RTD-Outdoor-Air

Platinum RTD Outdoor Air

  • Outside Air Temperature Sensing
  • Cold Storage Facilities
  • High Dew Point/Condensing Environments
RTD-Outdoor-Air
From
Platinum RTD Outdoor Air RTD-Outdoor-Air RTD-Outdoor-Air
loading all models
Product Overview
  • Accuracy +/- 0.06% Class A
  • Accuracy Detail (Tolerance Formula: +/- ºC = (0.15ºC + (0.002 *
  • Alloy Material (-) Copper
  • Alloy Material (+) Copper
  • Applications Building and Maintenance, Environmental Monitoring
  • Approvals DIN EN 60751 (IEC 751)
  • Electrical Connection Pigtails
  • Enclosure Ratings IP66, NEMA Type 3R, NEMA Type 4X, UL94 V-0
  • Fitting PVC
  • Insulation Etched Teflon (PTFE) Colored Leads 
  • Number of Sensing Points 1
  • Operating Current 5 mA
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -40 °C
  • Output Detail Sensor Output @ 0°C (32°F): A/100-xW-xx-O Series: 100 Ohms nominal
  • Response Time 25 Seconds nominal
  • Self Heating Effect 7 mW / °C
  • Series ID RTD-Outdoor-Air
  • Sheath Material PVC
  • Stability +/- 0.03% after 1000 Hours @ 300ºC (572ºF)
  • Storage Temperature, Max 70 °C
  • Storage Temperature, Min -40 °C
  • Temperature Coefficient DIN EN 60751 (IEC 751)
  • Temperature Measurement Range -40 to 70°C
  • Tube Length 4.7 in
  • Wire Gauge 22 AWG

Supported Applications

The ACI Platinum RTD Outdoor Air series is a single-point temperature sensor designed for use with electronic controllers in commercial heating and cooling building management systems. The sensors are intended for outdoor mounting to monitor ambient air conditions.

  • Commercial HVAC control loops requiring precise outside air measurement.
  • Building automation systems (BAS) utilizing 2-wire or 3-wire RTD inputs.

Operating Conditions & Performance

The series operates within a temperature range of -40 to 70°C (-40 to 158°F), with an identical storage temperature range. It is rated for operating humidity from 10 to 100% RH, condensing. The sensing element follows the DIN EN 60751 (IEC 751) standard with a temperature coefficient of 3850 ppm/°C.

  • Accuracy: Class A tolerance defined by +/- °C = (0.15°C + (0.002 * |t|)), where |t| is the absolute value of Temperature above or below 0°C in °C. Specific points include +/- 0.23°C (+/- 0.414°F) at -40°C (-40°F), +/- 0.15°C (+/- 0.27°F) at 0°C (32°F), and +/- 0.29°C (+/- 0.53°F) at 70°C (158°F).
  • Response Time: 25 Seconds nominal for a 63% step change.
  • Sensor Stability: +/- 0.03% after 1000 Hours @ 300°C (572°F).

Configuration Options

The series supports multiple sensor resistances, wire configurations, and enclosure types to accommodate various installation environments.

Sensor Elements & Outputs

  • Nominal Resistance: 100 Ohms (A/100 Series) or 1 KΩ (A/1K Series).
  • Wire Configuration: Two-wire (non-polarity sensitive) or Three-wire (polarity sensitive). The three-wire option compensates for external lead wire resistance.
  • Lead Wires: 14" (35.6 cm) length, 22 AWG (0.65 mm), Silver Plated Copper conductors with Etched PTFE Teflon colored insulation rated MIL-W-16878/4 (Type E).

Housing & Enclosures

Three enclosure styles are available, each with specific material and rating characteristics:

  • Euro (-EH): PC/ASA Plastic with UV Protectant; UL94-V0 flammability rating. Operating range -40 to 88°C (-40 to 190°F).
  • NEMA 4X (-4X): Polystyrene Plastic; UL94-V2 flammability rating, NEMA 4X (IP66). Operating range -40 to 70°C (-40 to 158°F).
  • Bell Box (-BB): Aluminum; NEMA 3R. Operating range -40 to 121°C (-40 to 250°F).

Approvals & Options

The series carries CE, RoHS2, and WEEE approvals. Optional NIST Certificates (3 Points) are available for specific configurations.

Key Product Differences

Variants differ primarily by sensor resistance value, wire count, and enclosure material/rating:

  • The A/100 series provides a 100 Ohm nominal output at 0°C (32°F), while the A/1K series provides a 1 KΩ nominal output.
  • Two-wire models are non-polarity sensitive; three-wire models are polarity sensitive and intended for systems requiring lead resistance compensation.
  • The Euro (-EH) enclosure features a twist-off cover with a water-tight cord grip. The NEMA 4X (-4X) is a weatherproof plastic housing, while the Bell Box (-BB) utilizes an aluminum construction.
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 5ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 3ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-CA
en_CA
Save Configuration