Airflow Measurement Station for HVAC, Easy Setup, G90 Casing, Accurate Sensors
Product Overview
- Series ID Series-FLST
Supported Applications
The Dwyer Series FLST is a duct-mounted airflow measurement station designed for HVAC applications. The system utilizes an averaging element that generates a differential (velocity) pressure signal, similar to orifice and venturi primary elements. Strategically located sensing ports sample total and static pressures when the device is inserted normal to flow; these signals are averaged within isolated chambers before being manifolded together for connection to a differential measurement device such as a gage or transmitter.
Operating Conditions & Performance
The Series FLST measures airflow in air with a range of 100 to 10,000 fpm (0.51 to 51 m/s). Accuracy is within 2% of actual flow when installed in accordance with published recommendations. The station operates at humidity levels from 0 to 100% non-condensing.
Temperature limits for galvanized casings and aluminum elements are:
- 350°F (177°C) continuous operation
- 400°F (204°C) intermittent operation
Configuration Options
The series supports multiple duct configurations including circular, rectangular, and oval stations. Standard construction features a 16 ga G90 galvanized steel casing with 6063-T5 anodized aluminum elements. Process connections are provided via 1/4" compression fittings.
Flange Dimensions
Circular flanges vary by station size "D":
- 8" - 15": .064" thickness, 1" flange size, 6" casing length
- 16" - 44": .064" thickness, 1-1/2" flange size, 6" casing length
- 45" - 72": .188" thickness, 1-1/2" flange size, 10" casing length
- 73" & over: .188" thickness, 2" flange size, 12" casing length
Oval and rectangular stations follow specific dimension tables based on width or height. Oval flanges are optional.
Material Options
The series offers stainless steel configurations via option codes:
- -SS1: 316 SS elements with 16 GA galvanized casing
- -SS2: 316 SS elements with 16 GA 304 SS casing
- -SS3: 316 SS elements with 16 GA 316 SS casing
Additional Options
- -F: Flange (oval stations only)
- -IM: Internal pressure connections (rectangular stations only)
Key Product Differences
The Series FLST is available in circular, rectangular, and oval configurations. Rectangular or oval flow station pressure taps are located on the longer of the two dimensions. Oval airflow measuring stations without flanges have a casing length of 5"; standard oval stations include a 18 gage galvanized casing with an overall length of 7-1/2 inches (including connecting sleeves). The device is not field serviceable and must be returned for repair if needed.
PDFs & Manuals
Show Ratings & Reviews
Hi, I want to know, what transmitter I must use with this Airflow Measurement Station, to send a signal to a vfd?
Hello,
There are many transmitters that can be used with the FLST. One that is commonly paired with it is the MSX series. If you need something that can modulate the output signal to try to achieve a setpoint, you can pair the MSX with a 16B process controller.
Date published: 2026-03-13
Shape
Size
Width
Options
Other sizes, including metric, are available: contact DwyerOmega.