Need assistance? Call us: 1-800-663-4209
Series-MTL7706-7787
Intrinsically Safe Shunt-Diode Barrier for Dwyer® Transmitters
Models In Stock
- Approved for use in hazardous areas
Series-MTL7706-7787
From
$
469.15
Models In Stock
Product Overview
- Accuracy ± 2 µA
- Capacitance FM: 0.083 µF, BASEEFA: 0.083 µF
- Certifications BASEEFA: IIC, FM: A & B
- Electrical Safety 28 µV 300 Ω 93 mA
- Input Control Signal 16.2 Vdc
- Input Voltage Note 16.2 V at 20 mA with 250 Ω load (negative w.r.t. earth); 11.0 V at 20 mA with 500 Ω load (negative w.r.t. earth)
- LED Indicators Green: Power indication
- Load Resistance 0 to 500 Ω
- Operating Temperature, Max 140 °F
- Operating Temperature, Min -4 °F
- Output Detail 4 to 20 mA
- Output Signal Current
- Relative Humidity 5 to 95% RH
- Series ID Series-MTL7706-7787
- Storage Temperature, Max 176 °F
- Storage Temperature, Min -40 °F
- Supply Power Note 20-35 Vdc w.r.t. earth
- Supply Power Type DC
- Supply Voltage 20 to 35 Vdc
- Terminal block up to 2.5 mm²
- Weight 4.9 oz
Supported Applications
The Dwyer Series MTL7706/7787 consists of intrinsically safe shunt-diode barriers designed to communicate with and provide isolation for specific Dwyer® transmitters approved for use in hazardous areas. These devices limit the amount of energy allowed to pass into the hazardous area, inhibiting ignition in flammable atmospheres.
According to series documentation, these Zener barriers are compatible with the following Dwyer transmitter models:
- Series 637
- Series 608
- SBLTX Series
- PBLTX Series
- IS626 Series
Operating Conditions & Performance
The barriers operate within an ambient temperature range of -4 to 140°F (-20 to 60°C) and a storage temperature range of -40 to 176°F (-40 to 80°C). Humidity ratings are specified as 5 to 95% RH. The electrical performance includes an accuracy of ±2 µA under all conditions, with a load resistance capability from 0 to 500 Ω.
Power supply requirements are 20-35 VDC w.r.t. earth. The output signal is specified as 4-20 mA. Safety parameters for the system include a safety description of 28 µV, 300 Ω, and 93 mA.
Configuration Options
The series includes two primary barrier models with distinct electrical characteristics:
- MTL7706: Zener barrier configured for FM Groups A & B (Capacitance 0.083 µF, Inductance 4.2 mH) and BASEEFA Group IIC (Capacitance 0.083 µF, Inductance 4.2 mH).
- MTL7787: Zener barrier configured for FM Groups A & B (Capacitance 0.083 µF, Inductance 3.05 mH) and BASEEFA Group IIC (Capacitance 0.083 µF, Inductance 3.05 mH).
Physical dimensions for the barriers are a width of 4-5/32 [105.57], height of 3-35/64 [90.09], and depth of 1/2 [12.70]. The unit weight is 4.9 oz (140 g). Electrical terminals accommodate up to 2.5 mm² stranded or single-core wire.
Mounting accessories available for the series include:
- A-360: Aluminum DIN rail, 1 m length.
Key Product Differences
The MTL7706 and MTL7787 models differ primarily in their approved hazardous area classifications and internal electrical parameters (inductance). The MTL7706 is listed for UL Class I, Div. 1 Groups A, B, C, D; CL II, Div. 1 Groups E, F, G; and CL III Div. 1. It also holds FM approval for Class I, II, III; Div. 1 Groups B, C, D, E, F, G (Model 637) and Groups A through G (Model 608).
The MTL7787 is identified as a Zener barrier in the model chart but specific hazardous area group approvals for this variant are not detailed separately from the general series capabilities in the provided data. Both models carry CE, CSA, Ex, FM Approved, and UL Listed certifications.
PDFs & Manuals