Series-16LConfiguration

Contrôle de limite approuvé par FM pour chauffages à gaz, entrée universelle, points de consigne

FM Approved Limit Control for Gas Heaters, Universal Input, Set Points
  • Remote or integral reset button
  • Peak and valley temperature indication
  • Open sensor protection
Series-16L

Build your Part Number

FM Approved Limit Control for Gas Heaters, Universal Input, Set Points Series-16L Series-16L
loading all models
Aperçu du produit
  • Accuracy ± 0.25% span ± 1 least significant digit
  • Display Note Two 4 digit, 7 segment 0.3˝ (7.62 mm) high LEDs
  • Display Type LED
  • Enclosure Ratings IP66, NEMA Type 4X
  • Input Control Signal 0 to 20 mA
  • Input Type Thermocouple, RTD, DC Voltage or DC Current
  • Memory Backup Non-Volatile
  • Number of Digits 4
  • Operating Temperature, Max 131 °F
  • Operating Temperature, Min 14 °F
  • Power Consumption max 5 VA
  • RTD Input Range JPt 100: -4 to 752°F; Pt 100: -328 to 1562°F; Ni 120: -112 to 572 °F; Cu 50: -58 to 302 °F
  • Series ID Series-16L
  • Supply Power Note 100-240 VAC, nominal, +10 -15%, 50 to 400 Hz. single phase; 132-240 VDC, nominal, +10 -20%
  • Supply Power Type AC/DC
  • Supply Voltage 100 to 240 Vac, 132 to 240 Vdc
  • Temperature Sensor Type RTD or Thermocouple
  • Thermocouple Input Range Note Type K: -328 to 2372°F; Type J: -148 to 2192°F; Type T: -328 to 752°F; Type E: 32 to 1112°F; Type W: -328 to 2372°F; Type R: 32 to 3092°F; Type S: 32 to 3092°F; Type B: 212 to 3272°F; Type L: -328 to 1562°F; Type U: -328 to 932°F
  • Voltage Input Range 0 to 5 V, 0 to 10 V
  • Weight 8 oz

Supported Applications

The Dwyer Series 16L is a microprocessor-based limit control designed for temperature and process monitoring. The primary application documented for this series is gas fired heater limit control. It functions as a universal input controller capable of accepting thermocouple, RTD, DC voltage, or DC current signals.

Operating Conditions & Performance

The Series 16L operates within an ambient temperature range of 14 to 131°F (-10 to 55°C). Accuracy is specified as ±0.25% of span, ±1 least significant digit. The unit features a dual display with two 4-digit, 7-segment LEDs that are 0.3" (7.62 mm) high. Power requirements support 100-240 VAC nominal (+10 -15%, 50 to 400 Hz single phase) or 132-240 VDC nominal (+10 -20%), with a maximum power consumption of 5 VA.

The front panel carries an NEMA 4X (IP66) rating. The device includes nonvolatile memory requiring no batteries for backup and features open sensor protection along with peak and valley temperature indication capabilities.

Approvals

  • FM Approved
  • cULus Listed

Configuration Options

The Series 16L offers configurable output and communication options to suit specific control needs. The controller supports selectable inputs for 10 thermocouple types, 4 RTD types, DC voltage, or DC current.

Output Configurations

  • N.O. relay (SPST)
  • N.C. relay (SPST)
  • SSR output
  • DC SSR output
  • 15 VDC output

Relay outputs are rated for 3 A @ 240 VAC resistive or 1.5 A @ 240 VAC inductive.

Options and Accessories

  • -934: Process signal output, isolated 0-20 mADC (Analog Retransmission)
  • -936: Process signal output, isolated 0-10 VDC (Analog Retransmission)
  • -948: 4-Stage Set Point
  • -992: RS-485 Serial Communications
  • -993: RS-232 Serial Communications
  • Option 9502: Low voltage power supply (12 - 24 Vdc/Vac, 50-400Hz)
  • A-600: R/C snubber accessory

Note that only Option 9502 may be combined with another option. The unit is designed for panel mounting with a cutout dimension of 1.77" + 0.02" [45 mm + 0.6 mm] square.

Key Product Differences

The series includes specific model configurations such as the 16L2030, which provides a N.O. relay output with no second output, and the 16L2034, configured with both a N.O. relay and a N.C. relay. Other configurations are available via the manufacturer's website.

Installation notes specify that thermocouple or Class 2 wiring must not be run in the same conduit as power leads. For thermocouple inputs, extension leads of the matching type designated for the specific thermocouple must always be used. The unit includes a remote or integral reset button option depending on configuration.

Accessoires

accessories

A-600 R/C SNUBBER
C$45.01 / each
4 En stock
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 41ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
fr-CA
en_CA
Enregistrer la configuration