1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here

Series-AT-ADPS
ATEX/IECEx Differential Pressure Switch, 0.08-20 inH2O, Flameproof
- Flameproof enclosure with optional glass window and aluminum housing protects the device in hazardous areas while giving local visibility to set point status
- Increased response time at low pressures with LD port configuration
Series-AT-ADPS
From
$
0.00

Can't find the right model?
Use our custom configurator to fine tune your product
Product Overview
- Approvals ATEX Certificate: INERIS 21ATEX0033X, IECEx Certificate: IECEx INE 21.0064X
- Compliance CE, Ex
- Compliance Note ATEX: 0080 II 2G Ex db IIC T5, T6 Gb -60°C≤Ta≤+50°C (T6) -60°C≤Ta≤+60°C (T5); II 2D Ex tb IIIC T75°C Db; IECEx: Ex db IIC T5, T6 Gb -60°C≤Ta≤+50°C (T6) -60°C≤Ta≤+60°C (T5) Ex tb IIIC T75°C Db.
- Electrical Connection 1/2 in NPT female Conduit with Screw Terminal block
- Enclosure Ratings IP66
- Materials, Wetted Brass, Nylon 6.6, POM, Silicone
- Mechanical Life >10^6 cycles
- Media Compatibility Air, Argon, Carbon dioxide, Helium, Nitrogen, Non-Corrosive Dry Gases
- Mounting Orientation Vertical with Downward Pressure Ports
- Operating Temperature, Max 185 °F
- Operating Temperature, Min -4 °F
- Pressure Type Differential
- Process Connection Note 1/8˝ NPT female brass (SS optional)
- Process Connection Size 1/8 in
- Process Connection Type NPT Female
- Proof Pressure Up to 10 kPa
- Set Point Adjustment Hand Knob (Inside Case)
- Switch Note Standard: Max. 1.5 A @ 250 VAC, max. switching rate: 6 cycles/ min
- Switch Rating 1.5 A @ 250 Vac
- Switch Type SPDT NO/NC, Selectable
- Weight 4.7 kg
The Series AT-ADPS ATEX/IECEx Approved Differential Pressure Switch is designed for pressure, vacuum, and differential pressure applications in hazardous areas. The dual scaled adjustment knob in inches water column and Pascals allows changes to the switching pressure to be made without a pressure gage. The switch is available with settings from 0.08 in w.c. (20 Pa) up to 20 in w.c. (5000 Pa). The silicone diaphragm makes this series ideal for use with air and other noncombustible gases. Flameproof enclosures are available in aluminum and can include a glass window for viewing set point status on the adjustment knob.
Important notes for installation:
• Cables must be fitted through 1/2" NPT cable gland or ATEX/IECEx conduit (not supplied with instrument).
• Make sure after cabling to close tight cover and cable gland, in order to maintain IP66 rating.
• Open cover only after de-energizing instrument.
Attention: Check local safety rules and warnings on unit and manual for a correct use of the instrument in hazardous areas.
Please see Series ADPS for non-ATEX/IECEx approved.
Product Applications
- Hazardous area pressure switch
- Air filter and ventilator monitoring
- Ventilation duct monitoring
- Industrial cooling circuits
- Fan heater overheating protection
- Fire-protection damper control
- Heat exchanger frost protection
PDFs & Manuals