Product Specs
<< See all Product Models| Brand |
|
| Accuracy | ± 10 μg/m3 |
| Accuracy Detail | +/- 10% reading @ 100 ~ 500/600 μg/m3 @ 25°C/50%RH |
| Applications | Air and HVAC, Building and Maintenance, Environmental Monitoring |
| Approvals | CE, RoHS2 |
| Data Interface | Modbus RTU, RS485 |
| Electrical Connection | Screw Terminal |
| Electrical Output | 4 to 20 mA, 0 to 10 Vdc |
| Enclosure Material | ABS Plastic |
| Enclosure Ratings | UL94 V-0 |
| Input Type | Fan |
| Loop Resistance, Max | 4-20 mA: 500 Ohms maximum (Default) |
| Material Construction Option | none |
| Operating Humidity | 0 to 95% RH, non-condensing |
| Operating Temperature, Max | 122 °F |
| Operating Temperature, Min | 32 °F |
| Protection | IP30 (Room) |
| Relay Output | 3 A @ 30 Vdc, 3A @ 250 Vac |
| Resolution | 1 µg/m3 |
| Response Time | In continuous service mode, sample time <1s, response time <10s |
| Sensor Type | Laser particulate matter sensor |
| Series ID | Particulate-Matter |
| Service Life | MTBF more than 3 years in continuous service mode, service life up to 8-10 years in auto (intermittent) service mode |
| Storage Temperature, Max | 70 °F |
| Storage Temperature, Min | -30 °F |
| Supply Current | 50 mA |
| Supply Voltage | 16 to 28 Vac, 16 to 35 Vdc |
| Tightening Torque | 0.45 lb-in (0.5 Nm) nominal |
| Trip Point Note | Relay Trip Point: 100 (Factory set), user adjustable |
| Warm Up Time | 15 minutes |
| Weight | 270 g |
| Wire Gauge | 22 to 16 AWG |
| See All Specs | |