1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here
CDSN
Carbon Dioxide/Temperature transmitter, wall mount, universal current/voltage output, 2000 PPM

Choose a Variant
measurement-type
Added to Your Shopping Cart
Configuration complete.
Please add to cart to keep it or exit the configuration
Please add to cart to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product ModelsBrand |
![]() |
Applications | HVAC |
Carbon Dioxide Accuracy | ± 40 PPM + 3% rdg |
Carbon Dioxide Concentration, Max | 2000 ppm |
Carbon Dioxide Concentration, Min | 0 ppm |
Carbon Dioxide Response Time | 120 s (τ90) |
Compliance | CE |
Display Type | N/A |
Electrical Connection | Screw Terminal |
Electrical Output | 0 to 20 mA |
Enclosure Ratings | IP30, NEMA Type 1 |
Materials | ABS |
Measurement Type | Carbon Dioxide |
Mounting Orientation | N/A |
Operating Temperature, Max | 122 °F |
Operating Temperature, Min | 32 °F |
Output Detail | Field selectable; Current: 4-20 mA or 0-20 mA; Voltage: 0-5 V, 1-5 V, 0-10 V, or 2-10 V |
Output Signal | Current, Voltage |
Relative Humidity | 0 to 85% RH Non-Condensing |
Sensor Life | 15 Years |
Sensor Type | NDIR |
Storage Temperature, Max | 158 °F |
Storage Temperature, Min | -22 °F |
Supply Power Note | ± 20%, 50/60 Hz |
Supply Power Type | AC/DC |
Supply Voltage | 24 Vac/Vdc |
Switch Type | N/A |
Temperature Accuracy | ± 1 °C |
Temperature Output Range | N/A |
Voltage Output Range | 0 to 5 V, 1 to 5 V, 0 to 10 V, 2 to 10 V |
Warm Up Time | <2 mins Operational; 10 mins Max Accuracy |
measurement-type | Carbon Dioxide |
See All Specs |
PDFs & Manuals
Show Ratings & Reviews