Models In Stock
  • Isolation and Conversion of Bipolar Process Voltage and Current Signals to Unipolar Signals
  • Slimline Housing—Only 6 mm (0.24') Wide
  • Multiple Signal Ranges (DIP-Switch Selectable)
  • High Accuracy, <0.05% of Selected Range
DRSL-DC4-Bipolar-Sig-Cond
From C$ 370.77
Models In Stock
DIN Rail Signal Conditioner for Bipolar Process Inputs DRSL-DC4-Bipolar-Sig-Cond DRSL-DC4-Bipolar-Sig-Cond
loading all models
Product Overview
  • Approvals CE, UL, RoHS
  • Bandwidth >100 Hz or 10 Hz (Selectable Via DIP-Switch)
  • Calibration Temperature, Max 28 °C
  • Calibration Temperature, Min 20 °C
  • Electrical Output 0 to 23 mA
  • EMC Immunity Note Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
  • EMC Standard NAMUR NE 21
  • Enclosure Ratings IP20
  • Height 113 mm
  • Installation Pollution degree 2 and measurement/overvoltage category II
  • Isolation 300 Vac
  • Length 115 mm
  • Load Resistance Current Output: 23 mA/600 Ω max, Voltage Output:>10 kΩ min
  • Mounting DIN Rail 35 mm Standard, EN 60715
  • MTBF 241 yrs
  • Noise Calibration >60 dB
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -25 °C
  • Output Value Process
  • Power Consumption 0.8 W, Internal - max 0.65 W
  • Relative Humidity 0 to 95% RH (non-condensing)
  • Screw Terminal Torque 0.5 Nm
  • Series ID DRSL-DC4-Bipolar-Sig-Cond
  • Span, Max Corresponds to the presently selected DIP switch output range
  • Stability Load Stability: ≤0.002% of span/100 Ω
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Power Type DC
  • Weight 70 g
  • Width 6.1 mm
  • Wire Gauge 26 to 12 AWG

Supported Applications

The Omega DRSL-DC4 is a bipolar isolated DIN rail signal conditioner designed for process signals. It provides galvanic isolation and converts bipolar process voltage and current inputs to unipolar output signals suitable for SCADA or PLC systems. The device eliminates ground loops and supports the measurement of floating signals.

Operating Conditions & Performance

The DRSL-DC4 operates within an ambient temperature range of -25 to 70°C (-13 to 158°F) with a storage temperature capability from -40 to 85°C (-40 to 185°F). It is rated for relative humidity between 0 to 95% RH non-condensing and carries an IP20 protection degree. The unit meets Pollution Degree 2 and Measurement/Overvoltage Category II installation area requirements.

Performance specifications include a response time of <7 ms (or <44 ms selectable) for the 0 to 90% rise and 100 to 10% fall, with an accuracy of <±0.05% of span. The signal-to-noise ratio exceeds 60 dB, and the cut-off frequency is >100 Hz or 10 Hz (selectable via DIP-switch). EMC immunity influence is specified at <±0.5% of span, while extended EMC immunity under NAMUR NE 21, A Criterion, Burst conditions remains below ±1% of span.

Input and Output Ranges

  • Bipolar Current Input: Programmable ranges include ±10 mA and ±20 mA. The functional range extends from -23 to 23 mA with an input voltage drop of <1V @ 23 mA.
  • Bipolar Voltage Input: Programmable ranges are available for ±5 V and ±10 V, supporting a functional range of -11.5 to 11.5 V with an input resistance ≥1 MΩ.
  • Unipolar Current Output: Configurable signal ranges include 0 to 20 mA and 4 to 20 mA. The output supports a load of up to 600 Ω (per channel) at 23 mA, with a current limit ≤28 mA.
  • Unipolar Voltage Output: Programmable signal ranges include 0 to 10 V, 2 to 10 V, 0 to 5 V, and 1 to 5 V. The functional range is 0 to 11.5 V with a minimum load resistance of >10 kΩ.

Isolation and Power

The unit features galvanic isolation between input, output, and supply circuits. Isolation voltage (test) is rated at 2.5 kVac, with an isolation working voltage of 300 Vac. The Mean Time Between Failures (MTBF) exceeds 241 years according to IEC 61709 (SN29500). Power supply requirements are 16.8 to 31.2 Vdc via power rail or connectors, with a maximum power consumption of 0.8 W.

Configuration Options

The DRSL-DC4 series is configured for DIN EN 60715 - 35 mm rails and features a slimline housing measuring 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5"). The unit weighs approximately 70 g (0.15 lb). Factory-calibrated ranges are configurable via DIP switches, and the device supports DIN rail mounting without an air gap.

Connections

The signal conditioner utilizes screw terminals for electrical connections. It accepts stranded wire sizes from 0.13 x 2.5 mm²/AWG 26 to 12 with a recommended screw terminal torque of 0.5 Nm.

Approvals and Certifications

  • CE
  • UL US
  • RoHS
  • 1 YEAR WARRANTY (OMEGACARE™ Extended Warranty Program available)

Key Product Differences

The primary model in this series is the DRSL-DC4, described as a bipolar isolated DIN rail signal conditioner for process signals. The series supports specific accessory configurations to facilitate installation and power distribution:

  • DRSL-PWR-RAIL: Power rail with cover and two end covers (one right hand, one left hand), 1 m (3.3') length.
  • DRSL-PCU: Power connector unit providing 24 Vdc/2.5 A output to the power rail.
  • DRSL-MOD-STOP: Module stop screwed onto the power rail to support and hold mounted devices.

Accessories

installation hardware

MODULE STOP FOR DRSL SERIES
C$15.11 / each
5 In Stock
POWER RAIL FOR DRSL SERIES
C$308.14 / each
0 In Stock

meters/controllers

PWR CONN FOR DRSL SERIES CE
C$197.90 / each
9 In Stock
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 6ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 3ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-CA
en_CA
Save Configuration