RTD-Flexible-Ave

Platinum RTD Flexible Averaging

  • The flexible averaging sensor measures across multiple points to produce a better duct air average than a single-point duct sensor.
  • The product uses a 1K ohm platinum RTD with Class A tolerance, DIN EN 60751 reference, and a 3850 ppm per deg C temperature coefficient.
  • The A/1K-2W-FA series is listed as two-wire and non-polarity-sensitive, with controller wiring connected to analog input leads.
  • The flexible sensor uses low-smoke PVC cable rated CL2P or CMP, with a 0.170 in nominal cable diameter and dual-wall adhesive heat shrink at sensing elements.
  • Ordering supports galvanized, plastic, aluminum bell box, and NEMA 4X enclosure options for different mounting and protection needs.
  • Flexible averaging is limited to 0 to 75 deg C operation, 10 to 90% non-condensing humidity, and applications that do not require UV, chemical, or high-humidity resistance.
  • Use the sensor across large air-handler duct sections where stratification makes a single-point reading less representative.
  • Use flexible averaging in rooftop HVAC ductwork when the operating temperature and humidity stay inside the flexible sensor limits.
  • Use a crisscross duct pattern to average mixed air streams and reduce error from hot and cold layers.
  • Place the averaging element downstream of fan discharge where the airstream is more uniform across the duct cross-section.
  • Use the sensor where return duct temperature needs a broad representative average instead of a local point sample.
  • Applications where averaged air temperature feedback can support tighter HVAC control.
RTD-Flexible-Ave
From $ 391.00
Platinum RTD Flexible Averaging RTD-Flexible-Ave RTD-Flexible-Ave
loading all models
Product Overview
  • Accuracy +/- 0.06% Class A
  • Accuracy Detail (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 *
  • Alloy Material (-) Copper
  • Alloy Material (+) Copper
  • Applications Air and HVAC, Building and Maintenance, Medical
  • Approvals DIN EN 60751 (IEC 751)
  • Cable Diameter 0.17 in
  • Cable Material PVC
  • Electrical Connection Pigtail Leads
  • Enclosure Ratings NEMA Type 4X
  • Fitting Polyamide 66 (High Performance Nylon)
  • Insulation Etched Teflon (PTFE) Colored Leads 
  • Operating Current 3 mA
  • Operating Humidity 10 to 95% RH, non-condensing
  • Operating Temperature, Max 150 °C
  • Operating Temperature, Min -40 °C
  • Output Detail Sensor Output @ 0ºC (32ºF): 1000 Ohms nominal
  • Response Time 15 Seconds nominal
  • Self Heating Effect 4 mW / °C
  • Series ID RTD-Flexible-Ave
  • Sheath Material 304 Stainless Steel
  • Stability +/- 0.03% after 1000 Hours @ 300ºC (572ºF)
  • Storage Temperature, Max 75 °C
  • Storage Temperature, Min -20 °C
  • Temperature Coefficient DIN EN 60751 (IEC 751)
  • Temperature Measurement Range -40 to 115°C
  • Temperature Sensor Type 100 Ω 2 Wire Platinum RTD
  • Tolerance +/- 0.06% Class A
  • Tube Length 4.5 in
  • Wire Gauge 22 AWG
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 5ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 4ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en
Save Configuration