Skip to search Skip to main content Skip to navigation

Need assistance? Call us: 1-800-663-4209

We noticed you are in , please visit your local site by clicking the below link for regional offers and support.

Series-DLD

Dual Channel Leak Detection Relay for Submersible Pumps – Monitors Seals

Series-DLD
From C$ 449.39
Dual Channel Leak Detection Relay for Submersible Pumps – Monitors Seals Series-DLD Series-DLD
loading all models
Product Overview
  • Control Mode On/Off
  • Isolation 2500 V
  • LED Indicators Red LED Illuminates when Leak is Detected
  • Materials Polycarbonate
  • Mounting 8-pin octal
  • Operating Temperature, Max 131 °F
  • Operating Temperature, Min -4 °F
  • Power Consumption 2 VA
  • Response Time Energize: 6 ms, Release: 2.5 ms
  • Series ID Series-DLD
  • Storage Temperature, Max 185 °F
  • Storage Temperature, Min -40 °F
  • Supply Power Type AC
  • Supply Voltage 120 Vac
  • Switch Activation Falling
  • Switch Note 5 A @ 120 VAC resistive, 345 VA inductive
  • Switch Rating 5 A @ 120 Vac, 345 VA
  • Switch Type (2) SPST NO
  • Switching Voltage 9 Vdc
  • Weight 8 oz

Supported Applications

The Dwyer Series DLD is a dual channel leak detection relay designed to monitor the shaft seals of two submersible pump motors. The unit detects leaks by sensing the status of a resistive float switch or conductivity switch installed in the seal cavity. When resistance drops below the sensitivity rating, the output relay energizes and an LED indicator illuminates. This configuration allows engineers to trigger an alarm or de-energize the pump before failure occurs.

Operating Conditions & Performance

The Series DLD operates on a 120 VAC, 50/60 Hz power supply with approximately 2 VA consumption. The unit provides isolation voltage of 2500 V and features response times of approximately 6 ms to energize and 2.5 ms to release. Ambient operating temperature limits are -4 to 131°F (-20 to 55°C), while storage temperatures range from -40 to 185°F (-40 to 85°C). The relay contacts support an electrical rating of 5 A @ 120 VAC resistive and 345 VA inductive. Each channel includes a respective red LED that illuminates when a leak is detected.

Configuration Options

The series offers two distinct models with adjustable sensitivity ranges to accommodate different switch types:

  • DLD-ACY: Sensitivity range of 10 K to 25 K Ω (adjustable).
  • DLD-ACZ: Sensitivity range of 4.7 K to 100 K Ω (adjustable).

The unit mounts via an 8-pin octal socket and includes a polycarbonate dust cover for enclosure protection. Output signals consist of two normally open (N.O.) SPST relay contacts with a switch voltage of 9 VDC excitation.

Key Product Differences

The primary distinction between the Series DLD variants is the adjustable sensitivity range required by the specific float or conductivity switches used in the seal cavity. The DLD-ACY model supports lower resistance thresholds (10 K to 25 K Ω), while the DLD-ACZ offers a broader span from 4.7 K to 100 K Ω. Both models share identical physical dimensions of 3 [76.20] height, 2-3/8 [60.32] width, and 1-3/4 [44.45] depth, with a weight of 8 oz (227 g). Agency approvals include UL 508, cUR, and UR.

  • bvseo_sdk, java_sdk, bvseo-4.0.0