Skip to search Skip to main content Skip to navigation

United Kingdom 0800 488 488 | Intl +44 (0) 161 777 6611 | Welcome to our new website, found an issue or bug? Please report it here

We noticed you are in , please visit your local site by clicking the below link for regional offers and support.

USR03-Series

Short Range Ultrasonic Level/Distance Transmitter-Switch

  • Short 1.75 inch dead band
  • Unaffected by optical factors like color and transparency
  • PC or button “teachable” setup
  • Narrow beam with adjustments to optimize performance
USR03-Series
From £ 663.39
Short Range Ultrasonic Level/Distance Transmitter-Switch USR03-Series USR03-Series
loading all models
Product Overview
  • Accuracy ± 0.5 %
  • Cable Length 6.5 ft
  • Electrical Output 2 Outputs (0-20 mA,0-10 V)
  • Enclosure Ratings IP68, NEMA Type 4X
  • Loop Resistance 450 Ω max @ > 15 Vdc, 250 Ω max @ 10 Vdc
  • Measuring Range, Max 36 in, 3 ft
  • Measuring Range, Min 1.75 ft, 1.75 in
  • Media Compatibility Any, Clean dry air / inert gas, Clean process / cooling water, Corrosive chemicals / acids / bases, Fuel gases, HVAC / room air, Hydraulic fluids, Inert / non-reactive gases, Liquids, Oils / lubricants, Organic solvents, Steam, Nitrogen, Non-corrosive Dry Gasses, Oil, Oxygen, Solvents, Water, Water-based fluids
  • Memory Non - Volatile
  • Operating Humidity 0 to 100% RH
  • Operating Pressure, Max 50 psi
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -40 °C
  • Output Signal Current, Voltage
  • Resolution 0.0034 in
  • Series ID USR03-Series
  • Transducer frequency 240 kHz
  • Ultrasonic Beam Width 12 ° at -3db
  • Weight 0.29 kg

Supported Applications

The Omega U-Series ultrasonic distance sensors (models USR03, UMR14, ULR30, UXLR50) perform non-contact target distance measurement designed for tough industrial environments. Documented applications include roll diameter monitoring, loop control, web break detection, dimensioning, proximity sensing, sort/select operations, and level measurement.

Operating Conditions & Performance

The series operates in ambient temperatures from -40 to +158 F (-40 to +70 C) with internal or external reference target temperature compensation. Sensors are rated for 0-100% humidity (avoiding heavy condensation) and feature IP-68, NEMA-4X ingress protection. Measurement accuracy is better than 0.5% of the target distance in a stable, homogeneous air environment; performance may be affected by temperature gradients, target echo strength, or speed of sound variations.

Performance specifications vary by model range:

  • USR03: Maximum range 3 ft (91cm); deadband minimum 1.75 in (4.4 cm). Repeatability is the greater of +/-0.03 in. (0.76 mm) or 0.25% of target distance.
  • UMR14: Maximum range 14 ft. (4.3 m); deadband 4 in. (10.2 cm). Repeatability matches USR03 specifications.
  • ULR30: Maximum range 30 ft. (9.1m); dead band 10 in. (25.4cm). Repeatability is 0.2% of target distance.
  • UXLR50: Maximum range 50 Ft. (15.2m); dead band 12 in. (30.5cm). Repeatability matches ULR30 specifications.

Default measurement rates are 50 msec (20 Hz) for USR03/UMR14, 100 msec (10 Hz) for ULR30, and 200 msec (5 Hz) for UXLR50. Rates are adjustable from 5 msec to 2.8 hours; faster rates limit maximum target distance.

Configuration Options

The series supports multiple output configurations selectable via OmegaVIEW software or rear pushbutton TEACH adjustment (except on serial-only and UXLR50 models). Full-featured USR03/UMR14 sensors provide two outputs, while ULR30 and UXLR50 offer five simultaneous outputs. Available signal types include:

  • Voltage: 0-10 VDC (or custom via OmegaVIEW; 10 mA max).
  • Current Loop: 4-20 mA sourcing or sinking, configurable to 0-20 mA.
  • Switches: PNP or NPN solid-state switches rated at 150 mA (external 40 VDC max.), configured for setpoint or window mode with reversible polarity (NO/NC).
  • Serial Data: RS-232 or RS-485 interfaces supporting Modbus slave, ASCII streaming, or SYNCH protocols. RS-485 models support 2-wire multi-drop addressing (addresses 1-247) with baud rates from 9600 to 115200.

Power requirements are 10-30 VDC @ 55 mA max for USR03/UMR14 and 10-30 VDC @ 70 mA max for ULR30/UXLR50. Sensors feature embedded shielded PUR cables with tinned wire ends (6-wire or 9-wire depending on series) or optional M12 connectorized cables.

Key Product Differences

The USR03-Series encompasses four primary sensor families distinguished by range, housing material, and mounting options:

  • USR03: 3 ft (91cm) maximum range; housed in 316 stainless steel with M30x1.5 mm or 1-in NPT thread.
  • UMR14: 14 ft. (4.3 m) maximum range; housed in 316 stainless steel with M30x1.5 mm or 1-in NPT thread.
  • ULR30: 30 ft. (9.1m) maximum range; housed in 316 stainless steel with dual 1.5-in NPT threads.
  • UXLR50: 50 Ft. (15.2m) maximum range; available in 316 stainless steel or PVC housing. Mounting options include clamp mount, rear-mounted 1.5-in NPT, or dual 2.5-in NPT threads.

Model numbers follow the structure [PRODUCT]-[MOUNT]-[SERIAL INTERFACE], where serial interface codes denote RS-232 (PC COM port) or RS-485 (addressable multi-drop). Accessories include OmegaVIEW software, USB interface kits, mounting brackets (MB30-SS90), and stainless steel nuts.

Accessories

accessories

USB SET-UP KIT (For RS-232 SENSORS)
£120.59 / each
0 In Stock
USB SET-UP KIT (For RS-485 SENSORS)
£123.24 / each
0 In Stock

installation hardware

SS,90 DEGREE MOUNTING BRACKET, M30 ONLY
£40.20 / each
0 In Stock
MOUNTING NUTS, QTY 2, M30 ONLY
£13.42 / each
0 In Stock
en-GB
en_UK
Save Configuration