Transmitter-Duct-LT

ACI Low Temperature Duct Temperature Transmitter Series for HVAC Air Monitoring

  • Three-wire RTD design improves measurement accuracy
  • 316 stainless steel probe for reliable performance
  • Teflon lead wires for demanding HVAC environments
  • Optional matched calibration and NIST certification
Transmitter-Duct-LT
From
ACI Low Temperature Duct Temperature Transmitter Series for HVAC Air Monitoring Transmitter-Duct-LT Transmitter-Duct-LT
loading all models
Product Overview
  • Accuracy Detail Transmitter Temp. Spans < 500ºF (260ºC): +/- 0.2%
  • Alloy Material (-) Copper
  • Alloy Material (+) Copper
  • Applications Air and HVAC, Building and Maintenance
  • Curve Type PTC (Positive Temperature Coefficient)
  • Electrical Connection Screw Terminal
  • Fitting 316 Stainless Steel
  • Insulation PTFE
  • Lead Length 8 ft
  • Load Resistance (Terminal Voltage - 8.5 V)
  • Operating Humidity 10 to 90% RH non-condensing
  • Operating Temperature, Max 85 °C
  • Operating Temperature, Min -40 °C
  • Probe Diameter 0.25 in
  • Series ID Transmitter-Duct-LT
  • Sheath Material 304 Stainless Steel
  • Span, Max 370 ºC
  • Span, Min 28 ºC
  • Stability < 0.04 % at 1000 hours at 400ºC
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Current 25 mA, min
  • Supply Voltage 8.5 to 32 Vdc
  • Temperature Accuracy +/- 0.12% Class B
  • Temperature Drift Temp. Spans < 100ºF (38ºC): +/- 0.04%/ºF
  • Temperature Measurement Range -198 to 150 ºC
  • Tightening Torque 0.5 Nm nominal
  • Transmitter Accuracy ± 0.2 %
  • Warm Up Time 10 Minutes with a drfit of +/- 0.1%
  • Wire Gauge 22 AWG
ACI Low Temperature Duct Temperature Transmitters combine a three-wire RTD sensor, Teflon lead wires, and a 316 stainless steel probe for accurate HVAC temperature monitoring. Available with multiple enclosure options and optional NIST-certified calibration.
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 14ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en
Save Configuration