Need assistance? Call us: 1-800-663-4209
Series-ARM2
Analog Current/Voltage Rescaling Signal Splitter
- Splits one analog signal into two outputs: The ACI ARM2 accepts a single voltage or current input and provides two matching DC current sourcing outputs that track together.
- Ideal for signal loop monitoring: Use it when one sensor or controller signal needs to be shared with two devices, controllers, or monitoring points.
- Flexible signal rescaling: Supports voltage-to-current, current-to-current, and resistance-to-current conversion for adapting non-compatible control signals.
- Adjustable field calibration: Multi-turn potentiometers allow fine adjustment of gain, offset, attenuation, and reverse-acting output for precise setup.
- Improves control system compatibility: Helps shrink or expand sensor ranges, increase analog input resolution, and match signal ranges to BAS requirements.
- Reverse signal capability: Can reverse the output signal, making it useful when equipment requires opposite-acting control logic.
- Built-in sensor power: Includes a regulated 23 VDC power output to support compatible sensors in signal conversion applications.
- Panel-ready design: Compact snap-track mounted module with 45° captive screw terminals supports clean installation in control panels and equipment enclosures.
Series-ARM2
From
$
247.00
Product Overview
- Accuracy Detail Signal Output Accuracy: Less than or equal to 1% of output span over full temperature range when using 1:1 input to output
- Applications Building and Maintenance, Electronic Equipment, Environmental Monitoring
- Approvals RoHS2, WEEE
- Electrical Connection Screw Terminal
- Height 1 in
- Impedance Output Note Output Current Load Impedance: 750Ω @ 20 mA
- Input Current 0 to 44 mA
- Input Type Note Input Resistance Signal Range: 0 to 500,000Ω
- Input Voltage Note 0-35 VDC @ 1,000,000Ω
- Length 3.69 in
- Materials PVC
- Operating Humidity 10 to 95% RH, non-condensing
- Operating Temperature, Max 120 °F
- Operating Temperature, Min 35 °F
- Output Configurations Rescalable
- Output Note Field Adjustable Ranges: Multi-turn potentiometers; Output Current Signal Range: Signal Gain 1 to 20 times (nominal) depending on input value;Output Signal Attenuation: 0 to 100%; Output Signal Offset: 0.25 to 20 VDC; Output Signal Inversion (RA): 20 to 0 mA (nominal)
- Series ID Series-ARM2
- Storage Temperature, Max 150 °F
- Storage Temperature, Min -20 °F
- Supply Current 100 mA
- Supply Voltage 24 Vac/Vdc
- Tightening Torque 0.5 Nm (Minimum); 0.6 Nm (Maximum)
- Weight 0.231 lb
- Width 2.17 in