Asense-Room

Carbon Dioxide Sensor, Wall Mount, 0-2000 ppm, Temperature

  • Commercial Office Buildings
  • Gymnasiums
  • Shopping Malls
  • Auditoriums
  • Theaters
  • Hospitals & Schools
  • Demand Control Ventilation & Economizers
Asense-Room
From
Carbon Dioxide Sensor, Wall Mount, 0-2000 ppm, Temperature Asense-Room Asense-Room
loading all models
Product Overview
  • Accuracy ± 30 ppm, ±3 %
  • Accuracy Detail Extended Range Accuracy > 2,000 PPM: +/- 30 ppm and +/- 5% of reading; Accuracy is defined after minimum three (3) ABC periods (1 period = 8 days) of continuous operations
  • Applications Air and HVAC, Building and Maintenance
  • Approvals EMC Directive 2014/30/EC, RoHS Directive 2011/65/EU & RoHS 3 Directive 2015/863/EU
  • Calibration Senseair ABC algorithm (Automatic Baseline Correction)
  • Calibration Note Calibration 3: Senseair ABC algorithm (Automatic Baseline Correction)
  • CO2 Measurement Range 0 to 2000 PPM
  • Deadband 100 ppm
  • Diagnostics Complete function check, yellow LED; LCD error indication (display model only)
  • Electrical Connection Screw Terminal
  • Electrical Output 0 to 20 mA, 4 to 20 mA, 0 to 10 Vdc, 2 to 10 Vdc
  • Enclosure Material Polycarbonate/ABS Blend, UL94V-1
  • Enclosure Material Note ABS, Flammability Rating UL94-HB
  • Installation 4-6’ o the floor
  • Material Construction Option none
  • Measuring Range 7500 sq. ft. maximum
  • Operating Humidity 0 to 85% RH, non-condensing
  • Operating Temperature, Max 122 °F
  • Operating Temperature, Min 32 °F
  • Output Detail Output 1 (CO2): 0/2 to 10V, 0/4 to 20 mA, 0 to 2000 ppm Output 2 (Temperature): 0/2 to 10V, 0/4 to 20 mA, 32 to 122ºF (0 to 50ºC)
  • Power Consumption 1 W
  • Relay Output 0.5 A @ 125 Vac; 1 A @ 24 Vdc
  • Repeatability ±20 ppm ±1% of measured value
  • Response Time <10 seconds @ 30 cc / minimum flow rate, <3 minutes diffusion time
  • Sensor Life >15 years
  • Sensor Type Single beam infrared sensing technology (NDIR)
  • Series ID Asense-Room
  • Storage Temperature, Max 158 °F
  • Storage Temperature, Min -40 °F
  • Supply Voltage 19 to 29 Vac/Vdc
  • Temperature Measurement Range -4 to 140ºF
  • Trip Point Note 1000 ppm (factory set)
  • Zero Drift ± 0.3 %

Supported Applications

The ACI ASENSE Room series monitors carbon dioxide (CO2) levels in commercial, school, and office environments. Based on single beam non-dispersive infrared technology, the sensor measures CO2 concentration up to 2,000 ppm and provides an analog temperature output. Documented applications include commercial office buildings, gyms, shopping malls, auditoriums, theaters, hospitals, and schools.

Operating Conditions & Performance

The series operates in residential, commercial, and industrial spaces with a specified operating environment of 32°F to 122°F (0°C to 50°C) and relative humidity from 0 to 85% RH Non-condensing. The sensing range covers CO2: 0 to 2000 ppm and Temperature: -4 to 140°F (-20 to 60°C). Accuracy is defined as ±30 ppm and ±3% of reading for CO2, and ±1.8°F (1°C) for temperature; this accuracy applies after a minimum three ABC periods where one period equals 8 days.

Performance characteristics include repeatability of ±20 ppm ±1% of measured value and an annual zero drift of <± 0.3% of measurement range. The response time is listed as <10 seconds @ 30 cc/minutes flow rate, with a diffusion time of <3 minutes. Warm-up time requires less than 5 minutes to reach full specifications (or 15 minutes). Operating pressure compensation is +1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmosphere = 14.7 psi (1.013 KPa)). The sensor life exceeds 15 years.

Configuration Options

The ASENSE Room series supports configurable output signals and optional relay functionality via hardware jumpers or programming cable configuration. Power supply requirements are 24 VAC/VDC ±20%; 50/60 Hz, with a maximum of 10.5 to 40 VDC (Half-wave rectified). The enclosure is constructed from ABS material with a Flammability Rating UL94-HB.

Available output configurations include:

  • Output 1 (CO2): 0/2 to 10V, 0/4 to 20 mA, or 0 to 2000 ppm.
  • Output 2 (Temperature): 0/2 to 10V, 0/4 to 20 mA, covering 32 to 122°F (0 to 50°C).
  • Output 3: N.O. or N.C. relay rated at 0.5A @ 125 VAC; 1A @ 24 VDC.

The series supports extended CO2 ranges up to 10,000 ppm when factory set or configured via programming cable. Extended range accuracy for readings > 2,000 PPM is ±30 ppm and +/5% of reading. Configuration options include the Sensear ABC algorithm (Automatic Baseline Correction), which requires building CO2 levels to drop to 400 ppm some time during the week; if occupied 24 hrs/day, ABC must be turned off.

Accessories for configuration and calibration include:

  • TTL-232R-3V3 Programming Cable
  • UIP5 Free Software Download (Contact ACI)
  • A/CUSTOM CAL GAS* Custom Calibration

Key Product Differences

The series is offered in standard and display-equipped models, with or without relay output. The ASENSE-R-LCD variant includes a 4 digits, 7 segments LCD with ppm indicator for self-diagnostics via yellow LED and error indication.

  • ASENSE-R: CO2 Room sensor with analog outputs (0-10 VDC or 0-20 mA), field selectable to 4-20mA or 2-10 VDC. Weight: 0.300 lbs (0.136 kg).
  • ASENSE-R-LCD: Includes display with analog outputs and weight of 0.314 lbs (0.142 kg). Storage temperature for LCD versions is -4 to 122°F (-20 to 50°C), whereas standard versions store from -40 to 158°F (-40 to 70°C).
  • ASENSE-R-REL: Includes relay output (N.O. or N.C.) with factory set trip point at 1000 ppm and deadband/hysteresis of 100 ppm.
  • ASENSE-R-LCD-REL: Combines display functionality with the optional relay configuration.