Need assistance? Call us: 1-800-663-4209
Model-CLS1
Capacitance Level Switch for Precise High/Low Level Detection in Tanks
Models In Stock
- Electronics provide highly sensitive measurement detection (requires less than a 1 picofarad shift from ambient)
- State of the art technology ignores material build-up on the vessel sidewall or along the probe assembly
- One time calibration is simple with a single multi-turn potentiometer
- Red LED on housing indicates sensor status
- Adjustable 1-30 second time delay and a 5 A, SPDT fail-safe relay output
- Added installation flexibility with vertically or horizontally mounting
Model-CLS1
From
C$
1,038.05
Models In Stock
Product Overview
- Applications Bins, Chutes, High or Low level detection, Hoppers, Silos, Tanks
- Electrical Connection 3/4 in NPT female Conduit with Screw Terminal block
- Enclosure Ratings Dust Tight, IP66, NEMA Type 4X, Water Resistant
- Materials, Wetted CPVC
- Media Compatibility Dry bulk solids / powders, Liquids, Slurries / sludge
- Mounting Orientation Horizontal, Vertical
- Operating Temperature, Max 185 °F
- Operating Temperature, Min -40 °F
- Power Consumption 1.5 VA
- Process Connection Size 1 in
- Process Connection Type NPS Male
- Process Temperature, Max 240 °F
- Process Temperature, Min -40 °F
- Sensitivity Adjustable to < 1 pF
- Sensor Break Detection Switch selectable, high/low
- Series ID Model-CLS1
- Supply Power Type AC
- Supply Voltage 120 Vac
- Switch Rating 5 (8) A @ 250 Vac
- Time Delay 1 to 30 s
- Weight 2 lb
Supported Applications
The Model CLS1 Capacitance Level Switch provides reliable point level measurement of solids, liquids, and slurries in metallic or non-metallic tanks and vessels. The unit detects the presence or absence of material by sensing a change in capacitance when material contacts the probe.
Operating Conditions & Performance
The series operates within an ambient temperature range of -40 to 185°F (-40 to 85°C) and supports process temperatures from -40 to 240°F (-40 to 116°C). The electronics provide highly sensitive measurement detection requiring less than a 1 picofarad shift from ambient. A fail-safe relay output is selectable for high or low level indication, with an adjustable time delay ranging from 1 to 30 seconds.
Configuration Options
The Model CLS1 features a PVC enclosure rated NEMA 4X (IP66), described as dust tight and water resistant. Wetted materials consist of CPVC, compatible with solids, liquids, or slurries. The unit mounts vertically or horizontally via a 1" male NPS process connection.
Electrical specifications include:
- Power Supply: 120 VAC, 1.5 VA
- Output Signal: SPDT fail-safe relay output rated at 5 A @ 250 VAC
- Conduit Connection: 1/2" female NPT
Sensitivity is adjustable via a single multi-turn potentiometer. Calibration settings correspond to sensitivity levels as follows:
- HIGH sensitivity: 1/8 to 1/2 turn
- MEDIUM sensitivity: 1/2 to 1 turn
- LOW sensitivity: 1 turn or more
A red LED on the housing indicates sensor status. The unit weighs 2.0 lb (0.91 kg).
Key Product Differences
The Model CLS1 is a single model designation for this capacitance level switch series. Configuration options include selectable fail-safe modes and adjustable time delays to accommodate specific process requirements.
PDFs & Manuals