Skip to search Skip to main content Skip to navigation

United Kingdom 0800 488 488 | Intl +44 (0) 161 777 6611 | Welcome to our new website, found an issue or bug? Please report it here

We noticed you are in , please visit your local site by clicking the below link for regional offers and support.

Therm-Pipe-Mount

Thermistor Pipe Mount Sensors

  • Cooling Coils
  • Heating Coils
  • Hot Water Systems
  • Chilled Water Systems
  • Hydronic Heating Systems
  • Chillers
Therm-Pipe-Mount
From
Thermistor Pipe Mount Sensors Therm-Pipe-Mount Therm-Pipe-Mount
loading all models
Product Overview
  • Alloy Material (-) Copper
  • Alloy Material (+) Copper
  • Applications Building and Maintenance, Clean Water and Purified Solutions, Cooling Tower, Environmental Monitoring, Heat and Energy Systems
  • Electrical Connection Pigtail Leads
  • Lead Length 24 in
  • Number of Sensing Points 1
  • Number of Wires 2
  • Operating Temperature, Max 115 °C
  • Operating Temperature, Min -40 °C
  • Pipe Size ½ in to 1 in
  • Probe Diameter 0.188 in
  • Probe Length 1.1 in
  • Response Time 20 Seconds nominal
  • Series ID Therm-Pipe-Mount
  • Sheath Material Brass
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Temperature Measurement Range -40 to 115°C
  • Weight 0.05 lb
  • Wire Gauge 22 AWG

Supported Applications

The ACI Thermistor Pipe Mount Series consists of temperature sensors designed for use with electronic controllers in commercial heating and cooling building management systems. The series is engineered to monitor air temperature within HVAC applications, specifically targeting pipe or coil sizes ranging from ½" (12.7mm) to 1" (25.4mm). These sensors are intended for surface mounting on pipes using a supplied nylon wire tie; they should not be fully submerged in water.

Operating Conditions & Performance

The series operates within an ambient temperature range of -40 to 150°C (-40 to 302°F) and supports storage temperatures from -40 to 85°C (-40 to 185°F). The sensors function in humidity levels between 10 to 95% RH, condensing. Performance characteristics vary by sensor element type:

  • Thermistors (Non-Linear NTC): Accuracy is typically +/-0.2°C (+/-0.36°F) across the 0-70°C range. Exceptions include the A/10K-E1 Series at +/-0.3°C (+/-0.54°F), and the A/1.8K Series which offers +/- 0.5°C @ 25°C (77°F) with a wider tolerance of (+/-1.0°C) (+/-1.8°F).
  • Response Time: The series exhibits a nominal response time of 20 seconds for a 63% step change.

The sensors utilize ACI's double encapsulation process with thermally conductive epoxy to eliminate moisture effects and improve thermal response. For optimal accuracy, the manufacturer recommends cleaning the pipe surface and applying silicone-free heat transfer paste between the sensor and pipe before fastening.

Configuration Options

The series offers a broad configuration envelope for specific installation needs, including various thermistor curves, lead lengths, wire types, and certification options. The standard probe features a 1.10" (27.9mm) long brass enclosure with a small curvature on the bottom to increase surface area.

Sensor Elements & Output Signals

Available thermistor nominal resistances at specified temperatures include:

  • A/1.8K: 1.8 KΩ (Red/Yellow)
  • A/2252: 2.252 KΩ (White/Red)
  • A/3K: 3 KΩ (White/Brown)
  • A/AN (Type III): 10 KΩ (White/White)
  • A/AN-BC: 5.238 KΩ (White/Yellow) with an internal shunt
  • A/CP (Type II): 10 KΩ (White/Green)
  • A/CSI: 10 KΩ (Green/Yellow)
  • A/10KS: 10 KΩ (White/Blue)
  • A/10K-E1: 10 KΩ (Gray/Orange or Orange/Gray depending on source context, listed as Gray/Orange in primary spec table)
  • A/20K: 20 KΩ (Brown/Blue)
  • A/50K: 50 KΩ (Brown/Yellow)
  • A/100KS: 100 KΩ (Black/Yellow)

Lead Wire & Cable Options

Sensors are supplied with two non-polarity sensitive leads. Standard configurations include:

  • Standard Lead Length: 24" (61 cm) of 22 AWG (0.65mm) Etched Teflon (PTFE) colored leads.
  • Extended Leads: Configurable lengths include 10' (3.05m), 20' (6.10m), and custom options like 6'. Note that the 20' length is RoHS Compliant but not CE Compliant.
  • Cable Types: Options include standard Etched Teflon, CL2P Plenum Rated Cable, or Z (2 Conductor White Zip Wire).

Approvals & Certifications

The series carries CE, RoHS2, and WEEE approvals. A NIST Certificate of Calibration (3 Points) is available as an option.

Key Product Differences

Variants within the Therm-Pipe-Mount series are distinguished by sensor curve type, lead length, wire insulation rating, and calibration certification. The model number structure follows the format: A/ - PM - - - . For example, a standard 24" thermistor is ordered as A/AN-PM, while a plenum-rated version with extended leads might be designated A/CP-PM-10'CL2P. The series also supports optional accessories such as thermal grease (silicone-free) and hardware for alternative mounting configurations.

en-GB
en_UK
Save Configuration