Skip to search Skip to main content Skip to navigation

1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here

We noticed you are from . Visit your local site for regional offers and live support.

DRSL-SP2-Rptr-Spltr

DIN Rail Isolated Repeater/Splitter for Process Signals.

Models In Stock
  • Isolation and Conversion of Process Voltage or Current Signals
  • Splitter Function: 1 Process Input–2 Process Outputs
  • Power Supply and Signal Isolator for 2-Wire Transmitter
  • Slimline Housing–Only 6 mm (0.24') Wide
DRSL-SP2-Rptr-Spltr
From $ 329.92
Models In Stock
DIN Rail Isolated Repeater/Splitter for Process Signals. DRSL-SP2-Rptr-Spltr DRSL-SP2-Rptr-Spltr
loading all models
Product Overview
  • Approvals CE, UL, RoHS
  • Calibration Temperature, Max 28 °C
  • Calibration Temperature, Min 20 °C
  • Electrical Output 0 to 20.5 mA
  • EMC Immunity Note Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
  • EMC Standard NAMUR NE 21
  • Enclosure Ratings IP20
  • Height 113 mm
  • Installation Pollution degree 2 and measurement/overvoltage category II
  • Isolation Isolation: Input/output 1/output 2/supply;Isolation Voltage (Test): 2.5 kVac;Isolation Voltage (Working):300 Vac
  • Length 115 mm
  • Load Resistance Current Output : 23 mA/300 Ω max;Voltage Output : >10 kΩ min
  • Mounting DIN Rail 35 mm Standard, EN 60715
  • Noise Calibration >60 dB
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -25 °C
  • Output Value Splitter
  • Power Consumption 1.2 W, Internal - max 0.65 W
  • Relative Humidity 0 to 95% RH (non-condensing)
  • Screw Terminal Torque 0.5 Nm
  • Span, Max Corresponds to the presently selected DIP switch output range
  • Stability Load Stability: ≤0.01% of span/100 Ω
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Power Type DC
  • Voltage Loss <1.5 V
  • Weight 70 g
  • Width 6.1 mm
  • Wire Gauge 26 to 12 AWG
The DRSL-SP2 isolated signal conditioner/splitter provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. Two process outputs are provided which mirror the single process input.
The DRSL-SP2 can be used for signal conversion of standard process voltage or current signals into two individual analog signals. The unit offers 4-port isolation, provides surge suppression and protects control systems from transients and noise. The DRSL-SP2 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. When the input is configured for 2-wire transmitter mode, the DRSL-SP2 provides the current loop supply voltage. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

Accessories

installation hardware

Module stop (screwed onto DIN rail to support and hold mounted devices)
$11.23
35 In Stock
Power rail (with cover and two end covers, one right hand and one le ft hand), 1 m (3.3 ft) length
$228.76
4 In Stock

meters/controllers

Power connector unit, 24 Vdc/2.5 A output to power rail
$146.92
14 In Stock
Rated 5 out of 5 by from Not Hard to Implement I was worried by the other review, but after reading the manual and wiring diagram it did not seem too complex to me. Implemented it in a retrofit, buying another one now. They work great and are not hard. Anyone with electrical literacy will be fine.
Date published: 2023-06-08
Rated 1 out of 5 by from Worst possible instructions I defy anyone to wire this without outside help. The manual is a translation where every key word was left out.
Date published: 2016-07-21
  • y_2025, m_10, d_21, h_11
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_2
  • loc_en_US, sid_DRSL-SP2, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 3ms
  • REVIEWS, PRODUCT
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 25ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en
Save Configuration