Need assistance? Call us: 1-800-663-4209
Series-AIM2
Analog Isolation Module w/ Rescaling
Models In Stock
- Optically isolates analog signals: AIM2 isolates voltage or current inputs from corresponding outputs to help solve ground loop and signal interference problems.
- Broad signal flexibility: Accepts signals from 0-20 VDC or 0-20 mA and can output any signal within those ranges.
- Preset or adjustable ranges: Supports common presets such as 0-5 VDC, 0-10 VDC, 1-5 VDC, 2-10 VDC, 0-20 mA, and 4-20 mA, plus field-adjustable custom ranges.
- Supports source and sink current: Current inputs and outputs can be configured as sink or source for compatibility with different controllers, actuators, and drives.
- Ideal for isolation applications: Useful for grounded electrical actuator isolation, fluorescent light dimmer isolation, VFD isolation, and general analog input/output isolation.
- Built-in isolated output power: Includes an onboard 24 VAC isolation transformer to supply the isolated output side.
- Field calibratable: Adjustable input and output calibration lets installers tailor the module to unique signal requirements, with factory calibration available when needed.
- Panel-ready design: UL94 V-0 snaptrack housing, 45° captive screw terminals, and optional DIN rail adapter support clean control-panel installation.
- Backed by ACI quality: RoHS2 and WEEE compliant, with ACI’s two-year limited warranty.
Series-AIM2
From
$
403.00
Models In Stock
Product Overview
- Accuracy ± 3 %
- Approvals RoHS2, WEEE
- Electrical Connection Screw Terminal
- Height 1.2 in
- Impedance Input Input Voltage Impedance: 9,500Ω; Input Current Impedance: 250Ω +/-1%
- Impedance Output Note Output Voltage Impedance: 5,000Ω; Output Current Impedance: 500Ω
- Input Type Note Input Voltage Signal Preset Ranges: 0-5V, 0-10V, 0-15V, 0-20V, 1-5V, 2-10V, 3-15V, 4-20V, 0-1V; Input Current Signal Preset Ranges: 0-20 mA, 4-20 mA, 0-1 mA;Input Signal Adjustable Voltage Span: 1 VDC (Minimum) to 20 VDC (Maximum); Input Signal Adjustable Voltage Oset: From 0 to 20 VDC; Input Signal Adjustable Current Span: 4 mA (Minimum) to 20 mA (Maximum); Current Oset: From 0 to 20 mA
- Isolation 600VAC / 1500 VDC Maximum
- Length 4.6 in
- Linearity +/- 1%
- Materials PVC
- Operating Humidity 10 to 95% RH, non-condensing
- Operating Temperature, Max 120 °F
- Operating Temperature, Min 35 °F
- Output Configurations Rescalable
- Output Note Output Voltage Signal Preset Ranges: 0-5 VDC, 1-5 VDC, 0-10 VDC, 2-10 VDC
- Series ID Series-AIM2
- Storage Temperature, Max 150 °F
- Storage Temperature, Min -20 °F
- Supply Current 200 mA
- Supply Voltage 24 Vac/Vdc
- Tightening Torque 0.5 Nm (Minimum); 0.6 Nm (Maximum)
- Weight 0.525 lb
- Width 3.23 in
Supported Applications
The ACI Series AIM2 is an analog input to optically isolated analog output interface designed to isolate voltage or current signals. Documented applications include grounded electrical actuator isolation, fluorescent light dimmer isolation, ground loop isolation, variable frequency motor drive isolation, and general analog signal input and output isolation.
Operating Conditions & Performance
The AIM2 operates within an ambient temperature range of 35 to 120°F (1.7 to 48.9°C) and a humidity range of 10 to 95% non-condensing. Storage is supported from -20 to 150°F (-28.9 to 65.5°C). The device provides analog optical isolation rated at 600VAC / 1500 VDC Maximum with an accuracy of +/- 3% and linearity of +/- 1%. It requires a supply voltage of 24 VAC (+/- 10%), 50/60 Hz, drawing up to 200 mA maximum. Input impedance is specified as 9,500Ω for voltage signals and 250Ω +/-1% for current signals.
Signal Ranges
The series accepts input signals between 0 and 20 VDC or 0 and 20 mA. Preset input ranges include:
- Voltage: 0-5V, 0-10V, 0-15V, 0-20V, 1-5V, 2-10V, 3-15V, 4-20V, and 0-1V.
- Current: 0-20 mA, 4-20 mA, and 0-1 mA.
Preset output ranges include:
- Voltage: 0-5 VDC, 1-5 VDC, 0-10 VDC, and 2-10 VDC.
- Current: 0-20 mA and 4-20 mA.
The device also supports adjustable spans for both input and output signals. Adjustable voltage span ranges from 1 VDC (Minimum) to 20 VDC (Maximum), with offsets configurable from 0 to 20 VDC on the input side and 0 to 10 VDC on the output side.
Power Requirements
The AIM2 requires an external 24 VAC isolation transformer with a floating secondary for power. The device cannot be connected or shared with any other device; it needs its own isolated transformer. An onboard 24 VAC isolation transformer is included to supply power to the isolated output.
Physical Specifications
The unit features dimensions of (L) 4.60" (W) 3.23" (H) 1.20" (116.84 x 81.90 x 30.48 mm) and weighs 0.525 lbs. (0.238 Kg). The snaptrack material is Polyvinyl Chloride (PVC) with a UL94 V-0 flammability rating.
Configuration Options
The Series AIM2 offers configurable input and output signals via DIP switches, allowing selection of preset ranges or adjustable spans. Current outputs can be configured as sink or source types. The device is field calibratable, with factory calibration available upon request for an additional charge.
Connections
The unit utilizes 45° Captive screw Terminal Blocks compatible with wire sizes from 12 (3.31 mm²) to 22 AWG (0.33 mm²). The terminal block torque rating is specified as 0.5 Nm (Minimum); 0.6 Nm (Maximum).
Approvals
The AIM2 carries RoHS2 and WEEE approvals.
Accessories
Available accessories include:
- LE105 (Item # 102553): Primary Voltage: 24 VAC, 50/60 Hz | Secondary Voltage: 24 VAC (VA: 40) (Hubs: 1) (Manual Reset: TC).
- A/DRC 4.69 X 3.25 (Item # 142620): DIN Rail Adapter Kit.
Key Product Differences
The Series AIM2 is offered as a single model configuration: AIM2 - <Item #>. The device distinguishes itself through its ability to handle both voltage and current inputs/outputs with optical isolation, supporting specific preset ranges defined by DIP switch configurations. Unlike general-purpose conditioners that may require external power supplies for the isolated side, this series includes an onboard 24 VAC isolation transformer specifically designed to supply the isolated output.
Configuration differences are managed through internal DIP switches which define input and output spans (Tables 1-6 in documentation). These allow selection between fixed ranges such as "0 - 5V" or adjustable options like "Adj. 1 - 9V." The series does not offer multiple housing styles; it is supplied with a standard PVC snaptrack enclosure.