CN72000-Series
1/4 DIN Temperature/Process Ramp/Soak Controller with Fuzzy Logic
- Dual-Display NEMA 4X (IP65) Front Panel Resists Dust and Moisture
- Front Panel Programmability
- 16 Ramp/Soak Segments with Program End Control
- Fuzzy Logic
CN72000-Series
From
£
939.66
Product Overview
- Accuracy ± 0.25 %
- Accuracy Detail ± 0.25% of span, ± 1 least significant digit
- Display Size 6.35 mm (.25 in)
- Display Type 4 Digit LED
- Display Type Note Two 4-digit, 7-segment, 6.35 mm H (0.25") LEDs
- Enclosure Ratings IP65, NEMA Type 4X
- Form factor 1/4 DIN
- Impedance Input Thermocouple: 3 MΩ minimum; Voltage: 5000; Current: 10; RTD Current: 200 μA maximum
- Input Type Thermocouple, RTD, mA, mV, Voltage
- Measurement Type Current, Temperature, Voltage
- Measuring Range Type K: -129 to 1371°C Type J: -73 to 871°C Type T: -212 to 398°C Type E: -73 to 982°C Type N: -73 to 1300°C Type R: -17 to 1760°C Type S: -17 to 1760°C Type B: 24 to 1820°C Type L (J DIN): -73 to 871°C Type C: -17 to 2320°C Pt100 RTD (0.00385 and 0.00392): -200 to 875°C RTD, 120 Ω nickel (0.00628): -80 to 320°C 0 to 20 mA, 4 to 20 mA: -1999 to 9999 0 to 10 Vdc,-10 to 10 Vdc, -10 to 10 mVdc: -1999 to 9999
- Number of Inputs 1
- Operating Temperature, Max 55 °C
- Operating Temperature, Min -10 °C
- Ramp and Soak 16 ramp/soak Programs
- Sampling Rate 1 Hz (1 update/second)
- Series ID CN72000-Series
- Supply Power Note 100 to 240 Vac, nominal, 10 to 15%, 50 to 400 Hz Single Phase: 132 to 240 Vdc, nominal, 10 to 20%
- Supply Power Type AC
- Supply Voltage 100 to 240 Vac
- Weight 369 g
Supported Applications
The Omega CN72000-Series is a 1/4 DIN temperature and process ramp/soak controller featuring fuzzy logic control. Designed for panel mounting, the series supports applications requiring precise thermal cycling profiles via its Four Stage Set Point option.
Operating Conditions & Performance
The CN72000-Series operates on a line input of 85 to 240 VAC at 50/60 Hz. The unit includes an isolated excitation voltage supply rated at 24 VDC @ 50 mA for external devices.
Installation Dimensions
- Panel Cutout: 92.0MM (3.620 IN) ±0.8 / -0.0 (±0.032 / -0.000)
Safety and Wiring Notes
- Input/Output Ratings: Input wiring for thermocouple, current, and RTD; and output wiring for 15 VDC are rated CLASS 2.
- Power Lead Separation: Do not run thermocouple or other class 2 wiring in the same conduit as power leads.
- Supply Connections: Must be made in accordance with the National Electrical Code per Article 300 and local regulations.
- Disconnect Requirements: All line voltage output circuits must have a common disconnect and be connected to the same pole of the disconnect.
Configuration Options
The CN72000-Series is configured via a model number guide following the format: CN72 - <Alarm> - <Output 1*> - <Output 2*> - <Options>. The series supports various combinations of alarms, outputs, and functional options.
Alarms
- Code 0: No Alarm
- Code 1: Yes (Alarm Enabled)
Output Configurations
The series offers selectable output types for Output 1 and Output 2, including:- SSR: Solid State Relay (Code 1)
- Relay: Electromechanical Relay (Code 3)
- Current: Current Loop Output (Code 5)
Functional Options
The controller supports the following optional features:- RSP1: Remote Set Point 0 to 20 mA
- RSP2: Remote Set Point 0 to 10 VDC
- PV1: Recorder Output 0 to 20 mA
- PV2: Recorder Output 0 to 10 VDC
- 4SP: Four Stage Set Point (Ramp/Soak)
Electrical Connections
The unit utilizes a terminal block with 32 terminals for connections.
Key Product Differences
Variants within the CN72000-Series differ by their specific alarm configuration, output type selection (SSR, Relay, or Current), and enabled options such as Remote Set Point inputs or Recorder Outputs. For example, model CN72011-1-1-RSP1 indicates a unit with an Alarm, SSR Output 1, SSR Output 2, and the RSP1 option.
Note: Use only the type of thermocouple or RTD probe for which the control has been programmed. Do not wire the 24 VOLT power supply across the input of the control; damage to the control input circuitry will result.