Models In Stock
  • DRSL-RTD Non-Isolated and DRSL-RTD-ISO Isolated Models
  • 2, 3 or 4-Wire Pt100 RTD Input
  • Pre-Calibrated Temperature Ranges Selectable via Dip-Switches
  • Slimline Housing—Only 6 mm (0.24') Wide
DRSL-RTD-Srs-Sig-Cond
From $ 179.43
Models In Stock
DIN Rail RTD Input Signal Conditioner | Low Profile DRSL-RTD-Srs-Sig-Cond DRSL-RTD-Srs-Sig-Cond
loading all models
Product Overview
  • Accuracy Detail Better than 0.2°C or ±0.1% of selected range
  • Approvals CE, UL, RoHS
  • Calibration Temperature, Max 28 °C
  • Calibration Temperature, Min 20 °C
  • Electrical Output 4 to 20 mA
  • EMC Immunity Note NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
  • EMC Standard NAMUR NE 21
  • Enclosure Ratings IP20
  • Height 113 mm
  • Input Range Note Sensor Current, RTD: <150 µA;Sensor Cable Specifications: 50 Ωper wire or 50 nF;Effect of Sensor Cable Resistance (3 or 4-wire RTD): <0.002 Ω/Ω;Broken Sensor Detection: >800 Ω;Shorted Sensor Detection: <18 Ω
  • Input Type RTD
  • Installation Pollution degree 2 and measurement/overvoltage category II
  • Length 115 mm
  • Mounting DIN Rail 35 mm Standard, EN 60715
  • Noise Calibration >60 dB
  • Number of Inputs 1
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -25 °C
  • Output Detail Current: Range Limits(NAMUR NE43 Out of Range):Below 3.8 mA or above 20.5 mA for 4 to 20 mA output; 0 mA or above 20.5 mA for 0 to 20 mA output Sensor Error Detection(Dip Switch Selectable for Enable or None): Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Incorrect DIP-Switch Setting Identification: Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Output Error Level: DIP switch selectable for upscale or downscale. Voltage: Range Limits (Out of Range):Range ±2.5% Sensor Error Detection (Dip Switch Selectable for Enableor None): 0V or selected range + 10% Incorrect DIP-Switch Setting Identification: 0V Output Error Level: DIP switch selectable for upscale or downscale
  • Output Signal Current, Voltage
  • Output Value Process
  • Power Consumption 0.7 W, Internal - 0.65 W
  • Relative Humidity 0 to 95% RH (non-condensing)
  • Response Time < 30 ms
  • Response Time Note Response Time (0 to 90%, 100 to 10%): <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed)
  • Screw Terminal Torque 0.5 Nm
  • Series ID DRSL-RTD-Srs-Sig-Cond
  • Stability Load Stability: ≤0.01% of span/100 Ω
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Power Type DC
  • Supply Voltage 16.8 to 31.2 Vdc
  • Temperature Coefficient ≤±0.02°C/°C
  • Voltage Output Range 0 to 10 Vdc
  • Weight 70 g
  • Width 6.1 mm
  • Wire Gauge 26 to 13 AWG

Supported Applications

The Omega DRSL-RTD Series consists of DIN rail signal conditioners designed to interface RTD inputs with SCADA systems or PLC equipment. The series converts signals from 2, 3, or 4-wire Pt100 RTDs into unipolar analog outputs suitable for industrial control environments.

Operating Conditions & Performance

The DRSL-RTD Series operates over an ambient temperature range of -25 to 70°C (-13 to 158°F) with a storage capability from -40 to 85°C (-40 to 185°F). The units support relative humidity levels of 0 to 95% RH non-condensing and carry an IP20 protection degree. Measurement ranges span -200 to 850°C (-328 to 1562°F) with a sensor current below 150 μA.

Accuracy specifications differ by model: the DRSL-RTD offers better than 0.2°C or ±0.1% of selected input range, while the isolated DRSL-RTD-ISO provides better than 0.1°C or ±0.05% of selected input range. Response time is selectable at <30 ms/300 ms (0 to 90%, 100 to 10%). The series includes broken sensor detection (>800 Ω) and shorted sensor detection (<18 Ω).

Configuration Options

The series supports configuration via DIP-switches for more than 1,000 factory-calibrated measurement ranges. Output signals are programmable to match specific system requirements.

  • Output Signals: Current outputs include 0 to 20 mA and 4 to 20 mA; voltage outputs include 0 to 10 V, 2 to 10 V, 0 to 5 V, and 1 to 5 V.
  • Power Supply: DRSL-RTD models accept 16.8 to 31.2 Vdc via connectors; DRSL-RTD-ISO models accept 16.8 to 31.2 Vdc via power rail or connectors.
  • Isolation (DRSL-RTD-ISO Only): Provides 3-way isolation between input, output, and supply with a test voltage of 2.5 kVac (reinforced) and working voltage of 300 Vac.
  • Error Detection: Sensor error detection is selectable via DIP-switch for enable or none; incorrect DIP-switch settings trigger specific out-of-range outputs.

Mechanical installation features DIN EN 60715 - 35 mm rail mounting with screw terminals accepting wire sizes from 0.13 x 2.5 mm² / AWG 26 to 12 stranded wire (torque: 0.5 Nm). The unit dimensions are 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") with an approximate weight of 70 g (0.15 lb).

Key Product Differences

The series is available in two primary configurations:

  • DRSL-RTD: Non-isolated RTD input DIN rail signal conditioner.
  • DRSL-RTD-ISO: Isolated RTD input DIN rail signal conditioner offering surge suppression and protection against transients and noise. This model requires the DRSL-PWR-RAIL power rail for operation when using the rail interface.

Accessories available for the series include the DRSL-PWR-RAIL (1 m length, with cover and end covers), DRSL-PCU (power connector unit, 24 Vdc/2.5 A output), and DRSL-MOD-STOP (module stop). The OMEGACARE™ extended warranty program is available for these models.

Accessories

installation hardware

MODULE STOP FOR DRSL SERIES
$11.46 / each
5 In Stock
POWER RAIL FOR DRSL SERIES
$233.43 / each
0 In Stock

meters/controllers

PWR CONN FOR DRSL SERIES CE
$149.92 / each
9 In Stock
Rated 5 out of 5 by from Excellent accuracy I bought this to be used in a test lab where temperature accuracy is 0.1C and the DRSL has stood up to the expectation. Excellent accuracy, stability, form factor and ease of use.
Date published: 2019-05-14
Rated 5 out of 5 by from Great converter Easy to get up and running. I have several up and running for years.
Date published: 2026-03-09
  • y_2026, m_8, d_9, h_10
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_2
  • loc_en_US, sid_DRSL-RTD, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT

I have 4 of these and only one is working all are setup identically. However I'm only recieving 3.45mA on the output and even on the one that is working there is no LED light on to be found

Asked by: Anonymous
Thank you for your question. We will require more information to help on this question, please email the DAS team at DAS@dwyeromega.com
Answered by: PVLENG
Date published: 2025-04-01
  • y_2026, m_8, d_9, h_10CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_1
  • loc_en_US, sid_DRSL-RTD, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 10ms
  • QUESTIONS, PRODUCT
en-US
en
Save Configuration