Need assistance? Call us: 1-800-663-4209
Model-TBU-00
Temp Transmitter for Process Control – Configurable 4-20 mA Output, Micro-USB
- Configurable measurement range
- Standard temperature sensor head enclosure mounting
- Pt100 connection for 2, 3, or 4 wires
Model-TBU-00
From
C$
246.98
Product Overview
- Accuracy ± 0.1 %
- Applications Boilers, Oil, Refrigeration, Refrigeration Equipment
- Current Output 4 to 20 mA
- Input Note Thermocouples J, K, R, S, T, N, E, and B; 2, 3, or 4-wire Pt100 RTD, 2 or 3-wire Pt1000 RTD, 2-wire NTC thermistor, or 0-50 mV voltage. RTD: 238 to 752°F, Thermocouple: 32 to 1202 °F
- Measurement Type Thermocouple, RTD, Thermistor, Voltage
- Number of Wires 2, 3, 4
- Operating Temperature, Max 185 °F
- Operating Temperature, Min -40 °F
- Output Detail Linearized 4-20 mA, 2-wire or 20-4 mA loop powered
- Output Signal Current
- Response Time 1.6 s
- Response Time Note 1.6 s, typical.
- Series ID Model-TBU-00
- Supply Power Type DC
- Supply Voltage 10 to 35 Vdc
- Temperature Drift <± 0.16%/25°C
- Temperature Input Range 32 to 1202 °F
- Voltage Accuracy ± 0.13%
- Voltage Input Range 0 to 50 mV
- Weight 40 g
Supported Applications
The Dwyer Model TBU-00 is a high precision temperature transmitter designed to mount in most temperature sensor instrument enclosures. It serves as a universal input signal conditioner for process control applications, reducing inventory requirements by supporting multiple sensor types through a single device.
- Temperature measurement using thermocouples (Types J, K, R, S, T, N, E, and B)
- Resistance Temperature Detector (RTD) inputs: 2, 3, or 4 wire Pt100; 2 or 3 wire Pt1000
- NTC thermistor input (2 wire)
- Voltage measurement from 0 to 50 mV
Operating Conditions & Performance
The transmitter operates within an ambient temperature range of -40°F to 185°F (-40 to 85°C). It requires a power supply between 10 and 35 VDC. The typical response time is 1.6 s, with a temperature drift specification of < ±0.16% / 25°C.
Accuracy varies by input type as documented in the series specifications:
- Voltage (0 to 50 mV): ±0.1% FS
- Thermocouples J, K, R/S, T, N, E, B: ±0.1% FS
- Pt100/Pt1000 RTDs: ±0.13% FS
- NTC Thermistor: ±0.3°C
Configuration Options
The Model TBU-00 offers configurable parameters to match specific sensor and process requirements.
Sensor Input Configuration
The universal input accepts the following configurations:
- Thermocouples: J, K, R, S, T, N, E, B
- Pt100 RTD: 2, 3, or 4 wire connections
- Pt1000 RTD: 2 or 3 wire connections
- NTC Thermistor: 2 wire connection
- Voltage: 0 to 50 mV range
Output and Power Options
The output signal is configurable via software:
- Linearized 4-20 mA (direct acting)
- Reverse 20-4 mA loop powered configuration
- Transmitter type: 2, 3, or 4 wire operation
Configuration and Physical Attributes
The device features a micro-USB port for easy configuration and calibration in the lab or field. The physical dimensions are 13/16 [20.5] height by 1-23/32 [43.5] diameter, with a weight of 1.4 oz (40 g). It carries CE approval.
Key Product Differences
The Model TBU-00 is factory set to Pt100 Ω RTD, 0 to 100°C, direct acting by default. Users can reconfigure the input type, measurement range, and calibration using configuration software connected via the micro-USB port.