Models In Stock
  • 5-digit OLED display
  • 2 alarm outputs
  • 350° rotating display
  • Durable housing rated IP67
PSW2100
From C$ 864.74
Models In Stock
Electronic Pressure Switch with OLED Display and Alarm Outputs PSW2100 PSW2100
loading all models
Product Overview
  • Accuracy ± 0.2 %
  • Deadband Type Adjustable
  • Display OLED Display
  • Electrical Connection M12 4 pin Male
  • Enclosure Ratings IP67, NEMA Type 6
  • Materials 316L Stainless Steel, Stainless Steel
  • Output Value 4 to 20 mA
  • Measurement Pressure Type Gauge
  • Process Connection Type NPT Male
  • Process Temperature, Max 120 °C
  • Process Temperature, Min -40 °C
  • Series ID PSW2100
  • Stability ± 0.2% URL / 5 years
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Power Note ≤1.44W(4-20mA+ transistor + OLED display @24Vdc)
  • Supply Voltage 12 to 30 Vdc
  • Transmission Distance up to 1000 meters
  • Vibration GB/T 1827.3/IEC61298-3 tests, <0.1% URL
  • Weight 0.4 kg

Supported Applications

The Omega PSW2100 is an electronic pressure switch featuring a display module for field adjustment and configuration. The series supports pipe, container, and differential pressure measurement applications, as well as container level measurement.

Operating Conditions & Performance

The device operates on a 12-30VDC power supply with an aviation plug (M12*1, 5 pins) electrical connection. The maximum process pressure rating is P-MAX: 4 MPa. Storage conditions require temperatures between -40-185°F (-40-85°C) and a maximum relative humidity of 95%. The measurement range setting spans from -99999 to 99999, with configurable display units including kPa, MPa, Pa, bar, mBar, Psi, mmH2O, mmHg, Torr, and Atm.

Alarm Settings Function

The alarm settings function table defines the following configuration parameters:

  • SPx (OUT upper limit): Setting range -99999~99999; Upper limit value of transistor output.
  • RPx (OUT lower limit): Setting range -99999~99999; Lower limit value of transistor output.
  • SPDTx (OUT output delay): 0.0~60.0(S); Delay time before transistor output active.
  • RPDTx (OUT reset delay): 0.0~60.0(S); Delay time before transistor output reset.
  • Modex (OUT working mode): Configurable modes include no output, measured value > SPx with delay activation, and measured value < RPx with delay reset.

Configuration Options

The PSW2100 series offers multiple output signal configurations including 4-20mA, 1-5VDC, and two-way transistor outputs. The product overview specifies a two-way transistor output (PNP). Available variants include model codes such as PSW2100-005C, PSW2100-035E, PSW2100-1.5KC, PSW2100-400E, and others.

Signal Connection

The aviation plug (M12*1, 5 pins) pinout is defined as follows:

  • Pin 1: Power+
  • Pin 2: Transistor output 2
  • Pin 3: Power-
  • Pin 4: Transistor output 1
  • Pin 5: *Signal+

The signal connection table details wire colors and connections: brown (terminal 1) for positive power supply, white/blue/black/gray wires connecting to negative signal module or transistor outputs. For a 4-20mA + two-way NPN output configuration, the common port in specific steps is noted as the positive power supply.

Display Configuration

The display mode allows selection of auto optimal display or integer/decimal precision from one to four decimal places. The process unit can be set via codes 0 through 11 corresponding to various pressure units listed above.

Key Product Differences

Variants in the series are distinguished by their specific model suffixes (e.g., -C, -E) and numerical prefixes indicating different configurations or ranges. The active electrical level for transistor outputs is 2V lower than the power supply level; for example, a 24V power supply results in an active electrical level of 22V.

Installation notes indicate that zero point adjustment should be performed after installation to counter mounting position effects and reset annually. The device carries CE certification indicating alignment with EU standards (EMC equipment instructions 2014/30/EU).

Accessories

Pressure Snubbers to Protect Against Pressure Surges
From C$27.12
0 In Stock
A-170 316 SS Siphons for High Temp – Prevents Steam Contact – NPT Connection
From C$60.59
0 In Stock
Gage Guard for Pressure/Vacuum, Polypropylene, Inorganic Compatibility
From C$154.37
0 In Stock

cables

5-PIN, 2M (6.6 FT) M12 CABLE ASSEMBLY
C$34.61 / each
4 In Stock
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 2ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;

Do these switches have CRN's?

Asked by: Ovidiu
Thank you for your inquiry, the PSW2100-005C doesn&rsquo;t have CRN&rsquo;S .
Answered by: rkent
Date published: 2022-09-19

can it used on a helium supply system.

Asked by: Sparkie1
The wetted parts of this pressure transducer are all 316 Stainless Steel. It would be ok to use with Helium
Answered by: Applicatrions Engineer JK
Date published: 2021-11-10

What is the Emission and immunity to interference standard that applies to PSW2100 switch? For example, EN 61326 or NAMUR NE 21

Asked by: jfvanegasv
Thank you for your inquiry. Contacting manufacturing for information on which standard it conforms to. Will forward the information via email to you directly via email
Answered by: JK Applications Eng
Date published: 2025-01-06

Will this switch work with a 4 pin M-12 connector?

Asked by: CSGPP
This pressure switch requires a 5-pin M12 female connector. It will not interface with a 4-pin M12.
Answered by: JK Applications Engineer
Date published: 2024-03-22

Just purchased a PSW2100-150C, I'm not getting a 4-20mA output, reads 21.1V open circuit and plugged into an measurement unit. Do I need to enable the output? Signal connection diagram is incorrect, Pin 3 RET pin 5 SIG 2 SW2 4 SW1

Asked by: Mark123456
You should not have to enable the 4 to 20mA output. A wiring issue may be causing the problem. Reviewing the manual and will make corrections. Advise you contact us at pressure@omega.com with your contact information so we can respond directly with the resolution of this issue
Answered by: Applicatrions Engineer JK
Date published: 2022-11-30

Is this suitable for liquid measurement? The water we are measuring is contaminated with mercury.

Asked by: rebeler1
The Process Connection Material for the PSW2100-400C is 316L SS, this material is suitable for liquids
Answered by: rkent
Date published: 2021-05-19

Is this product capable of external visual warning/monitoring? As in output wired to 2-3 LEDs a couple feet away that read under pressure, good pressure, and/or overpressure? If not, could you point me in the direction of a product that does. Thank you.

Asked by: Greg14
The two on board transistor output can be wired to switch the power being used to drive the unit to also drive external alarm devices.
Answered by: Applicatrions Engineer JK
Date published: 2022-11-21
  • y_2026, m_8, d_27, h_9CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_7
  • loc_en_CA, sid_PSW2100-005C, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 28ms
  • QUESTIONS, PRODUCT
en-CA
en_CA
Save Configuration