Netherlands 07077 03815 | Intl +31 (0) 7077 03815 | Welcome to our new website, found an issue or bug? Please report it here
DRSL-SP1-Rptr-Spltr
DIN Rail Isolated Repeater/Splitter for Current Signals
- Isolation and Conversion of Current Signals
- Splitter Function: 1 Current Input—2 Current Outputs
- Slimline Housing—Only 6 mm (0.24') Wide
- Fast Response Time <7 ms
DRSL-SP1-Rptr-Spltr
From
€
286,42
Product Overview
- Approvals CE, UL, RoHS
- Calibration Temperature, Max 28 °C
- Calibration Temperature, Min 20 °C
- Electrical Output 0 to 20.5 mA
- EMC Immunity Note Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
- EMC Standard NAMUR NE 21
- Enclosure Ratings IP20
- Height 113 mm
- Installation Pollution degree 2 and measurement/overvoltage category II
- Isolation Isolation: Input/output 1/output 2/supply;Isolation Voltage (Test): 2.5 kVac;Isolation Voltage (Working):300 Vac
- Length 115 mm
- Load Resistance Current Output: 23 mA/600 Ω max
- Mounting DIN Rail 35 mm Standard, EN 60715
- Noise Calibration >60 dB
- Operating Temperature, Max 70 °C
- Operating Temperature, Min -25 °C
- Output Value Splitter
- Power Consumption 0.8 W, Internal - max 0.65 W
- Relative Humidity 0 to 95% RH (non-condensing)
- Screw Terminal Torque 0.5 Nm
- Series ID DRSL-SP1-Rptr-Spltr
- Stability Load Stability: ≤0.01% of span/100 Ω
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -40 °C
- Supply Power Type DC
- Voltage Loss <1.5 V
- Weight 70 g
- Width 6.1 mm
- Wire Gauge 26 to 12 AWG
Supported Applications
The Omega DRSL-SP1 is an isolated DIN rail repeater/splitter designed for current signals. It provides galvanic isolation and converts a single current input into two independent current outputs, intended for use with SCADA systems or PLC equipment.
Operating Conditions & Performance
The unit operates within an ambient temperature range of -25 to 70°C (-13 to 158°F) and a storage temperature range of -40 to 85°C (-40 to 185°F). It is rated for relative humidity from 0 to 95% RH non-condensing with an IP20 protection degree. Performance specifications include an accuracy of <±0.05% of span, a response time (0 to 90%, 100 to 10%) of <7 ms, and a signal-to-noise ratio >60 dB.
Electrical isolation is provided between input/output 1/output 2/supply with an Isolation Voltage (Test) of 2.5 kVac and an Isolation Voltage (Working) of 300 Vac. The device meets EMC Immunity Influence <±0.5% of span and Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span.
Configuration Options
The DRSL-SP1 series supports the following configurable parameters and options:
- Input/Output Signals: Measurement range 0 to 20.5 mA; functional range 0 to 23 mA with two current outputs.
- Power Supply: 16.8 to 31.2 Vdc via Power Rail or Connectors, consuming a maximum of 0.8 W (typical internal consumption 0.4 W).
- Mechanical Mounting: Designed for DIN EN 60715 - 35 mm rail mounting with dimensions 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5").
- Electrical Connections: Screw terminals accepting wire sizes from 0.13 to 2.5 mm²/AWG 26 to 12 stranded wire with a torque of 0.5 Nm.
- Available Options and Accessories: DRSL-PWR-RAIL (Power rail), DRSL-PCU (Power connector unit, 24 Vdc/2.5 A output), and DRSL-MOD-STOP (Module stop).
Key Product Differences
The series is represented by the model number guide DRSL-SP1 for the isolated repeater/splitter function. The power rail, connector unit, and module stop are sold separately as distinct accessories to support installation on DIN rails.
PDFs & Manuals