Need assistance? Call us: 1-800-663-4209
Series-CLS2
Capacitive Level Switch, PVDF/316 SS, DPDT Output, Weatherproof
Models In Stock
- Automatic Calibration: No need to turn calibration pots, just push the calibration button. The CLS2 even has an external magnet to activate the calibration without having to open the enclosure.
- Universal Power Supply: One model works from 12 to 240 VAC/DC without any jumpers or settings.
- Coat Guard: Unit is not affected by sticky, dusty, or clingy materials that coat or build up on the probe preventing false alarms.
- Failsafe Setting: Output switches can be set for Normally Open or Normally Closed condition on loss of power.
- Status Indication: Ultra high brightness external red LED switch status indicator, and internal indicators for power, sensor, and switch status that can be seen externally with window cap option (external LED on weatherproof model only).
- Time Delay: Prevent false alarms from material splashing, agitation, etc.
- Removable Terminals: Removable terminal block snaps in and out enabling easy wiring outside of the enclosure.
- No Moving Parts: Permitting for no jams, no wear, nothing to break, and no maintenance.
- Impulse RF: Admittance measurement combined with an active guard, provides excellent level measurement and stability while being insensitive to material buildup.
- Immune To: External RF sources like walkie-talkies and cell phones as well as minimal interference with radio communication or other electronic systems.
- Can Be Used For: Liquid interface applications to detect the level of two immiscible liquids that have different dielectric constants such as oil and water.
- Wetted Materials: PVDF and 316 SS assure great chemical compatibility and meet food grade requirements.
Series-CLS2
From
$
823.75
Models In Stock
Can't find the right model?
Use our custom configurator to fine tune your product
Product Overview
- Applications Chemical Refineries, Chemicals, Food and Beverage
- Electrical Connection 1/2 in NPT female Conduit with Screw Terminal block
- Electrostatic Discharge 10 M Ω
- Enclosure Ratings IP66, NEMA Type 4X, Weatherproof
- Materials, Wetted 316 SS, Polyvinylidene Fluoride
- Media Compatibility Dry bulk solids / powders, Liquids, Powders
- Mounting Orientation Horizontal, Vertical
- Operating Temperature, Max 185 °F
- Operating Temperature, Min -4 °F
- Power Consumption 2.8 W
- Measurement Pressure, Max 365 psi
- Probe Type Standard rod: 316 SS, .375˝ diameter
- Process Connection Size 3/4 in
- Process Connection Type NPT Male
- Process Temperature, Max 250 °F
- Process Temperature, Min -40 °F
- Response Time 0.2 s
- Sensitivity 8 selectable settings, 1, 2, 4, 6, 8, 10, 14, 20 pF
- Sensor Break Detection Switch selectable, high/low
- Series ID Series-CLS2
- Supply Power Type AC
- Supply Voltage 12 to 240 VAC/DC
- Switch Rating 8 A @ 12/240 VAC, 30 VDC
- Switch Type DPDT
- Time Delay 0 to 60 sec
- Weight 2 lb
Supported Applications
The Dwyer Series CLS2 is a capacitive level switch designed to sense material levels in liquids, powders, and bulk materials compatible with its wetted materials. The series utilizes impulse RF admittance measurement combined with an active guard mechanism to provide stability while remaining insensitive to material buildup on the probe. Documented applications include pulp and paper processing, chemical processing, food and beverage, plastics, and mining.
Operating Conditions & Performance
The Series CLS2 operates within specific environmental limits defined by its power supply configuration. The ambient temperature range is -40 to 185°F (-40 to 85°C); when using a power supply under 24 VAC/DC, the lower limit adjusts to -4 to 185°F (-20 to 85°C). Process temperatures are rated from -40 to 250°F (-40 to 121°C). The unit features an enclosure rating of Weatherproof, NEMA 4X. Performance specifications include a response time of 0.2 s and a pressure limit of 365 psi (25 bar).
Electrical ratings for the DPDT switch are 8 A @ 12/240 VAC resistive or 30 VDC resistive, with motor loads rated at 1/2 hp @ 120 VAC and 1/4 hp @ 240 VAC inductive. Power requirements span 12-240 VAC/DC with a maximum power consumption of 2.8 watts.
Key Performance Features
- Sensitivity: Eight selectable settings (1, 2, 4, 6, 8, 10, 14, and 20 pF) at a nominal free capacitance of 30 pF.
- Time Delay: Adjustable from 0 to 60 s to prevent nuisance triggering from splashing or tank disturbances.
- Failsafe Mode: Selectable relay output (normally open or normally closed).
- Status Indication: Ultra-high brightness external red LED for level status; three internal multicolored LEDs for diagnostics.
Configuration Options
The Series CLS2 offers a configurable envelope to accommodate diverse installation requirements. The series supports various probe types, process connections, and optional features as detailed below:
Probe Types & Dimensions
- Rod (Code R): Standard 316 SS rod with .375" diameter.
- Cable (Code C): 316 SS cable with weight.
- Threaded Rod (Option T): 316 SS rod, .375" diameter, with a 3/8-16 threaded tip; field extensions up to 47" (1.2 m) can be attached.*
- Insertion Length: Configurable in inches (e.g., code Ø19 indicates 19"). Minimum length is 6", featuring a 3/4" sensing tip.
Process Connections & Materials
- NPT Male: Available in 3/4", 1", and 1-1/2" sizes (Codes 1, 2, 3).
- BSPT: Available in 3/4", 1", and 1-1/2" sizes (Codes 4, 5, 6).
- Sanitary Clamp: Options for 1-1/2" (Code 7) or 2" (Code 8).
- Wetted Materials: Constructed of 316 SS and polyvinylidene fluoride (PVDF). A "Food grade wetted materials" option is available.
Housing & Electrical Options
- Enclosure: Weatherproof/corrosion resistant, NEMA 4X (Code W).
- Electrical Connection: Standard 1/2" NPT conduit opening with screw termination and removable terminal block.
- M20 Conduit Option: M20 conduit connection with gland available as an option.
Special Features & Adjustments
- Calibration: Automatic calibration is standard; manual initiation via internal switch or external magnet allows adjustment without removing the cover.
- Probe Modification: The probe can be cut to a minimum of 1" or extended by welding to set the trip point, though minimum length may vary based on material sensed.
- Safety Features: Includes spark/static protection with 10 M Ω dissipation resistance and surge current handling up to 100A max. The unit is immune to external RF sources such as walkie-talkies and cell phones.
Key Product Differences
The Series CLS2 distinguishes itself through its configurable model structure, allowing selection of specific enclosure types (Weatherproof), switch configurations (DPDT rated 8 A @ 12/240 VAC res., 30 VDC res.), and power supply ranges. Variations are primarily defined by the probe type (Standard rod vs. Cable with weight) and process connection geometry (NPT, BSPT, or Sanitary clamp). The series supports both vertical and horizontal mounting orientations.
For sanitary applications utilizing a Sanitary Process Connection, the unit is suitable for "Clean In Place" methods but must be cleaned and/or sanitized in accordance with appropriate guidelines prior to installation. The device carries cULus agency approvals.
PDFs & Manuals