United Kingdom 0800 488 488 | Intl +44 (0) 161 777 6611 | Welcome to our new website, found an issue or bug? Please report it here
TSENSE-Series
Carbon Dioxide Sensor, Analog, Modbus, or BACnet, RH/TEMP, RELAY
- Commercial Office Buildings
- Gymnasiums
- Shopping Malls
- Auditoriums
- Theaters
- Hospitals & Schools
- Demand Control Ventilation & Economizers
Product Overview
- Additional Features 1 Maintenance free
- Calibration Note CO2 Calibration 3: Senseair ABC algorithm (Automatic Baseline Correction)
- CO2 Measurement Range 0 to 2000 PPM
- Data Interface BACnet MS/TP, Modbus RTU
- Deadband 100 ppm
- Diagnostics Complete function check
- Enclosure Material ABS, Polycarbonate
- Enclosure Material Note Bayblend FR3000 (PC & ABS blend), Flammability rating UL 94V-0
- Enclosure Ratings UL94 V-0
- Humidity Measurement Range 0 to 100 %
- Hysteresis ±1% @ 20 to 80% RH
- Installation 4-6’ off the floor
- Length 0.87 in
- Material Construction Option none
- Network and Communications 0 to 127 (Default 104)
- Operating Environment Residential and Commercial spaces
- Operating Humidity 0 to 95% RH, non-condensing
- Operating Temperature, Max 122 °F
- Operating Temperature, Min 32 °F
- Output Detail Out 1 (CO2): 0 to 10V, 0 to 2000 ppm Out 2 (Temperature): 0-10V, 32°F to 122°F (0°C to 50°C) Out 3 (RH): 0 to 10V, 0 to 100% RH
- Power Consumption 2 W
- Pressure Dependence ±1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmospher = 14.7 psi (1.013 KPa))
- Repeatability ±00.45°F @ 63 to 82°F (±0.25°C @ 17 to 28°C); ±0.25% RH @ 63 to 82°F (±0.25% RH @ 17 to 28°C)
- Resolution 10-bits, 10mV/steps, , 0.1% steps of full ppm/°C/%RH range
- Response Time <3 minute diffusion time
- Sensing Method Single bean non-dispersive Infrared (NDIR)
- Sensor Life > 15 years (typical)
- Series ID TSENSE-Series
- Software CO2 (Default) / Temp/RH Configurable via Touchscreen or UIP5 Software
- Storage Temperature, Max 158 °F
- Storage Temperature, Min -22 °F
- Supply Voltage 12 Vdc, 24 Vac/Vdc
- Trip Point Note Relay Trip Point (CO2): 1000 ppm (factory set)
- Zero Drift ± 0.3 %
Supported Applications
The ACI TSENSE series is a wall-mountable transmitter designed for measuring indoor air carbon dioxide (CO2) concentration, temperature, and relative humidity in residential and commercial spaces. The unit connects to Direct Digital Control (DDC) systems via analog outputs or communication protocols. Documented applications include energy efficiency strategies in commercial office buildings, hospitals, hotels, schools, and other facilities requiring indoor air quality monitoring.
The series incorporates non-dispersive infrared (NDIR) technology for CO2 sensing and complies with ASHRAE 189.1 standards as well as CA Bill 841 requirements to support healthy occupant environments.
Operating Conditions & Performance
The TSENSE series operates within an ambient temperature range of 32°F to 122°F (0°C to 50°C) and a relative humidity environment of 0-95% RH non-condensing. Storage temperatures are rated from -22°F to 158°F (-30°F to 70°F). The device requires a supply voltage of 12 VDC or 24 VAC/VDC (±20%, half-wave rectified, 50-60 Hz), with power consumption under 0.35W average for the non-display version and less than 0.6W for the display version.
Performance specifications include:
- CO2 Measurement Range: 0 to 2000 ppm (standard) or optional 0 to 3000 ppm.
- Temperature Range: 32°F to 122°F (0°C to 50°C).
- RH Measurement Range: 0-100% RH.
- CO2 Accuracy: ±50 ppm @ 1000 ppm, 63°F to 82°F (17°C to 28°C); typical full range accuracy is ±30 ppm ±3% of reading.
- Temperature Accuracy: ±0.9°F (@ 63 to 82°F / ±0.5°C @ 17 to 28°C) and ±1.8°F (@ 32 to 122°F / ±1.0°C @ 0 to 50°C).
- RH Accuracy: ±5% @ 20 to 80% RH.
- Response Time (T1/e): <3 minutes for CO2; <6 minutes for temperature and RH at an air velocity of 0.15m/s.
- Pressure Dependence: ±1.6% per 0.145 psi (1 kPa) deviation from normal pressure (1 Atmosphere = 14.7 psi / 1.013 KPa).
The CO2 sensor utilizes the Senseair ABC algorithm for Automatic Baseline Correction, with a typical sensor life exceeding 15 years.
Configuration Options
The series offers configurable output signals and communication protocols to suit various control system requirements. Standard analog outputs are pre-programmed as linear 0-10 VDC signals for CO2, temperature, and relative humidity on terminals OUT(1), OUT(2), and OUT(3). Alternative output ranges can be configured using PC software (UIP version 5 or higher) via a USB communication cable.
Output & Communication Options:
- Analog Voltage Output: 0 to 10V, R out <100Ω, Load >5KΩ with 10-bit resolution (10mV/steps).
- Digital Protocols: Modbus RTU or BACnet MS/TP.
- Relay Output: Form C, SPDT rated at 1A @ 50 VAC / 24 VDC. The relay trip point is factory set to 1000 ppm CO2 with a deadband/hysteresis of 100 ppm; the input source can be configured via touchscreen or software.
- Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200 for communication protocols.
Housing & Physical Configuration:
- Enclosure Material: Bayblend FR3000 (PC & ABS blend) with a flammability rating of UL 94V-0.
- Dimensions: 4.92" (125 mm) H x 3.35" (85 mm) W x 0.87" (22 mm) D.
- Electrical Connections: Screw terminals compatible with 0.00232 in² (1.5 mm²) wire.
Display & Configuration:
- TSENSE-LCD models feature a configurable color touch display showing CO2 (PPM), Temperature, and Humidity (%RH). Settings can be adjusted via the touchscreen or using the TTL-232R-3V3-AJ programming cable.
- Standard TSENSE models without an LCD require the TTL-232R-3V3-AJ programming cable and UIP5 software for configuration, BACnet/Modbus setup, or setting changes.
Key Product Differences
The series is available in two primary configurations distinguished by display capability:
- TSENSE-LCD (Item #135458): Includes a touch screen menu for local configuration and monitoring. Weight: 0.414 lbs (0.188kg).
- TSENSE Standard (Item #135459): No display; requires external programming cable for all settings adjustments. Weight: 0.361 lbs (0.166kg).
Additional options include Custom Calibration (Item #140970) and the USB to Serial Programming Cable, TTL-232R-3V3-AJ (Item #137011). The series supports a maximum coverage area of 7500 sq. ft., with recommended mounting heights between 4-6' off the floor.