Need assistance? Call us: 1-800-663-4209
Series-RHPLC
Wall Mount Humidity/Temp Transmitter - Capacitive Sensor, Analog Output
Models In Stock
- 2% or 3% accuracy models
- Humidity only or temperature and humidity combo
- Wide selection of passive thermistor or RTD temperature sensors
Series-RHPLC
From
C$
172.79
Models In Stock
Product Overview
- Applications HVAC
- Electrical Connection Screw Terminal
- Hysteresis ± 0.8%
- Materials Polycarbonate
- Measurement Type Temperature, Humidity
- Mounting Orientation Wall Mount
- Operating Temperature, Max 140 °F
- Operating Temperature, Min -40 °F
- Relative Humidity 0 to 100% RH
- Repeatability ± 0.1%
- Response Time 8 s
- RH Sensor Drift <0.25% RH/year
- Series ID Series-RHPLC
- Storage Temperature, Max 176 °F
- Storage Temperature, Min -40 °F
- Weight 4.4 oz
Supported Applications
The Series RHPLC Wall Mount Humidity/Temperature Transmitter is a compact, economical sensor designed for the building automation marketspace. Its stylish housing is well vented to promote air flow across the sensing element, improving measurement accuracy in occupied spaces, mechanical rooms, and HVAC return-air environments where continuous relative humidity and temperature monitoring is required.
Each unit uses a capacitive polymer sensing element to deliver a proportional analog output that integrates directly with building controllers and BAS front ends. A combination humidity and temperature model can be configured, allowing a single wall-mounted device to report both parameters. The polycarbonate housing and screw terminal block connections suit permanent indoor wall installation.
Operating Conditions & Performance
The transmitter measures relative humidity across a 0 to 100% RH range and temperature across -40 to 140°F (-40 to 60°C). It operates over an ambient range of -40 to 140°F (-40 to 60°C) and may be stored between -40 to 176°F (-40 to 80°C).
- RH accuracy: ±2% 10 to 90% RH @ 25°C for 2% accuracy units; ±3% 20 to 80% RH @ 25°C for 3% accuracy units.
- RH hysteresis: ±0.8%.
- RH repeatability: ±0.1% typical.
- Drift: <0.25% RH/year.
- Response time: 8 s (t63).
Temperature accuracy depends on the selected temperature sensor. The passive thermistor sensor is rated ±0.2°C @ 25°C. The RTD temperature sensor is DIN class B, rated ±0.3°C @ 0°C. The current/voltage temperature output is rated ±0.3°C @ 25°C.
Power requirements vary with output type: 10-35 VDC for 4-20 mA or 0-5 VDC output; 15-35 VDC for 0-10 VDC output; 10-29 VAC for 0-5 VDC output; and 15-29 VAC for 0-10 VDC output. Electrical connections are made through a screw terminal block. The polycarbonate housing weighs 125 g, measuring 4-1/2 in high, 2-51/64 in wide, and 1-3/32 in deep. The device carries the CE mark.
Configuration Options
Models differ primarily by accuracy class, humidity output signal, and temperature output type, following the order code RHPLC - <Accuracy> - <Housing> - <Humidity Output> - <Temperature Output> - <Options>.
Accuracy class
The 2 designator provides 2% accuracy (±2% 10 to 90% RH @ 25°C), while the 3 designator provides 3% accuracy (±3% 20 to 80% RH @ 25°C). All units share the North American style wall mount housing (N).
Humidity output
- 1: Current 4-20 mA.
- 2: Voltage 0-10 VDC.
- 3: Voltage 0-5 VDC.
Temperature output
- 0: None (humidity-only configuration).
- 1: Current 4-20 mA.
- 2: Voltage 0-10 VDC.
- 3: Voltage 0-5 VDC.
- A: 10K Ω @ 25°C thermistor type III.
- B: 10K Ω @ 25°C thermistor type II.
- C: 3K Ω @ 25°C thermistor.
Additional temperature sensing elements include a 20K Ω @ 25°C thermistor as well as 100 Ω or 1K Ω RTD types conforming to DIN 385. The FC option adds a factory calibration certificate for 3% accuracy units.
Key Product Differences
The Series RHPLC comprises the following eight configured models, each pairing an accuracy class with a specific humidity and temperature output:
- RHPLC-2N11 — 2% accuracy, North American wall mount, Current 4-20 mA humidity output, Current 4-20 mA temperature output.
- RHPLC-2N22 — 2% accuracy, Voltage 0-10 VDC humidity output, Voltage 0-10 VDC temperature output.
- RHPLC-3N11 — 3% accuracy, Current 4-20 mA humidity output, Current 4-20 mA temperature output.
- RHPLC-3N1A — 3% accuracy, Current 4-20 mA humidity output, 10K Ω @ 25°C thermistor type III temperature output.
- RHPLC-3N1B — 3% accuracy, Current 4-20 mA humidity output, 10K Ω @ 25°C thermistor type II temperature output.
- RHPLC-3N22 — 3% accuracy, Voltage 0-10 VDC humidity output, Voltage 0-10 VDC temperature output.
- RHPLC-3N2A — 3% accuracy, Voltage 0-10 VDC humidity output, 10K Ω @ 25°C thermistor type III temperature output.
- RHPLC-3N2B — 3% accuracy, Voltage 0-10 VDC humidity output, 10K Ω @ 25°C thermistor type II temperature output.
PDFs & Manuals
Accessories
accessories
AC power transformer, 120/208/240/277/480 VAC input, 24 VAC isolated output, 40 VA, dual hub
C$41.38 / each
1424 In Stock
Show Ratings & Reviews
Rated 5 out of
5
by
Cameron Adriaan from
Excellent product
Very good for my use case. I had to keep track of temp and humidity in a manufacturing room making chocolates. The small size and ease of installation made this an excellent product. Additionally the repeatability is excellent
Date published: 2026-06-27
Rated 5 out of
5
by
DinRail from
Excellent product
High quality, rigid construction, sleek lines, and perfect fit makes these an excellent choice
Date published: 2025-10-28