Need assistance? Call us: 1-800-663-4209
Series-EPW
PWM to Pneumatic Output for 20 to 25 psig Air Supply Pressure
- Converts PWM to pneumatic control: EPW Series modules convert pulse or digital PWM signals into proportional pneumatic output from 0 to 20 psig.
- Flexible pressure ranges: Jumper-selectable outputs support 0-10 psig, 0-15 psig, and 0-20 psig, with field calibration available for matching actuator requirements.
- Ideal for HVAC pneumatic applications: Designed for 3-way mixing valves, chiller loading, pilot positioners, pneumatic valve and damper actuators, fan vane control, DDC control, VAV boxes, and above-ceiling applications.
- Direct or reverse acting options: Available models support standard direct-acting control or reverse-acting operation for applications requiring opposite pressure response.
- Built-in pressure feedback: A 0-5 VDC feedback signal provides branch line pressure visibility for monitoring and control verification.
- Manual override for service: Manual/Auto switch and potentiometer allow technicians to locally vary pneumatic output during setup, checkout, or troubleshooting.
- Multiple pneumatic behaviors: Choose constant-bleed EPW models, EPW2 branch-pressure-holding models, or EPW2FS fail-safe models that exhaust branch pressure on power failure.
- Installer-friendly design: Electrical terminals and pneumatic fittings are separated for cleaner panel wiring and tubing, with optional gauge models for direct pressure readings.
- Reliable field package: Integral 80-100 micron filtering, removable brass fittings, snaptrack mounting, RoHS2/WEEE compliance, and ACI’s two-year warranty support dependable operation.
Series-EPW
From
$
428.00
Product Overview
- Accuracy Detail Output Pressure Accuracy: 2% full scale at room temperature (above 1 psig or 6.895 kPa) 3% full scale across operating temperature range (above 1 psig or 6.895 kPa); Gauge Pressure Accuracy (Gauge Models): ± 2.5% Midscale (± 3.5% Full Scale)
- Air Supply Pressure, Max 25 psi
- Air Supply Pressure, Min 20 psi
- Applications Air and HVAC, Building and Maintenance, Environmental Monitoring, Pneumatic Systems
- Approvals RoHS2, WEEE
- Auto/Manual function Manual/Auto Override Switch: MAN function = output can be varied
- Control Valve 1 Valve
- Electrical Connection Screw Terminal
- Filter Furnished with integral-in-barb 80-100 micron lter (Part # PN004) Optional standard barb (PN002) with external 5 micron in-line lter (PN021)
- Input Type PWM
- Materials PVC
- Operating Humidity 10 to 95% RH, non-condensing
- Operating Temperature, Max 120 °F
- Operating Temperature, Min 35 °F
- Output Note Feedback Output Signal Range: 0-5 VDC = Output Span
- Output Pressure Range 0 to 10 psi, 0 to 15 psi, 0 to 20 psi
- Pressure Note Gauge Pressure Range (Gauge Models): 0-30psig (0-200 kPa), Output Pressure Range-Jumper Selectable: 0-10 psig (0-68.95 kPa), 0-15 psig (0-103.43 kPa) or 0-20 psig (137.9 kPa)
- Pulse Input Note Input Pulse Source: Relay Contact Closure, Transistor (solid state relay) or Triac; Input Pulse Trigger Level (@ Impedance): 9-24 VAC or VDC @ 750Ω nominal; O Time Between Pulses: 10 milliseconds minimum
- Resolution Selectable Ranges-See Ordering Grid
- Series ID Series-EPW
- Storage Temperature, Max 150 °F
- Storage Temperature, Min -20 °F
- Supply Current 50 mA
- Supply Voltage 24 Vac/Vdc
- Tightening Torque 0.5 Nm (Minimum); 0.6 Nm (Maximum)
- Tube Size 1/4 in OD x 1/8 in ID
- Wire Gauge 26 to 16 AWG
Supported Applications
The ACI Series EPW converts a pulse or digital PWM signal into a proportional pneumatic output ranging from 0 to 20 psig. The series is designed for applications requiring the translation of electrical control signals—such as relay contact closure, transistor (solid state relay), or Triac inputs—into precise air pressure levels. It supports both direct and reverse acting configurations via firmware versions.
Key functional capabilities include:
- Pneumatic signal generation proportional to input timing ranges
- Manual override potentiometer for varying pneumatic output independent of the input signal
- A 0-5 VDC feedback signal that varies linearly with the selected branch pressure range, indicating resultant line pressure
- Field calibration capability up to a maximum of 20 psig (138 kPa)
Operating Conditions & Performance
The Series EPW operates within an ambient temperature range of 35 to 120°F (1.7 to 48.9°C) and a humidity rating of 10 to 95% non-condensing. Storage is supported from -20 to 150°F (-28.9 to 65.5°C). The unit requires an air supply pressure between a minimum of 20 psig (137.9 kPa) and a maximum of 25 psig (172.38 kPa).
Performance specifications include:
- Output Pressure Accuracy: 2% full scale at room temperature (above 1 psig or 6.895 kPa); 3% full scale across the operating temperature range (above 1 psig or 6.895 kPa)
- Jumper Selectable Output Ranges: 0-10 psig (0-68.95 kPa), 0-15 psig (0-103.43 kPa), and 0-20 psig (137.9 kPa)
- Input Pulse Trigger Level: 9-24 VAC or VDC @ 750Ω nominal
- Minimum Off Time Between Pulses: 10 milliseconds
- Pneumatic Tubing Requirement: Branch line minimum of 2 in³ (33.78 cm³) volume; recommended branch line length is a minimum of 25 ft of 1/4" O.D. poly tubing for standard models, or as specified by the specific model's exhaust characteristics.
Configuration Options
The series offers three primary configurations distinguished by their valve architecture and fail-safe behavior:
- EPW (Constant Bleed): A constant bleed interface where branch exhaust response time is determined by the bleed orifice size (0.007" standard) and pressure differentials. On power failure, it continues to bleed until branch pressure reaches zero psig.
- EPW2 (Two Valve / Non-Bleed): Incorporates two valves with one controlling exhaust; does not bleed air at set point. Branch exhaust flow is not limited by an internal restrictor and response time is similar to the load rate. On power failure, branch line pressure remains constant provided there are no leaks.
- EPW2FS (Fail-Safe): A two-valve fail-safe model featuring a 3-way branch exhaust valve that allows for the exhaust of branch line air upon power failure.
Additional configurable options include:
- Gauge Models: Available with an integrated pressure gauge (0-30 psig range, ±2.5% Midscale accuracy).
- Firmware Versions: Version 1 and Version 4 support standard timing ranges; Version 2 supports Solydne or Staefa duty cycle inputs.
- Filtering: Furnished with an integral-in-barb 80-100 micron filter (Part # PN004). An optional external 5 micron in-line filter (PN021) is available for installation between the air supply and main barb connection.
- Mounting: Designed with electrical terminals on one end and pneumatic connections on the other. A DIN Rail Adapter Kit is offered as an accessory.
Key Product Differences
The Series EPW distinguishes models by exhaust capacity, gauge inclusion, and input timing compatibility:
- Exhaust Capacity: Standard EPW/EPWG models list an exhaust of 41 SCIM (0.6719 Liters). The EPW2 family lists an exhaust of 750 SCIM (12.29 Liters).
- Gauge Integration: Models with the "G" suffix include a pressure gauge; non-suffixed models do not.
- Firmware Versions: Version #4 provides reverse acting operation compared to Version #1. Version #2 supports specific duty cycle inputs (0-10s Duty Cycle or 0.023-6s).