Product Specs
<< See all Product Models| Brand |
|
| Accuracy | 0.1 Class |
| Applications | Building and Maintenance, Control Panel, Environmental Monitoring, Industrial and Manufacturing |
| Baud Rate | 9600, 19200, 38400, 76800 |
| Compliance Note | Measurement Standard: IEC 62053-22; ANSI C12.20 Environmental Standard: IEC 60068-2 Safety Standard: IEC 61010-1, UL 61010-1, IEC 61557-12 EMC Standard: IEC 61000-4/-2-3-4-5-6-8-11, CISPR 22, IEC 61000-3-2, IEC 61000-6-2/4 Outlines Standard: DIN 43700, ANSI C39.1 |
| Connection Note | Two pluggable pre-cut holes to feed wiring, fused terminal blocks for voltage connections pre-installed, color-coded and labelled |
| Data Format | 8 data bits:no parity:1 stop bit |
| Data Interface | Modbus, BACnet MS/TP, BACnet Over IP, IEC 61850, Modbus®-TCP, HTTP/HTTPs Webserver, SMTP Email, SNMP, HTTP/HTTPs Push, FTP Post, sFTP Server, WiFi |
| Display Type | LCD |
| Electrical Connection | Screw Terminal |
| Enclosure Material | Flame retardant polycarbonate |
| Enclosure Ratings | IP66, NEMA Type 4X |
| Frequency | 50/60 Hz |
| Fuse Rating | 600 VAC/1A |
| Height | 7.34 in |
| Impedance Input | 2MΩ/Phase |
| Input_Current Note | 120% of current sensor rating (mV CTs) to maintain accuracy. Up to 6000 Amps w/ Rogowski Coils |
| Length | 7.88 in |
| Materials | Polycarbonate |
| Memory Backup | 8 GB Datalogging |
| Mounting | ANSI C39.1 (4” Round) or an IEC 92mm DIN (Square) form |
| Network and Communications | BACnet Device Instance Number: 1 (Default); Field adjustable from 1 to 4194302; Max Station: 127 MS/TP Masters (MAC Addresses is 0 to 127); Supported Baud Rates: BACnet MS/TP Protocol: 9600, 19200, 38400, 76800 Baud Rate (38400 BACnet Default) Modbus RTU Protocol: 1200, 2400, 4800, 9600, 19200, 38400 Baud Rate (19200 Modbus Default) |
| Number of Channels Note | 4 Channels, 0.400 VAC max, 333 mV CTs or 0 to 6000 Amps with Rogowski Coils (Field Selectable); Voltage Channels : 400 Volts AC (L-N), 690 VAC (L-L), 45Hz - 65Hz, 300Hz - 500Hz |
| Number of Inputs | 4 |
| Operating Distance, Max | 1200 m |
| Operating Humidity | 5 to 95% RH, non-condensing |
| Operating Temperature, Max | 158 °F |
| Operating Temperature, Min | -13 °F |
| Operating Voltage, Min | 10 V |
| Power Consumption | 5 W |
| Protection | External 1A/250VAC Fuse |
| Resolution | 63rd Harmonic (50Hz or 60Hz type) or 15th Harmonic (400Hz type) |
| Series ID | KW320 |
| Software | Acuview Utility Software, Windows Based; (USB-RS485 converter is required to connect to computer) |
| Storage Temperature, Max | 185 °F |
| Storage Temperature, Min | -40 °F |
| Supply Voltage | 100 to 415 Vac, 100 to 300 Vdc |
| Termination | 120 to 300 Ω |
| Update Rate | Accumulated Parameter Update Rate: 1 sec ; Real Time Parameter Update Rate: <20 ms |
| Voltage Measurement Range | 100 to 400 Vac (L-N), 100 to 690 Vac (L-L), 100 to 400 Vac rms (1 phase) |
| Weight | 8 lb |
| Width | 11.81 in |
| Wire Gauge | 22 to 14 AWG |
| Withstand Voltage | 3250 Vac |
| See All Specs | |