Need assistance? Call us: 1-800-663-4209
DRST-AC-Srs-Sig-Cond
DIN Rail AC Current and Voltage Transmitter
Models In Stock
- UL and cUL Approval
- Measures AC Current and Voltage Signals
- Outputs Passive or Active Current Signals
- Response Time < 0.75 s and Excellent Accuracy Better Than 0.3%
DRST-AC-Srs-Sig-Cond
From
C$
496.59
Models In Stock
Product Overview
- Approvals UL, RoHS
- Approvals Note EMC: 2014/30/EU, LVD: 2014/35/EU, RoHS: 2011/65/EU, UL: UL 508 / C22.2 no. 14, NB: For custom configurable signal ranges, general accuracy and EMC specifications are 0.3% of full sc
- Calibration Temperature, Max 28 °C
- Calibration Temperature, Min 20 °C
- CMRR 0.02 ppm/VHz
- Display Type Programmer
- Electrical Output 0 to 23 mA
- EMC Immunity Note NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
- EMC Standard NAMUR NE 21
- Enclosure Ratings IP20
- Height 109 mm
- Installation Pollution degree 2 and measurement/overvoltage category II
- Isolation 2.3 kVac
- Length 104 mm
- Load Resistance Current Output: ≤ 800 Ω, Voltage Output: 500 kΩ
- Mounting DIN Rail 35 mm Standard, EN 60715
- Noise Calibration >60 dB
- Operating Temperature, Max 60 °C
- Operating Temperature, Min -20 °C
- Output Value Process
- Power Consumption max 1.8 W
- Power Dissipation ≤ 2.5 W
- Relative Humidity <95% RH
- Screw Terminal Torque 0.5 Nm
- Series ID DRST-AC-Srs-Sig-Cond
- Signal Dynamics Input 20 bit
- Signal Dynamics Output 18 bit
- Stability Load Stability: ≤0.01% of span/100 Ω
- Supply Power Type AC/DC
- Vibration IEC 60068-2-6
- Vibration Note 2 to 13.2 Hz: ±1 mm;13.2 to 100 Hz: ±0.7 g
- Weight 250 g
- Width 23.5 mm
- Wire Gauge 26 to 14 AWG
Supported Applications
The Omega DRST-AC series comprises universal AC/DC transmitters designed for DIN rail mounting in industrial and factory automation applications. These devices provide signal conditioning for hazardous electric voltages, converting high-voltage inputs into standardized process signals.
Operating Conditions & Performance
The transmitter is engineered to operate within an ambient temperature range of -20°C to +60°C with a maximum relative humidity of 95% RH (non-condensing). The unit features double insulation and carries UL Listed and CE Mark approvals. It must be installed in environments meeting pollution degree 2 or better.
Input capabilities cover hazardous electric voltages ranging from 75 to 1500 VDC and 50 to 1000 VAC, with specific measurement ranges including 0-1000 VAC, 0-1000 VDC, or a universal 0-1000 VAC/VDC configuration. The device requires a power supply of 24 VDC (±10%). For current outputs, the minimum load resistance is specified as 500 Ω for 4-20 mA output.
Mounting and Physical Specifications
- Housing Material: Plastic enclosure with an IP20 rating.
- Dimensions: 110 mm (H) x 75 mm (W) x 100 mm (D).
- Mounting Standard: DIN rail according to DIN EN 60715.
- Electrical Connection: Screw terminals.
Configuration Options
The DRST-AC series is configurable via a model number guide following the structure: DRST-AC - <Input Type> - <Output Type> - <Power Supply> - <Options>. The series supports various input types, output signals, and optional interfaces to accommodate specific monitoring needs.
Configurable Options
- Input Types:
- VAC: AC Voltage Input
- VDC: DC Voltage Input
- VAC/VDC: Universal AC/DC Voltage Input
- Output Signals:
- 4-20 mA Output (code: 4-20mA)
- 0-20 mA Output (code: 0-20mA)
- 0-10 V Output (code: 0-10V)
- 0-5 V Output (code: 0-5V)
- Power Supply:
- 24 VDC Power Supply (code: 24VDC)
- Options and Accessories:
- DRSL-DISPLAY: Detachable display for local monitoring and programming.
- CM: Remote Operator Interface (ROI) providing Modbus/RTU and Wi-Fi connectivity.
Key Product Differences
Variation within the series is defined by the selected input type, output signal range, power supply configuration, and optional interfaces. The device contains no DIP-switches or jumpers; configuration relies on the detachable DRSL-DISPLAY for local monitoring and programming.
Important operational constraints include a maximum hazardous fuse size of 10 A. Users must not open the front plate to avoid damaging the connector for the DRSL-DISPLAY, and repair or replacement of circuit breakers is restricted to Omega A/S only.
PDFs & Manuals