Product Overview
  • Detection Angle 360 °
  • Measurement Note Measuring Range: 34.4´ diameter at 13.8´ mount height ; Detectable Speed: 0.33 to 9.8 ft/s
  • Mounting Note Mounting Height: 7.9 to 13.8 ft
  • Operating Temperature, Max 140 °F
  • Operating Temperature, Min -4 °F
  • Power Consumption Standby: 5 mA; Operating: 18 mA
  • Sensor Type Infrared Dual Element
  • Series ID Model-OSC-200
  • Supply Power Type AC/DC
  • Supply Voltage 22 to 26 Vac/Vdc
  • Switch Rating 0.2 A @ 30 Vdc
  • Switch Type SPDT NO/NC, Selectable
  • Weight 2.4 oz

Supported Applications

The Dwyer Model OSC-200 Omnidirectional Occupancy Sensor is designed to automatically control HVAC ventilation systems. Utilizing infrared technology and a spherical Fresnel lens, the sensor provides a 360° detection zone for occupancy monitoring in ceiling-mounted installations.

Operating Conditions & Performance

The Model OSC-200 operates within an ambient temperature range of -4 to 140°F (-20 to 60°C). The sensor detects movement at speeds between 0.33 and 9.8 ft/s (0.1 to 3.0 m/s) with a detection diameter of 34.4 ft (10.5 m) when mounted at a height of 13.8 ft (4.2 m). The recommended mounting height range is 7.9 to 13.8’ (2.4 to 4.2 m).

Power requirements are specified as 22-26 VAC/DC, with power consumption of 5 mA in standby and 18 mA during operation. The control output rating is SPDT, 0.2 A @ 30 VDC.

Configuration Options

The series includes configurable ON/OFF delay settings to prevent false activation from short-term occupancies via an integrated dual delay processor. Available delay configurations include:

  • ON Delay Options: 0 Sec., 10 Sec., 30 Sec., 1 Min., 5 Min., or 10 Min.
  • OFF Delay Options: 10 Sec., 1 Min., 5 Min., 10 Min., 20 Min., or 30 Min.

The sensor is pre-wired with five wires (BROWN, GREEN, WHITE, RED & BLACK) compatible with 22AWG cabling. The unit carries CE compliance certification and features a dual-element infrared sensor.

Key Product Differences

The Model OSC-200 is an omnidirectional ceiling-mount occupancy sensor distinct from the wall-mounted OSW-100 model found in related documentation. While both models utilize infrared technology, the OSC-200 provides a 360° detection zone with dimensions of Ø4-5/16 [Ø109.54] diameter and 1-47/64 [44.05] height, weighing 2.4 oz (68 g). The OSW-100 offers a wide 110° viewing angle with different dimensional specifications.

Installation notes specify that the Model OSC-200 is not field serviceable; units requiring repair must be returned to the manufacturer. Care should be taken during installation to avoid direct sunlight, strong heat sources, or obstructions such as plants and furniture that may block detection.

  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 5ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 4ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en
Save Configuration