Skip to search Skip to main content Skip to navigation

Netherlands 07077 03815 | Intl +31 (0) 7077 03815 | Welcome to our new website, found an issue or bug? Please report it here

We noticed you are in , please visit your local site by clicking the below link for regional offers and support.

DRSL-RTD-ISO

RTD Input DIN Rail Signal Conditioners

€ 211,00 / each

Item# DRSL-RTD-ISO

In Stock

Lead Time (If not in stock): 7 Days

Product Specs

<< See all Product Models
Brand
Accuracy ± 0.05 %
Accuracy Detail Better than 0.2°C or ±0.1% of selected range
Approvals CE, UL, RoHS
Calibration Temperature, Max 28 °C
Calibration Temperature, Min 20 °C
EMC Immunity Note NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
EMC Standard NAMUR NE 21
Electrical Output 4 to 20 mA
Enclosure Ratings IP20
GrossWeightValue 0.25
Height 113 mm
Input Range Note Sensor Current, RTD: <150 µA;Sensor Cable Specifications: 50 Ωper wire or 50 nF;Effect of Sensor Cable Resistance (3 or 4-wire RTD): <0.002 Ω/Ω;Broken Sensor Detection: >800 Ω;Shorted Sensor Detection: <18 Ω
Input Type RTD
Installation Pollution degree 2 and measurement/overvoltage category II
LED Indicators Green LED indicates operational status of the unit and input sensor
Length 115 mm
Load Resistance Current: 21 mA/600Ω /12.6V max;Voltage:>10 kΩ min
Mounting DIN Rail 35 mm Standard, EN 60715
Noise Calibration >60 dB
Number of Inputs 1
Operating Temperature, Max 70 °C
Operating Temperature, Min -25 °C
Output Detail Current: Range Limits(NAMUR NE43 Out of Range):Below 3.8 mA or above 20.5 mA for 4 to 20 mA output; 0 mA or above 20.5 mA for 0 to 20 mA output Sensor Error Detection(Dip Switch Selectable for Enable or None): Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Incorrect DIP-Switch Setting Identification: Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Output Error Level: DIP switch selectable for upscale or downscale. Voltage: Range Limits (Out of Range):Range ±2.5% Sensor Error Detection (Dip Switch Selectable for Enableor None): 0V or selected range + 10% Incorrect DIP-Switch Setting Identification: 0V Output Error Level: DIP switch selectable for upscale or downscale
Output Signal Current, Voltage
Output Value Process
Power Consumption 0.7 W, Internal - 0.65 W
Relative Humidity 0 to 95% RH (non-condensing)
Response Time < 30 ms
Response Time Note Response Time (0 to 90%, 100 to 10%): <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed)
Screw Terminal Torque 0.5 Nm
Series ID DRSL-RTD-Srs-Sig-Cond
Stability Load Stability: ≤0.01% of span/100 Ω
Storage Temperature, Max 85 °C
Storage Temperature, Min -40 °C
Supply Power Note 16.8 to 31.2 Vdc via power rail or connectors
Supply Power Type DC
Supply Voltage 16.8 to 31.2 Vdc
Temperature Coefficient ≤±0.02°C/°C
Voltage Output Range 0 to 10 Vdc
Weight 70 g
Width 6.1 mm
Wire Gauge 26 to 13 AWG
Country of Origin Denmark
See All Specs Show Less
RTD Input DIN Rail Signal Conditioners DRSL-RTD-ISO DRSL-RTD-ISO

Accessories

installation hardware

MODULE STOP FOR DRSL SERIES
C$15.11 / each
5 In Stock
POWER RAIL FOR DRSL SERIES
C$308.14 / each
0 In Stock

meters/controllers

PWR CONN FOR DRSL SERIES CE
C$197.90 / each
9 In Stock
en-NL
en_NL
Save Configuration