1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here
KW1850
Added to Your Shopping Cart
Configuration complete.
Please add to cart to keep it or exit the configuration
Please add to cart to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product Models| Brand |
|
| Accuracy | 0.5 Class |
| Applications | Building and Maintenance, Control Panel, Environmental Monitoring, Industrial and Manufacturing, Refrigeration Equipment |
| Approvals | UL 508A, EN62208 |
| Baud Rate | 1200 to 115200 |
| Compliance Note | UL 746C 5-inch flame test |
| Connection Note | DIN rail mounted pre-labeled terminal blocks for voltage connection pre-installed |
| Control Output | Alarm |
| Data Format | 8 data bits:no parity:1 stop bit |
| Data Interface Note | RS-485 Serial, Dual Ethernet (KW1850-P1-D-W Only), Wireless Network Card (KW1850-P1-D-W Only) |
| Display Type | LCD |
| Enclosure Material | Flame retardant polycarbonate |
| Enclosure Ratings | IP66, NEMA Type 4X |
| Frequency | 45/65Hz |
| Frequency Note | Pulse Frequency (MAX):100Hz, 50% Duty Cycle |
| Fuse Rating | 600 VAC/2A |
| Height | 7.01 in |
| Impedance Input | 2MΩ/Phase |
| Inductive Loads | <0.2VA |
| Input Control Signal | 15 to 30 Vdc |
| Input Current | 2 mA |
| Input Note | Digital Inputs / Type: 18 Digital Inputs for Water and Gas Metering Pulse Counting / Dry Node; Acceptable CT Inputs: 333mV or Rogowski Coil (cannot mix CT’s); |
| Isolation | 4000 Vac |
| Length | 11.81 in |
| Load Current, Max | 3 A |
| Load Voltage, Max | 30 V |
| Materials | Polycarbonate |
| Measurement Type | Single Phase, 3 Phase – Four Wire (WYE), 3 Phase – Three Wire (Delta) |
| Mounting | ANSI C39.1 (4" Round) or an IEC 92mm DIN (Square) form; IEC 35mm DIN Standard |
| Network and Communications | Modbus Address Range:1 to 247 (The default is 1) |
| Number of Inputs | 18 |
| Operating Distance, Max | 1200 m |
| Operating Humidity | 5 to 95% RH, non-condensing |
| Operating Temperature, Max | 158 °F |
| Operating Temperature, Min | -13 °F |
| Output Detail | Ten limit alarms configured for peak demand, current, or power quality; Auxiliary Power Output: 15VDC, 1W; Pulse Output: Two-wire pulse train, Isolation Voltage 2500VAC, 0-30 VDC Load Voltage, 10mA Max Load Current, Pulse Width 20~100ms (80ms Default), Pulse Constant 1~60,000 (50000 Default) IMP/kWh |
| Power Consumption | 5 W |
| Relay Output | 250 Vac |
| Response Time | 2 ms |
| Security | Password Protected to access Settings. Sealed and Tamper Proof Cover |
| Series ID | KW1850 |
| Software | Accuview Utility Software, Windows Based. USB-RS485 converter is required to connect to computer for KW1850-P1-D-S only |
| Storage Temperature, Max | 185 °F |
| Storage Temperature, Min | -40 °F |
| Supply Voltage | 100 to 415 Vac, 100 to 300 Vdc |
| Volt-Amperes Burden | <0.2VA |
| Voltage Measurement Range | 100 to 400 Vac (L-N), 100 to 690 Vac (L-L), 100 to 400 Vac rms (1 phase) |
| Weight | 8 lb |
| Width | 11.81 in |
| Wire Gauge | 22 to 16 AWG |
| Working Life | Multi-Tariff Time of Use (TOU): 4 tariffs (sharp, peak, normal, valley), 14 schedules, 14 segments, weekends and 10-year holiday settings |
| See All Specs | |