1/4 DIN 6 Zone Universal Input Autotune Ramp & Soak Controller

  • 6 Channel PID Loop
  • Universal TC, RTD and Process Inputs Firmware Selectable
  • User Programmable Alarms Individually Settable per Channel
  • Adjustable Scan Time: 400ms Scan Rate per Channel
CN616A-Series
From $ 1,270.74
1/4 DIN 6 Zone Universal Input Autotune Ramp & Soak Controller CN616A-Series CN616A-Series
loading all models
Product Overview
  • A/D Conversion 24-bit Sigma Delta
  • Accuracy ± 1 mV
  • Accuracy Detail ± 1 mV
  • Additional Features 1 2 Alarm Outputs
  • Approvals ECCN: EAR99 Safety: 2014/35/EU EMC: 2014/30/EU RoHS: 2011/65/EU UL File No: E209855 UL/cUL Listed
  • Channel Display Time 1 to 99 sec
  • Cutout Dimensions 92 × 92 mm
  • Data Interface RS232
  • Data Interface Note Selectable RS232 / RS485 Modbus RTU
  • Depth Behind Panel 140 mm
  • Diameter 135 mm
  • Display Size 15 mm (0.60 in)
  • Display Type Dual 3.5 Digit LED
  • Display Type Note 3.5 Digit Dual Display
  • Electrical Output 4 to 20 mA, 0 to 1 Vdc
  • Enclosure Ratings NEMA Type 1
  • Form factor 1/4 DIN
  • Frequency 50/60 Hz
  • Input Type Thermocouple, RTD, Voltage, Current
  • Input Type Note TC: J, K, T, E, R, S, B, C, N RTD: 2 wire PT100, 0.00385 CU10, 0.00427 NI120, 0.00672
  • Length 95 mm
  • Measurement Type Current, Temperature, Voltage
  • Measuring Range Process Voltage: 0 to 1000 mV Process Current: 0 to 24.00 mA Thermocouple Type J: -150 to 0°C and 0 to 1200°C Type K: -150 to 0°C and 0 to -1372°C Type T: -150 to 0°C and 0 to 400°C Type E: -150 to 0°C and 0 to 1000°C Type R: -50 to 0°C and 0 to 1788°C Type S: -50 to 0°C and 0 to 1768°C Type B: 150 to 700°C and 700 to 1820°C Type C: 0 to 2320°C Type N: -150 to 0°C and 0 to 1300°C RTD (2 wire) Pt, 0.00385, 100 Ω: -200 to 850°C Cu, 0.00427, 10 Ω: -200 to 260°C Ni, 0.00672, 120 Ω: -80 to 260°C
  • Number of Inputs 6
  • Number of Outputs 6
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -20 °C
  • Output Detail 6 Common Drain DC Pulse Outputs Switches up to 36Vdc and 1A, 5Vdc @25mA per channel
  • Power Consumption 3 W
  • Ramp and Soak Multiple Ramp & Soak
  • Resolution 1°, 1 mV, 0.01 mA
  • Scan Rate 400 ms
  • Series ID CN616A-Series
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Voltage 120/240 Vac
  • Weight 725 g
  • Width 95 mm

Supported Applications

The Omega CN616A-Series is a 1/4 DIN, 6-zone universal input autotune ramp and soak controller. Designed for multi-loop control applications, the series provides programmable temperature profiles with ramp and soak capabilities.

Operating Conditions & Performance

The CN616A-Series features a compact 1/4 DIN form factor suitable for panel mounting in industrial automation environments. As a universal input controller, it accepts multiple sensor types to manage process variables across six independent zones or loops.

Key Functional Attributes

  • Housing Size: 1/4 DIN
  • Zones: 6-zone control capability
  • Input Type: Universal input configuration
  • Control Features: Autotune, ramp and soak programming

Configuration Options

The series is available in specific power configurations to accommodate different installation requirements. The documented variants include models with distinct suffixes indicating their electrical interface.

Available Models

  • CN616A: Standard configuration variant.
  • CN616A-DC: Variant designated for DC power applications.

The series supports 6-zone control logic, allowing engineers to program complex thermal cycles involving multiple temperature setpoints and time durations within a single unit. The universal input capability allows flexibility in sensor selection without requiring separate hardware families for different transducer types.

Key Product Differences

The primary distinction between the enumerated variants lies in their power supply designation, as indicated by the model suffixes CN616A and CN616A-DC. Both models share the same 1/4 DIN footprint and core functionality of providing autotune ramp and soak control across six zones.

Specific electrical ratings, accuracy specifications, output types, communication protocols, and detailed dimensional data are not provided in the current source bundle for this series code. Selection should be based on the confirmed universal input architecture and 6-zone programmable capability documented here.

  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;

An internal output power supply provides 5Vdc and 25mA. External output power source voltage range is 3.3-36Vdc, and what is the current rating for the external power supply? thanks

Asked by: AnnaH
Thank you for the inquiry. External power supply should be rated to at least 3 watts. Best regards OMEGA
Answered by: NorwalkAE_RS
Date published: 2023-07-31

What output signals does the controller produce and how do you power the LV series heaters.

Asked by: LArrow
Thank you for your inquiry. This unit has an Internal Control Output Voltage: 5Vdc @25mA per channel which will trigger DC Controlled Solid State Relay whether it controls a AC or DC Load.
Answered by: Application Engineer CB
Date published: 2023-03-29

Will software previously written for the CN616 run on the new CN616A?

Asked by: DPSdave
Thanks for your question. Unfortunately no, but we have a brand new software for CN616A. Omega provides software for the user to work with CN616A out of the box. For setup and configuration, we offer Omega Sync. For long term data logging and integration, you can use OEG. Please contact our Tech Support team if you have any further questions. Omega Sync: https://assets.omega.com/software/CN616A-Series.zip OEG: https://assets.omega.com/software/Omega_Enterprise_Gateway.zip
Answered by: Jane
Date published: 2019-05-15

Where is the full manual? You only have the quickstart guide available.

Asked by: BobDowney
Thank you for your inquiry. You can find the complete manual at https://assets.omega.com/manuals/M5704.pdf
Answered by: Application Engineer JB
Date published: 2020-04-06
  • y_2026, m_8, d_12, h_7CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_4
  • loc_en_US, sid_CN616A, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 10ms
  • QUESTIONS, PRODUCT
en-US
en
Save Configuration