Product Overview
  • Approvals CE
  • Approvals Note CE: BS EN 61326
  • Baud Rate 19200
  • Calibration Calibration Scaling: 2 to 6 points signal against process;Active Calibration:Active calibration against live load cell
  • Data Interface USB
  • Display Type LED
  • Drift < ± 0.05%
  • Electrical Output 0 to 21.5 mA
  • Enclosure Ratings IP65
  • Excitation Current 59 mA
  • Filter 1 to 20 seconds to reach 70% of final value
  • Height 90 mm
  • Isolation 500 Vdc
  • LED Indicators LED, Green when output -0.1 to 100.1%, all else red
  • Length 56.4 mm
  • Materials Polyimide 6.6
  • Mounting DIN Rail 43880, Color Grey
  • Offset Tare Input Type - Remote volt free contact, up to 10 meter distance
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -30 °C
  • Output Value Process
  • Relative Humidity 10 to 90%RH (non condensing)
  • Series ID TXDIN1600S-Transmitter
  • Shell Color Gray
  • Software Windows PC Software
  • Supply Power Type AC/DC
  • Update Rate 10 or 80 SPS
  • Weight 70 g
  • Width 17.5 mm

Supported Applications

The Omega TXDIN1600S is a smart powered bridge amplifier designed for strain gauge and load cell signal conditioning. It functions as a DIN rail mount transmitter that scales input signals to process values, supporting applications requiring voltage or current re-transmission of sensor data.

Operating Conditions & Performance

The TXDIN1600S operates with an ambient temperature range of -30 to 70°C (-22 to 158°F) and a storage ambient range of -30 to 70°C (-22 to 158°F). Configuration is specified for an ambient environment of 10 to 30°C (50 to 86°F). The device maintains operation within a humidity rating of 10 to 90% RH (non condensing) and features an enclosure protection level of IP65.

Performance specifications include bridge input linearity of ± 0.01% and drift less than ± 0.05%. The device utilizes ratio metric measurement for high stability with a sample rate selectable at 10 or 80 SPS (samples per second). Output accuracy is defined as (mA out/2000) or 5 µA whichever is the greater, with a drift of 1 µA/°C. Voltage output accuracy is ± 5 mV.

Measurement and Signal Parameters

  • Bridge Input: -7.6 to 7.6 mV/V (-38 to 38) mV at 5V excitation; Four wire radimetric type.
  • Bridge Excitation: 5 Volts DC ± 0.1 V @ 59 mA, supporting total bridge impedance from 85 to 10000 Ω (operates with four 350 Ω cell in parallel).
  • Response Time: Filter selectable from 1 to 20 seconds to reach 70% of final value.

Configuration Options

The TXDIN1600S series supports configurable output signals, calibration scaling, and user interface options. The device is housed in a DIN rail enclosure (style DIN 43880) constructed from Polyimide 6.6 with dimensions of 56.4 mm width x 90 mm height x 17.5 mm depth.

Output Signal Options

  • Current Source: Range (0 to 21.5) mA, max load 750 Ω.
  • Current Sink: Range 0 to 21.5 mA, supply 10 to 30 Vdc, voltage effect 0.2 µA/V.
  • Voltage Output: 0 to 10.1 V or -10.1 to 10.1 V with ± 2 mA current drive and min load 5000 Ω @ 10 V.

User Interface & Configuration

  • Calibration: Supports (2 to 6) points signal against process scaling, including active calibration against live load cell and remote set tare offset with programmable user set point.
  • Front Panel: Independent “Low” and “High” push buttons allow manual setting of low and high output points. LED indication shows green when output is -0.1 to 100.1%, red otherwise.
  • Digital Interface: USB 2.0 at 19,200 baud for PC running Windows XP or later; supports process units (4 characters) and tag number (20 characters).

Power & Electrical Connections

  • Supply: 10 to 48 Vdc, 10 to 32 Vac protected by internal 500 mA resettable fuse; power consumption < 1 W full power.
  • Isolation: Supply to input to output 500 Vdc.
  • Tare Input: Remote volt free contact, up to 10 meter distance.
  • Terminals: Screw terminals accepting wire size maximum 2.5 mm (0.10").

Key Product Differences

The TXDIN1600S is a single model family designated as the DIN-rail mount load-cell transmitter. If configuration is not specified at the time of order, the product ships with default settings: 2 mV/V input and 4 to 20 mA output range.

Rated 5 out of 5 by from Works as indicated Works as indicated and ordering was easy. Thankszc
Date published: 2023-12-30
  • y_2026, m_8, d_6, h_10
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_1
  • loc_en_CA, sid_TXDIN1600S, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 6ms
  • REVIEWS, PRODUCT

We have a TXDIN1600S, which we are having issues with getting USB Speedlink to work with, we have been trying to get support on this issue for quite a while now, have tried multiple contact, including pressure@omega.com, really need some support now.

Asked by: Clif
Thank you for your inquiry. Sorry for your issue,will have a engineer reach out to to by email to discuss how to rectify this.
Answered by: application engineer je
Date published: 2020-07-23

How to tell which load cells are compatible with the TXDIN1600S load cell transmitter? are they all compatible, or only some of them?

Asked by: KevinH
The TXDIN1600S will function with any full bridge load cell that has a mV/V sensitivity range of 0.2 to 7.5 mV/V. All of our load cells that do not already have built-in signal conditioning have mV/V sensitivities that fall within this range. Please note that even though the TXDIN1600S is a load cell excitation that is fixed a 5 VDC it will still work with load cell that indicate 10 VDC as their nominal excitation
Answered by: Applications Engineer Jk
Date published: 2023-03-06

I've ordered the TXDIN1600s to couple it with the load cell PXM600MU-14BARGV and with the OMB-DAQ-2416. Unfortunately ihe TXDIN doesn't get recognized by the USB Speedlink software that comes with it so I can't set them up. What should I do?

Asked by: Tarik
Please contact our Pressure Applications Engineers at pressure@omega.com or call 1-800-826-6342 and ask for Pressure Engineering.
Answered by: Applicatrions Engineer JK
Date published: 2020-07-22
  • y_2026, m_8, d_6, h_10CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_3
  • loc_en_CA, sid_TXDIN1600S, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 12ms
  • QUESTIONS, PRODUCT
en-CA
en_CA
Save Configuration