Need assistance? Call us: 1-800-663-4209
Series-TTE
Explosion-Proof RTD Temp Transmitter, -30 to 250 °F, Easy Adjust, Offshore HVAC
Models In Stock
- FM approved for Class I, Groups B, C, D; Class II, Groups E, F, G classified explosive environments
- Optional LCD
- Output span selected from seven common ranges or user determined
Series-TTE
From
$
769.55
Models In Stock
Can't find the right model?
Use our custom configurator to fine tune your product
Product Overview
- Construction Type Well Probe
- Current Output 4 to 20 mA
- Electrical Connection 1/2 in NPT female Conduit with Screw Terminal block
- Enclosure Ratings Hazardous Location Rated
- Enclosure Ratings Note Enclosure Rating: Weatherproof NEMA 4X (IP66) and Explosion-proof. Listed with FM for Class I, Division 1, Groups B, C and D, and dust-ignitionproof for Class II, Division 1, Groups E, F and G and Class III atmospheres. ATEX Certified: 2813 II 2 G Ex db IIC T6...T4 Gb, 2813 II 1 D Ex ta IIIC T111°C Da, T6 Process Temp ≤80°C, Temperature Class T5 Process Temp ≤95°C, Temperature Class T4 Process Temp ≤120°C as defined on nameplate. EUtype Cerificate No.: EMT17ATEX0021 X. ATEX Standards: EN IEC 60079-0, EN 60079-1, EN 60079-31. IECEx Certified: For Ex db IIC T6...T4 Gb, Ex ta IIIC T111°C Da, T6 Process Temp ≤80°C, Temperature Class T5 Process Temp ≤95°C, Temperature Class T4 Process Temp ≤120°C as defined on nameplate. IECEx Certificate of Conformity: Element IECEx EMT 17.0007X; IECEx Standards: IEC 60079-0, IEC 60079-1, IEC 60079-31. UKCA Ex Certified for: 0518 II 2 G Ex db IIC T6...T4 Gb / II 1 D Ex ta IIIC T111°C Da, T6 process temp ≤ 80°C, T5 process temp ≤ 95°C, T4 process temp ≤ 120°C. UKCA Ex Certificate of Conformity: EMA22UKEX0066X. UKCA Ex Standards: EN IEC 60079-0, EN 60079-1, EN 60079-31.
- Measurement Type RTD
- Number of Wires 2
- Operating Temperature, Max 158 °F
- Operating Temperature, Min -4 °F
- Output Detail 4-20 mA (2-wire loop powered)
- Output Signal Current
- Pressure Limits Up to 2000 psi
- Process Connection Size 1/2 in
- Process Connection Type NPT Male
- Process Temperature, Max 250 °F
- Process Temperature, Min -30 °F
- Protection Explosion-Proof
- Response Time 250 ms
- Sensor Type Pt1000
- Series ID Series-TTE
- Supply Power Type DC
- Supply Voltage 10 to 35 Vdc
- Thermal Effects ± 0.02%/°C max
- Transmitter Accuracy Transmitter: ± 0.1%, Probe: ± 0.3%
- Weight 1134 g
Supported Applications
The Dwyer Series TTE Explosion-Proof RTD Temperature Transmitter is designed for hazardous temperature measurement applications. The series supports use in refrigeration, building automation, commercial hot water heaters, boilers, and water chillers.
Operating Conditions & Performance
The transmitter measures process temperatures from -30 to 250°F (-34.4 to 120°C) using a Pt1000 sensor (DIN 0.00385). Accuracy is specified as Transmitter ±0.1% FS and Probe ±0.3% FS, with thermal drift effects of ±0.02%/°C max. The device operates in ambient conditions from -4 to 158°F (-20 to 70°C) and features a response time of 250 ms.
Configuration Options
The Series TTE offers configurable temperature ranges via an internal dip switch, including seven pre-programmed options or a user-settable range between -30 to 250°F with a minimum span of 40°F. The series supports the following configurations:
- Output Signal: 4-20 mA (2-wire loop powered) on a power supply of 10-35 VDC.
- Housing & Enclosure: Weatherproof NEMA 4X (IP66) and explosion-proof. Listed with FM for Class I, Division 1, Groups B, C and D; dust-ignitionproof for Class II, Division 1, Groups E, F and G; and Class III atmospheres.
- Approvals: ATEX Certified (CE 2813), IECEx Certified, UKCA Ex Certified, and FM approved. Certificates include EU-type certificate No.: EMT17ATEX0021 X, IECEx Certificate of Conformity: Element IECEx EMT 17.0007X, and UKCA Ex Certificate of Conformity: EMA22UKEX0066X.
- Process Connection: 1/2" male NPT or 1/2" male BSPT with wetted materials in 316 SS. The probe stem length ranges from 2" to 18" depending on the model, and the pressure rating is 2000 psi (137.9 bar).
- Electrical Connection: Terminal block with 6 terminals; conduit connection via 1/2" female NPT or M20.
- Display Option: Optional 2 lines X 8 character LCD display is available on select models (e.g., TTE-104-W-LCD).
Pre-programmed Temperature Ranges
The following ranges are selectable via dip switches 2, 3, and 4:
- 40 to 90°F (4.4 to 32.2°C)
- -20 to 140°F (-28.9 to 60°C)
- 0 to 100°F (-17.8 to 37.8°C)
- 30 to 240°F (-1.1 to 115.6°C)
- 32 to 212°F (0 to 100°C)
- 32 to 122°F (0 to 50°C)
- -30 to 65°C (-1.1 to 18.3°C) — Note: Source lists this range with mixed units as printed.
Key Product Differences
The series includes models with and without the optional LCD display, indicated by the "-LCD" suffix in part numbers (e.g., TTE-104-W vs. TTE-104-W-LCD). Stem lengths vary from 2" to 18", corresponding to model codes such as -04 through -18. Units without a specific '2' suffix following the base series name are noted in documentation as not being directive 2014/34/EU (ATEX) Compliant for use in potentially hazardous atmospheres in the EU, though they may be CE marked for other directives.
Accessories
installation hardware
Mounting bracket for pipe or surface mounting (includes bracket and two 2 in U-bolts)
$71.35 / each
28 In Stock
Show Ratings & Reviews