United Kingdom 0800 488 488 | Intl +44 (0) 161 777 6611 | Welcome to our new website, found an issue or bug? Please report it here
I-7513-Series
DIN-Rail Mountable RS-485 3 Way Converter Hub
- RS-485 Active Star Wiring Applications
- Hub & Repeater Functions, 1 RS-485 to 3RS-485
- Auto Switching Baud Rate, 300 to 115,200 bps
- ESD Protection for the RS-485 Data Line
I-7513-Series
From
£
251.68
Product Overview
- Baud Rate 300 to 115200
- Baud Rate Note Max. 1,200 m for at speed 9.6 kbps; Max. 400 m at 115.2 kbps
- Cable Length 4000 ft
- Cable Note Belden 8941 (2P twisted-pair cable), if different cables are used, the transmission distance may change
- Cable Type 2P Twisted-Pair Cable, 4P Twisted-Pair Cable
- Data Interface Note 3, RS485 Channels: Data+, Data-
- Height 4.8 in
- Input Cable Connector Type RS485: 10 - Pins Terminal Block, Removable
- Input Type 1, RS485 Channel: Data+, Data-
- Isolation Three Way Protection: 3000 Vdc
- LED Indicators Power/Communication LED
- Length 1.5 in
- Materials ABS
- Mounting DIN-Rail Mounting
- Number of Channels 1
- Number of Wires 2
- Operating Temperature, Max 75 °C
- Operating Temperature, Min -25 °C
- Output Cable Connector Type RS485
- Power Consumption 2.16 W
- Relative Humidity 10 to 90% RH, Non-Condensing
- Self Tuner Yes, Asic Inside
- Series ID I-7513-Series
- Storage Temperature, Max 75 °C
- Storage Temperature, Min -30 °C
- Supply Power Type DC
- Supply Voltage 10 to 30 Vdc
- Supported Devices 256 (each channel)
- Transmission Distance 4000 ft
- Width 2.83 in
Supported Applications
The Omega I-7513 Series is a 3-channel RS-485 Active Star Wiring Hub designed for industrial communication networks. It functions as both a hub and repeater, enabling the connection of multiple devices to an RS-485 network while maintaining signal integrity over extended distances.
Key application capabilities include:
- Extending RS-485 transmission signals up to 1,200 m (at 9.6 kbps) or 400 m (at 115.2 kbps).
- Supporting star-wiring topologies with three independent output channels.
- Cascading configurations where each output channel can connect to another hub via its repeater function.
Operating Conditions & Performance
The I-7513 Series operates within an ambient temperature range of -25 °C ~ +75 °C and a storage temperature range of -30 °C ~ +75 °C. It is rated for humidity levels between 10 ~ 90% RH, non-condensing.
Performance specifications include:
- Baud Rate Support: Auto-switching from 300 to 115200 bps via an internal Self-Tuner ASIC.
- Isolation: Three-way isolation rated at 3000 VDC between input and output interfaces.
- Device Capacity: Supports up to 256 devices per channel (total of three channels).
- Cabling Recommendation: Belden 8941 (2P twisted-pair cable) for optimal transmission distance; distances may vary with different cables.
Power and Environmental Ratings
- Input Voltage Range: +10 VDC ~ +30 VDC (Non-isolated).
- Power Consumption: 2.16 W.
- Enclosure Rating: IP-411.
- Housing Material: Plastic with Fire Retardant Materials (UL94-V0 Level).
Certifications
The series carries CE, FC, and RoHS approvals.
Configuration Options
The I-7513 Series is configured for DIN-Rail mounting with a compact footprint of 72 mm x 122 mm x 35 mm. It features removable terminal blocks for electrical connections and includes LED indicators for Power (Red) and Data Transmission (Green).
Electrical Connections
The device utilizes two removable 10-Pin Terminal Blocks, providing a total of 20 terminals with the following pin assignments:
- Input Channel: Terminals 01 (DATA+), 02 (DATA-).
- Power Input: Terminal 09 ((R)+Vs) and Terminal 10 ((B)GND).
- Output Channels:
- Data Channel 3: Terminals 11 (DATA3-) and 12 (DATA3+).
- Data Channel 2: Terminals 14 (DATA2-) and 15 (DATA2+).
- Data Channel 1: Terminals 19 (DATA1-) and 20 (DATA1+).
Available Options & Accessories
The series supports the following power supply options:
- GPSU06U-6: 24 VDC/0.25 A, 6 W Power Supply.
- DIN-KA52F: 24 VDC/1.04 A, 25 W Power Supply with Din-Rail Mounting.
Housing Variants
The series is offered in two model configurations based on enclosure color:- I-7513 CR: Three Way Isolated RS-485 Active Star Wiring Hub (RoHS).
- I-7513-G CR: Three Way Isolated RS-485 Active Star Wiring Hub with Gray Cover (RoHS).
Key Product Differences
The primary distinction between the I-7513 Series models is the enclosure color. The standard model, I-7513 CR, features a default housing finish, while the I-7513-G CR variant includes a gray cover. Both variants share identical electrical specifications, isolation ratings (3000 VDC), and communication capabilities.The series is designed specifically as an RS-485 Star Wiring Hub; it does not function as a sensor or measurement device for physical quantities such as temperature, pressure, or flow.