Skip to search Skip to main content Skip to navigation

Need assistance? Call us: 1-800-663-4209

We noticed you are in , please visit your local site by clicking the below link for regional offers and support.

HTS-HANI-CLAMP-P

Item# HTS-HANI-CLAMP-P

In Stock

Lead Time (If not in stock): 0 week

Product Specs

<< See all Product Models
Brand
Accuracy ± 1.5 °C (± 2.7 °F)
Accuracy Detail ± 1.5°C from factory and improved accuracy possible with in-situation 1 or 2-point calibration
Applications Aeronautics and Aerospace, Air and HVAC, Building and Maintenance, Chemicals, Clean Water and Purified Solutions, Energy Generation and Distribution, Fluid Measurement and Control, Food and Beverage, Fuel and Gas, General Purpose, Heat and Energy Systems, Hydraulic and Pneumatic Systems, Industrial and Manufacturing, Laboratories and Scientific, Materials and Surfaces, Medical, Office and Commercial, Oils, Pharmaceutical, Waste Management
Base Mounting PVC, CPVC, PP, PFA
Electrical Connection M12 8 pin Female
Enclosure Ratings IP65
Height 2.03 in
Length 2.53 in
Loop Resistance (Vsupply -8V)/0.24 A
Materials Nylon, Silicone, Brass, Stainless Steel
Media Compatibility Clean process / cooling water, Water-based fluids
Mounting Clamp
Operating Temperature, Max 40 °C
Operating Temperature, Min 0 °C
Output Detail 4 to 20 mA User scalable analog output, default scaling 0-100°C
Output Signal Current
Process Temperature, Max 100 °C
Process Temperature, Min 0 °C
Response Time t63: 30 sec; t90: 60 sec
Series ID HTS-HANI-CLAMP-P
Supply Power Note 8 VDC - 28 VDC (loop powered) Max Loop Resistance: Rmax (Ω)= (Vsupply -8V)/0.24 A
Supply Voltage 8 to 28 Vdc
Width 2.38 in
See All Specs Show Less