Series-AFP
Analog to Floating Point Interface for Electric Actuator Control
Models In Stock
- Converts analog signals to floating point control: AFP modules let voltage or current signals control floating point actuators using two relay outputs for increase and decrease commands.
- Flexible input compatibility: Supports common voltage and current ranges including 0-5 VDC, 0-10 VDC, 0-15 VDC, 0-20 mA, 1-5 VDC, 2-10 VDC, 3-15 VDC, and 4-20 mA.
- Ideal for electric actuator control: Designed for applications where a controller analog output needs to drive floating point damper, valve, or actuator positioning.
- Selectable actuator timing: Multiple firmware versions and DIP-switch selectable rates of change allow the AFP to match a wide range of actuator stroke times.
- Reliable relay output design: Provides isolated dry-contact Form C relay outputs rated up to 2A at 24 VDC, with separate increase and decrease contacts.
- Automatic startup positioning: On power-up, the AFP drives the actuator to a known minimum or maximum position depending on version, helping synchronize control signal and actuator position.
- Installer-friendly terminals: 90° pluggable screw terminal blocks accept 16 to 26 AWG wire for straightforward panel wiring and service.
- Compact snaptrack package: PVC UL94 V-0 snaptrack housing supports clean interface-panel mounting, with optional DIN rail adapter kit available.
- Backed by ACI quality: RoHS2 and WEEE compliant, with ACI’s two-year limited warranty for dependable interface control applications.
Series-AFP
From
$
278.00
Models In Stock
Product Overview
- Applications Building and Maintenance
- Approvals RoHS2, WEEE
- Control Output 2 Relays
- Current Input Range 4 to 20 mA
- Electrical Connection Screw Terminal
- Electrical Life 100,000 operations minimum
- Height 1.15 in
- Impedance Input Voltage @ 10,000Ω Nominal / Current @ 250Ω nominal
- Input Current 0 to 20 mA
- Input Type Analog
- Input Voltage Note 0-5 VDC, 0-10 VDC, 0-15 VDC
- Length 4 in
- Materials PVC
- Mechanical Life 1 million operations
- Operating Humidity 10 to 95% RH, non-condensing
- Operating Temperature, Max 120 °F
- Operating Temperature, Min 35 °F
- Relay Output 2 A max @ 24 VDC
- Series ID Series-AFP
- Storage Temperature, Max 150 °F
- Storage Temperature, Min -20 °F
- Supply Current 190 mA
- Supply Voltage 24 Vac/Vdc
- Tightening Torque 0.5 Nm (Minimum); 0.6 Nm (Maximum)
- Voltage Input Range 1 to 5 Vdc, 2 to 10 Vdc, 3 to 15 Vdc
- Weight 0.325 lb
- Width 3.25 in
- Wire Gauge 26 to 16 AWG
Supported Applications
The ACI Series AFP (Analog to Floating Point) interface is designed for electric actuator control. It converts an analog voltage or current signal into two isolated relay contact outputs—one for increase and one for decrease—to drive floating point actuators.
Operating Conditions & Performance
The unit operates on a 24 VAC or 24 VDC (+/- 10%), 50/60 Hz power supply. It accepts nine analog input signal ranges: 0-5 VDC, 0-10 VDC, 0-15 VDC, and 0-20 mA as standard inputs; with an offset jumper configured, it supports 1-5 VDC, 2-10 VDC, 3-15 VDC, and 4-20 mA. Input impedance is nominal at 10,000Ω for voltage signals and 250Ω for current signals.
Relay outputs are Dry Contact, Form C, rated for a maximum of 2A @ 24 VDC. The relay electrical life is specified as 100,000 operations minimum, with a mechanical life of 1,000,000 operations. Upon power-up, the decrease relay drives 100% of the chosen timing range to ensure the output reaches its minimum position (unless configured otherwise by version). On loss of power, output relays open and no signal is generated; the actuator remains at the last commanded position unless it has 'spring return'.
Operating conditions are 35 to 120°F (1.7 to 48.9°C) ambient temperature and 10 to 95% non-condensing humidity. Storage temperature range is -20 to 150°F (-28.9 to 65.5°C). The enclosure material is Polyvinyl Chloride (PVC) with a UL94 V-0 flammability rating.
Rate of Change Configuration
The AFP output rate of change is DIP switch selectable across sixteen ranges organized into eight versions:
- Version #1 (AFP_0101.hex): 30 sec., 60 sec., or 90 sec.
- Version #2 (AFP_0201.hex): 120 sec., 150 sec., or 180 sec. Drives actuator down 200% of range on power reapplication; at input signals between 2-5% or below and 95-98% or higher, the up or down contact drives an additional 100% of the chosen timing range.
- Version #3 (AFP_0301.hex): 14 sec., 16.5 sec., or 19 sec.
- Version #4 (AFP_0401.hex): 30, 60, or 90 sec. Relay stays on at minimum and maximum voltage.
- Version #5 (AFP_0501.hex): 90, 135, or 180 sec. Relay stays on with 5% of maximum or minimum input voltage; no overshoot occurs at max or min input voltage.
- Version #6 (AFP_0601.hex): 18, 75, or 360 sec.
- Version #7 (AFP_0701.hex): 30, 60, or 90 sec. Drives actuator up 105% of range on power reapplication.
- Version #8 (AFP_0801.hex): 46, 240, or 600 sec.
Jumper Settings
The unit includes configurable jumpers for input signal type and offset:
- J3 (Input Signal Type): Selects between 10V, 15V, or 20mA.
- J6 (Offset Jumper): Moving the jumper to ON adds an offset to the input signal based on the selected range (e.g., converting 0-5 VDC to 1-5 VDC). The jumper must remain in the CD setting when not adding offset.
- J4, J5 (Manual Relay Control): Configurable for Off, Auto, or Manual digital outputs.
Configuration Options
The Series AFP is available in eight distinct versions corresponding to specific firmware and rate-of-change profiles. The unit features 90° pluggable screw terminal blocks compatible with wire sizes from 16 AWG (1.31 mm²) to 26 AWG (0.129 mm²). Terminal block torque rating is 0.5 Nm minimum; 0.6 Nm maximum.
Physical dimensions are (L) 4.00" x (W) 3.25" x (H) 1.15" (101.6 x 82.55 x 29.21 mm). The unit weighs 0.325 lbs. (0.147 Kg).
Available accessories include:
- A/D0008 (Item #142583): Transient Voltage Suppressor, Bi-directional, 56 VAC/DC, 1500W.
- DIN Rail Adapter Kit (A/DRC 3.88 X 3.25, Item #142621).
Agency approvals include RoHS2 and WEEE compliance.
Key Product Differences
Variants within the Series AFP differ primarily by firmware version (AFP_0101.hex through AFP_0801.hex), which dictates the available rate-of-change timing ranges and specific power-up/power-down behaviors. For example, Version #4 maintains relay activation at minimum and maximum voltage inputs, while Version #5 prevents overshoot at signal extremes. Versions 2 and 7 include specialized actuator drive logic (down 200% or up 105%) upon power reapplication.