PXP

Analog to Pneumatic Output Transducer for 18 to 25 psig Air Supply Pressure

  • Converts analog control signals into pneumatic output: The PXP Series accepts 0-5 VDC, 0-10 VDC, 0-15 VDC, or 0-20 mA input signals and produces a proportional 0-15 psig pneumatic output.
  • Ideal for HVAC pneumatic control: Designed for three-way mixing valves, pilot positioners, pneumatic valve and damper actuators, fan vane control, DDC systems, mixing boxes, and VAV box applications.
  • Built-in pressure feedback: Provides a 0-5 VDC feedback signal that represents branch line pressure, making it easier to monitor output pressure from a controller or BAS.
  • Flexible model options: Available in single-valve, constant-bleed, low-consumption, fail-safe, and high-flow configurations to match different pneumatic control requirements.
  • Manual override for setup and service: Jumper-selectable manual override allows technicians to control output pressure during installation, checkout, and troubleshooting.
  • Reliable operation in control panels and ceiling spaces: Compact snaptrack-mounted design with removable terminal blocks and barbed pneumatic fittings supports clean installation in panels or above-ceiling HVAC applications.
  • Accurate pneumatic modulation: Delivers 1% full-scale accuracy at room temperature and 2% full-scale accuracy across the operating range for dependable actuator positioning.
  • Service-friendly connections: Includes removable brass barbed fittings, pluggable screw terminals, integral air filtration, and a plugged gauge port with optional pressure gauge support.
PXP
From $ 363.00
Analog to Pneumatic Output Transducer for 18 to 25 psig Air Supply Pressure PXP PXP
loading all models
Product Overview
  • Accuracy Detail Output Pressure Accuracy: 1% full scale @ room temperature
  • Air Supply Pressure, Max 25 psi
  • Air Supply Pressure, Min 18 psi
  • Applications Air and HVAC, Building and Maintenance, Environmental Monitoring, Pneumatic Systems
  • Approvals RoHS2, WEEE
  • Auto/Manual function Manual / Auto Override: MAN function = output can be varied
  • Electrical Connection Screw Terminal
  • Filter Furnished with integral-in-barb 80-100 micron lter (Part # PN004) except for PXP2LG which is furnished with external 5 micron in-line lter (PN021)
  • Height 2.18 in
  • Impedance Input Input Signal Source (@ Impedance): 0-5 VDC @ 10,000 Ω
  • Input Type Analog
  • Length 3.25 in
  • Materials PVC
  • Operating Humidity 10 to 95% RH, non-condensing
  • Operating Temperature, Max 120 °F
  • Operating Temperature, Min 35 °F
  • Output Note Feedback Signal Output Range: 0-5 VDC = Output Span
  • Output Pressure Range 0 to 15 psi
  • Pressure Note Gauge Pressure Range (Gauge Models): 0-30 psig (0-200 kPa)
  • Series ID PXP
  • Storage Temperature, Max 150 °F
  • Storage Temperature, Min -20 °F
  • Supply Voltage 24 Vac/Vdc
  • Tightening Torque 0.5 Nm (Minimum); 0.6 Nm (Maximum)
  • Tube Size 1/4 in OD x 1/8 in ID
  • Width 2.18 in
  • Wire Gauge 26 to 16 AWG
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 6ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 19ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en
Save Configuration