1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here

PM1000-Series
Pressure Transmitter & loop powered pressure monitor
Models In Stock
- Unique Local Plug-on Display
- Designed for the PX4200 Series Pressure Transducers
- Switching Setpoint - PM1001 only
PM1000-Series
From
C$
375.16
Models In Stock

Product Overview
- Status Control false
- Accuracy ± 0.25 %
- Accuracy Detail ±0.25% full scale includes linearity, and hysteresis
- Additional Features 1 Plug-on display
- Burst Pressure 2
- Case Material Stainless Steel
- Electrical Connection DIN 43650 A (solenoid valve)
- Electrical Output 4 to 20 mA
- Enclosure Ratings IP65
- Humidity Range 0.95
- Long Term Stability ±0.2%
- Materials, Wetted Titanium
- Operating Temperature, Max 80 °C
- Operating Temperature, Min -40 °C
- Output Detail 4 to 20 mA (2-Wire) with zero and span adjustments
- Process Connection Size 1/4 in
- Process Connection Type NPT Male
- Process Temperature, Min -50 °C
- Repeatability ±0.1%
- Response Time 10 ms
- Sensor Type Silicon on Sapphire
- Supply Power Note 13 to 36 Vdc with PM1000 18 to 36 Vdc reverse polarity protected; Load Driving Capacity: 1150Ω @ 36 Vdc, R maximum = (Vs-13)/20 with PM1000 R maximum = (Vs-18)/20
- Supply Voltage 13 to 36 Vdc
- Thermal Span Effect <±0.016% FS/°F
- Thermal Zero Effect <±0.016% FS/°F
- Weight 90 g
Description
The PM1000 plug-on display is a local display suitable for the PX4200 series pressure transducers. The plug-on display is simply plugged in between the transmitter connector plug and socket and is then ready for operation. Directly from this unit, the following parameters can be set: zero, scale, decimal point position, damping and switching set point (PM1001 only).
PDFs & Manuals
Show Ratings & Reviews
Can the display be changed to read PSI instead of mA?
Thank you for your question. Yes, the display can read out psi. It is an in-line display for a loop set-up with 4-20mA, and users can setup the unit to output the display values based on the mA values.
Date published: 2019-04-24
What is "switching set point"?
The PM1000 series plug on displays are for use with the PX4200 pressure transmitters. The PM1000 is for display only. The PM1001 also has a single set point with a solid-state switch output. This allows the user to set a pressure value and when the unit exceeds this value the switch will activate. It can be sued as an alarm or for simple on/off control. Thank you and please feel free to contact us again if you have additional questions.
Date published: 2019-11-19