°C): +/-0.72°F (0.4°F); 70°F (21.1°C): +/-0.34°F (0.17°C); 130°F (54.4°C): +/-1.00°F (0.56°C)
- Storage Temperature, Max 65 °C
- Storage Temperature, Min -40 °C
- Supply Power Type DC
- Supply Voltage 24 Vdc
- Temperature Sensor Type Nickle RTD
- Tightening Torque 4.43 to 5.31 lb-in (0.5 to 0.6 Nm)
- Weight 0.17 lb
- Width 1.12 in
- Wire Gauge 26 to 16 AWG
Supported Applications
The ACI Relative Humidity Room with Nickel RTD Series is a relative humidity transmitter designed for use in commercial heating and cooling building management systems. The series utilizes a thermoset polymer capacitive sensing element with a factory-fitted hydrophobic filter to improve moisture resistance, providing durability against dust, dirt, oils, and common environmental chemicals.
Documented applications include:
- Humidification and dehumidification control
- Monitoring indoor space humidity in clean rooms, hospitals, laboratories, museums, schools, office buildings, and data centers
- Process control environments
- ESD (anti-static) control applications
Operating Conditions & Performance
The series operates within an ambient temperature range of 35 to 122°F (1.5 to 60°C). The relative humidity measurement range is specified as 0-100% RH, with an operating range of 0 to 95% RH non-condensing. Storage temperatures are rated from -40 to 149°F (-40 to 65°C).
Performance specifications for the relative humidity sensor at 77°F (25°C) include:
- RH Accuracy: ±/- 1% over a 20% RH range between 20 to 90%; or ±/- 2%, or 3% from 10 to 95%
- Sensitivity/Resolution: 0.1% RH
- Stability (Repeatability): Less than 2% drift / 5 years
- Response Time (T63): 20 Seconds Typical
- Transmitter Stabilization: 30 Minutes recommended before accuracy verification
The Nickel RTD temperature sensor follows the Din 43760 standard with a Temperature Coefficient of 637.0 ppm/°C (0-100°C). The nominal output at 70°F (21.1°C) is 1 KΩ for RHx-1K-NI-R2 Series units.
Configuration Options
The series offers configurable options across enclosures, outputs, and sensor configurations to meet specific installation needs.
Housing & Enclosure Options
- R Enclosure: ABS Plastic (Beige), UL94-HB flammability rating. Dimensions: 2.75" x 4.50" x 1.12".
- R2 Enclosure: ABS Plastic (White), UL94-HB flammability rating. Dimensions: 2.75" x 4.50" x 1.12".
Both enclosures feature four-way airflow to minimize self-heating. Accessories include wall mounting back plates for beige (R) and white (R2) finishes, a clear locking cover thermostat guard, and an A/ROOM-FOAM-PAD thermally-insulated backing pad.
Output Signals & Power
The transmitter is field-selectable via on-board DIP switches for the following output signals:
- 4-20 mA (Factory Default): 2-wire configuration. Requires a minimum supply voltage of 15 VDC with a 250 Ω load or 18 VDC with a 500 Ω load.
- 0-5 VDC: Field selectable, requires 3-wire connection. Supply range: 12 - 40 VDC / 18 - 28 VAC.
- 0-10 VDC: Field selectable, requires 3-wire connection. Supply range: 18 - 40 VDC / 18 - 28 VAC.
All power supplies are reverse polarity protected. Load resistance limits are 700 Ω maximum for current output and 4K Ω minimum for voltage outputs.
Configuration & Calibration Options
- Sensor Configurations: Available as Room (R/R2), Room with Override (RO/R2O), Room with Setpoint (RS/R2S), and Room with Setpoint and Override (RSO/R2SO).
- NIST Calibration Certificates: Three-point NIST certificates are available. Default test points cover 3 Points (20%, 50% & 80%). A 1% NIST option provides 5 Points within a selected 20% range.
- Field Calibration: Single-point field calibration is possible via increment/decrement DIP switches, allowing ±0.5% adjustments.
Key Product Differences
Variants in the series differ primarily by accuracy class and configuration features as defined in the model number guide (e.g., A/RH1-1K-NI-R).
- RH Accuracy Classes: Models are designated RH1 for ±/- 1% over a specified range, RH2 for ±/- 2%, and RH3 for ±/- 3%.
- Enclosure Color: The "R" suffix denotes the beige enclosure; "R2" denotes the white enclosure.
- Functional Additions: Models with "O", "S", or "SO" in the configuration segment include Override, Setpoint, or both features respectively. These configurations may utilize slidepots (e.g., A09 for 0 to 2K) and setpoint stickers.